1. SPECIFICATIONS HEAT SOURCE
I.WY SERIES1. SPECIFICATIONS
Model PQHY-P200YLM-A
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 22.4
(Nominal) kcal/h 20,000
*1 BTU/h 76,400
Power input kW 3.71
Current input A 6.2-5.9-5.7
EER kW/kW 6.03
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Circulating water °C 10.0~45.0°C (50~113°F)
Heating capacity *2 kW 25.0
(Nominal) kcal/h 21,500
*2 BTU/h 85,300
Power input kW 3.97
Current input A 6.7-6.3-6.1
COP kW/kW 6.29
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating Circulating water °C 10.0~45.0°C (50~113°F)
Indoor unit Total capacity 50~130% of heat source unit capacity
connectable Model/Quantity P15~P250/1~17
Sound pressure level (measured in anechoic room) dB <A> 46
Sound power level (measured in anechoic room) dB <A> 60
Refrigerant Liquid pipe mm (in.) 9.52 (3/8) Brazed
piping diameter Gas pipe mm (in.) 19.05 (3/4) Brazed
Circulating water Water flow rate m3/h 5.76
L/min 96
cfm 3.4
Pressure drop kPa 24
Operating volume range m3/h 3.0 ~ 7.2
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 4.8
Case heater kW -
Lubricant MEL32
External finish Galvanized steel sheets
External dimension H x W x D mm 1,100 x 880 x 550
in. 43-5/16 x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection
Compressor Over-heat protection
Refrigerant Type x original charge R410A x 5.0 kg (12 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 174 (384)
Heat exchanger plate type
Water volume in plate I 5.0
Water pressure Max. MPa 2.0
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKS94C746
Wiring WKE94G131
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104, 108, 1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the heat source unit needs to be kept below 40°C D.B.
The ambient relative humidity of the heat source unit needs to be kept below 80%.
The heat source unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Water temperature: 30°C (86°F)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.) ,Water temperature: 20°C (68°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is
subject to rounding variation.