7
-
'21 • KX-T-386
A
PJG000Z759
Models FDUM71KXE6F-W, 90KXE6F-W, 112KXE6F-W, 140KXE6F-W, 160KXE6F-W
Model FDUM71KXE6F-W FDUM90KXE6F-W FDUM112KXE6F-W FDUM140KXE6F-W FDUM160KXE6F-W
Nominal cooling capacity*1 kW 7.1 9.0 11.2 14.0 16.0
Nominal heating capacity*2 8.0 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Power consumption
Cooling
kW 0.160 - 0.160 / 0.160 0.160 - 0.160 / 0.160 0.250 - 0.250 / 0.250 0.260 - 0.260 / 0.260 0.380 - 0.380 / 0.380
Heating
0.160 - 0.160 / 0.160 0.160 - 0.160 / 0.160 0.250 - 0.250 / 0.250 0.260 - 0.260 / 0.260 0.380 - 0.380 / 0.380
Running current
Cooling
A1.41 - 1.29 / 1.41 1.41 - 1.29 / 1.41 1.62 - 1.49 / 1.62 1.68 - 1.54 / 1.68 2.30 - 2.11 / 2.30
Heating
1.41 - 1.29 / 1.41 1.41 - 1.29 / 1.41 1.62 - 1.49 / 1.62 1.68 - 1.54 / 1.68 2.30 - 2.11 / 2.30
Sound pressure level
Cooling
dB(A)
P-Hi
:
37 Hi
:
31 Me
:
27 Lo
:
22 P-Hi
:
37 Hi
:
31 Me
:
27 Lo
:
22 P-Hi
:
40 Hi
:
36 Me
:
34 Lo
:
28 P-Hi
:
41 Hi
:
37 Me
:
34 Lo
:
28 P-Hi
:
45 Hi
:
38 Me
:
34 Lo
:
29
Heating
P-Hi
:
39 Hi
:
33 Me
:
28 Lo
:
23 P-Hi
:
39 Hi
:
33 Me
:
28 Lo
:
23 P-Hi
:
41 Hi
:
36 Me
:
34 Lo
:
28 P-Hi
:
41 Hi
:
37 Me
:
34 Lo
:
28 P-Hi
:
45 Hi
:
38 Me
:
34 Lo
:
29
Sound power level
Cooling
63 63 68 68 72
Heating
65 65 69 69 72
Exterior dimensions
Height x Width x Depth mm 280 × 950 × 635 280 × 950 × 635 280 × 1,368 × 740 280 × 1,368 × 740 280 × 1,368 × 740
Net weight kg 34 34 54 54 54
Refrigerant equipment Heat exchanger
Louver n & inner grooved tubing Louver n & inner grooved tubing Louver n & inner grooved tubing Louver n & inner grooved tubing Louver n & inner grooved tubing
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Air handling equipment Fan type & Q'ty
Centrifugal fan ×2 Centrifugal fan ×2 Centrifugal fan ×3 Centrifugal fan ×3 Centrifugal fan ×3
Fan motor <Starting method>
W 130 < Direct line start > 130 < Direct line start > 100 + 130 < Direct line start > 100 + 200 < Direct line start > 100 + 200 < Direct line start >
Air ow(Standard)
Cooling
m3/min
P-Hi
:
24 Hi
:
19 Me
:
15 Lo
:
10 P-Hi
:
24 Hi
:
19 Me
:
15 Lo
:
10 P-Hi
:
36 Hi
:
28 Me
:
25 Lo
:
19 P-Hi
:
39 Hi
:
32 Me
:
26 Lo
:
20 P-Hi
:
48 Hi
:
35 Me
:
28 Lo
:
22
Heating
P-Hi
:
24 Hi
:
19 Me
:
15 Lo
:
10 P-Hi
:
24 Hi
:
19 Me
:
15 Lo
:
10 P-Hi
:
36 Hi
:
28 Me
:
25 Lo
:
19 P-Hi
:
39 Hi
:
32 Me
:
26 Lo
:
20 P-Hi
:
48 Hi
:
35 Me
:
28 Lo
:
22
Available static pressure Pa 100 (at 24 m3/min) 100 (at 24 m3/min) 100 (at 36 m3/min) 100 (at 39 m3/min) 100 (at 48 m3/min)
Outdoor air intake Possible Possible Possible Possible Possible
Air lter, Q'ty Procure locally Procure locally Procure locally Procure locally Procure locally
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (Noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control
Remote control switch (Option)
Wired : RC-EX3A,RC-E5,RCH-E3
Wireless : RCN-KIT4-E2
Wired : RC-EX3A,RC-E5,RCH-E3
Wireless : RCN-KIT4-E2
Wired : RC-EX3A,RC-E5,RCH-E3
Wireless : RCN-KIT4-E2
Wired : RC-EX3A,RC-E5,RCH-E3
Wireless : RCN-KIT4-E2
Wired : RC-EX3A,RC-E5,RCH-E3
Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Safety equipment Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Installation data Liquid line
Refrigerant piping size
Gas line
φ9.52 (3/8") <Flare piping>
φ15.88 (5/8") <Flare piping>
φ9.52 (3/8") <Flare piping>
φ15.88 (5/8") <Flare piping>
φ9.52 (3/8") <Flare piping>
φ15.88 (5/8") <Flare piping>
φ9.52 (3/8") <Flare piping>
φ15.88 (5/8") <Flare piping>
φ9.52 (3/8") <Flare piping>
φ15.88 (5/8") <Flare piping>
Refrigerant R32 R32 R32 R32 R32
Drain pump Built-in drain pump Built-in drain pump Built-in drain pump Built-in drain pump Built-in drain pump
Drain hose Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJG000Z761 PJG000Z761 PJG000Z762 PJG000Z762 PJG000Z762
Electrical wiring PJG000Z764 PJG000Z764 PJG000Z765 PJG000Z765 PJG000Z765
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) Initial static pressure values of optional air lter "UM-FL□EF" are 5Pa.
(5) Select the breaker size according to the own national standard.
Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Standards
External static pressure of
indoor unit (Pa)
Operation DB WB DB WB
Cooling*1 27℃19℃35℃24℃ISO-T1
35(FDUM71),47(FDUM90,112)
60(FDUM140,160)
Heating*2 20℃7℃6℃
OPTION Model Specication
Remote
control
Wired RC-EX3A PJZ000Z333
Wired RC-E5 PJZ000Z295
Wired RCH-E3 PJZ000Z272
Wireless RCN-KIT4-E2 PJZ000Z323
Motion sensor LB-KIT2 PJZ000Z341
Air lter (For 71-90) UM-FL2EF -
Air lter (For 112-160) UM-FL3EF -