1.2 Outdoor air processing unit (FDU-F)
Models FDU650FKXZE1, 1100FKXZE1, 1800FKXZE1, 2400FKXZE1
Models FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1
Nominal cooling capacity kW 9.0 14.0 22.4 28.0
Nominal heating capacity 6.5
55
10.5
62
16.0
68
21.5
70
Power source 220-240V 50Hz / 220V 60Hz 220-240V 50Hz / 220V 60Hz 220-240V 50Hz / 220V 60Hz 220-240V 50Hz / 220V 60Hz
Power consumption Cooling kW 0.24 - 0.25 / 0.24 0.35 - 0.36 / 0.35 1.16 - 1.20 / 1.16 1.16 - 1.20 / 1.16
Heating 0.24 - 0.25 / 0.24 0.35 - 0.36 / 0.35 1.16 - 1.20 / 1.16 1.16 - 1.20 / 1.16
Running current Cooling A1.80 - 1.70 / 1.80 2.30 - 2.20 / 2.30 6.80 - 6.50 / 6.80 6.80 - 6.50 / 6.80
Heating 1.80 - 1.70 / 1.80 2.30 - 2.20 / 2.30 6.80 - 6.50 / 6.80 6.80 - 6.50 / 6.80
Sound pressure level dB(A)
Sound power level dB(A)
Hi:31
Hi:37
Hi:42
Hi:45
Exterior dimensions
Height x Width x Depth mm 280 × 950 × 635 280 × 1,370 × 740 379 × 1,600 × 893 379 × 1,600 × 893
Net weight kg 34 54 89 89
Refrigerant equipment
Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Air handling equipment
Fan type & Q'ty Centrifugal fan × 2 Centrifugal fan × 3 Centrifugal fan × 3 Centrifugal fan × 3
Motor W 130 100 + 200 130 + 350 130 + 350
Starting method Direct line start Direct line start Direct line start Direct line start
Air flow(Standard) m3/min Hi:11
Hi:18
Hi:30 Hi:40
External static pressure Pa 200 (at 11 m3/min) 200 (at 18 m3/min) 200 (at 30 m3/min) 200 (at 40 m3/min)
Outside air intake Possible Possible Possible Possible
Air filter, Q'ty Procure locally Procure locally Procure locally Procure locally
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor) Rubber sleeve (for fan motor) Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control
Operation switch
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Safety equipment Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Installation data
Refrigerant piping size
Liquid line: φ9.52 (3/8")
Gas line: φ15.88 (5/8")
Liquid line: φ9.52 (3/8")
Gas line: φ15.88 (5/8")
Liquid line: φ9.52 (3/8")
Gas line: φ19.05 (3/4")
Liquid line: φ9.52 (3/8")
Gas line: φ22.22 (7/8")
Connecting method Flare piping Flare piping Brazing Brazing
Refrigerant R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump ー ー
Drain hose Connectable with VP25 (Standard) Connectable with VP25 (Standard) Connectable with VP25 (Standard) Connectable with VP25 (Standard)
Insulation for piping Necessary (both Liquid & Gas line) Necessary (both Liquid & Gas line) Necessary (both Liquid & Gas line) Necessary (both Liquid & Gas line)
Accessories Drain hose Drain hose Drain hose Drain hose
(1) The data are measured at 33℃DB 28℃WB (68%RH) during cooling and 0℃DB -2.9℃WB (50%RH) during heating (no frost).
Adapted to RoHS directive
PJG000Z293 C
Wireless: RCN-KIT3-E Wireless: RCN-KIT3-E Wireless: RCN-KIT3-E Wireless: RCN-KIT3-E
Notes
(2) Temperature range of outdoor air must be 20 - 40℃DB (32℃WB or less) during cooling and -10℃- 24 ℃DB during heating.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) The factory E.S.P. setting is set within the range of 10 -120Pa. When SW8-4 is turned to “ON”, E.S.P. setting range can be changed to 10 -200Pa. (For RC-EX1A and RC-E5 only)