Mitsubishi FX2N-32CCL-NP User manual

FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL BLOCK
HARDWARE MANUAL
JY992D96001A
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX2N-32CCL-NP CC-Link SYSTEM LOCAL BLOCK. It should be read and
understood before attempting to install or use the unit. Further information can be found in the FX series
PLC hardware manuals.
Note’s on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the user’s personal safety and protect the integrity of the equipment.
Whenever any of the following symbols are encountered, its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
1. INTRODUCTION
The FX2N-32CCL-NP is the interface block that connects the FX series PLC to the CC-Link system.
It is connected as a local station.
Master station .................Station which controls the remote I/O station, remote device station, and local
stations
Remote I/O station..........Remote station which handles only on/off data
Remote device station ....Remote station which handles both on/off data and numeric data
Local station....................Station which has a CPU and can communicate with the master station and
other local stations
Protocolinterface
FX
2N
-232AW C-NP
R e m o te I/O s ta tio n
FX
2N
PLC
M asterStation
AJ65BT-G4
RS-422 RS-232C
Program m ing
softw are
Powersupply
FX
2N
PLC
C C -Link
FX
2N
-3 2 C C L
-N P
FX
2N
-3 2 C C L -N P
Program cable Program cable
1.1 Dimensions and Setting
Dimensions: mm (inches) MASS (Weight): 0.4 kg (0.88 lbs)
Number Name Description
1) LED
indicators 1 LED
name Description LED status
Normal Error
RUN ON : Module is normal.
OFF: Watchdog timer error has occurred. ON OFF
ERR.
Indicates the communication status with
the stations set in the parameters.
ON : Communication error has
occurred in all stations.
Flashing : Communication error has
occurred in some stations.
OFF ON or
flashing
L RUN ON : Data link is being executed
(host station). ON OFF
L ERR.
ON : Communication error has
occurred (host station).
Flashing : The settings of the switches 4)
to 7) are changed while the
power is ON.
OFF ON or
flashing
2) Power indictor POWER ON : 24V DC is supplied from the outside. ON OFF
3) LED
indicators 2 SW ERR. ON : Switch setting error has occurred. OFF ON
TEST 1 Test result indication OFF except during testTEST 2
TEST 3
LINE ERR.
ON : The cable is broken the transmission
route is affected by noise, etc. OFF ON
SD ON : Data is being transmitted. ON OFF
RD ON : Data is being received. ON OFF
4)
Station
numbersetting
switch
Sets the station number of the module. (Default setting at shipment: 00)
<Setting range>
Local station : 1 to 64
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn ON.
5) Mode setting
switch Sets the operation status of the module. (Default setting at shipment: 0)
Number Name Description
0 Online Sets connection to data link.
1 (Unusable)
2 Offline Sets disconnection from data link.
3 (Unusable)
4 (Unusable)
5 (Unusable)
6 Hardware test
7 (Unusable) Setting error (The SW LED indicator turns ON.)
8 to A (Unusable) Used in PLC internal operations.
B to F (Unusable) Setting error (The SW LED indicator turns ON.)
6) Transmission
speed setting
switch
Sets the transmission speed of the module. (Default setting at shipment: 0)
Number Setting contents
0 156 kbps
1 625 kbps
2 2.5 Mbps
3 5 Mbps
4 10 Mbps
5 to 9 Setting error (The SW and L ERR. LED indicators turn ON.)
RUN
ERR.
L E R R .
L R U N
POW ER
SW ERR.
TEST 1
TEST 2
TEST 3
LIN E ER R .
SD
RD
×10
×1
STATION
NO.
MODE
B RATE
1
3
2
4
156K
625K
2.5M
5M
10M
0
HLD
41
ONOFF
SW
1
2
3
--
-
-
-
-
4
5
6
7
8
-
-
--
-
-
CLR
FX
2N
-3 2 C C L -N P
0
1
2
3
4
5
6
7
8
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
12345678
ON
RUN
ERR.
L R U N
L E R R .
POW ER
SW ERR.
TEST 1
TEST 2
TEST 3
LIN E ER R .
SD
RD
85(3.34)
90(3.5)
87(3.43)
9(0.35)
FX2N -3 2 C C L -N P
2-
φ4.5
80(3.15)
75(2.95)
MITSUBISHI
1)
2)
3)
4)
5)
6)
8)
7)
9)
10)
11)
13)
Inside oftop cover
24+
24-
FG
SLD D G DA DB
12)
RUN
ERR.
L RUN
L ERR
SW ERR.
TEST 1
TEST 2
TEST 3
LINE ERR.
SD
RD
STATION NO.
×10
×1
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
MODE
12
3
4
5
6
7
8
9
0
A
B
C
D
E
F
B RATE
0
2
1
3
4
156K
625K
2.5M
5M
10M
1
2
3
4
5
6
7
8
9
0
2. Installation and wiring
INSTALLATION PRECAUTIONS
• Use the module in the environment described in the HARDWARE MANUAL General Specification.
Do not use the PLC in a place with dust, soot, conductive dust, corrosive gas or combustible gas,
place exposed to high temperature, condensation, wind or rain or place with vibration or impact.
Using the module outside the range of the general specification may result in electrical shock, fire,
malfunctions, or may damage the PLC.
• When drilling screw holes or performing wiring, make sure that cutting chips, wire chips or
other foreign matter does not enter the ventilation window of the module.
Such matter may cause fire, failure or malfunction.
• When the installation work is completed, remove the dust protection sheet from the ventilation
window of the PLC.
If the sheet remains attached, it may cause fire, failure or malfunction.
• Securely connect extension cables to specified connectors.
Poor contact may cause malfunction.
WIRING PRECAUTIONS
• Before beginning any installation or wiring work, make sure all phases of the power supply
have been shut down from the outside.
Incomplete shutdown of thepower supply phases may cause electrical shock or damage in the
module.
• Following an installation or wiring work, when turning on the power supply and operating the
PLC, make sure that the terminal cover provided as an accessory has been attached to the
module.
A missing cover may cause electrical shock.
• For the CC-Link system, use dedicated cables specified by the manufacturer.
The performance of the CC-Link system cannot be guaranteed with any cable other than the
ones specified by the manufacturer.
With wiring outside the specification range, normal data transfer cannot be guaranteed.
• Make sure to fix communication cables and power cables connected to the module by placing
them in the duct or clamping them.
Cables not placed in duct or not clamped may hang or shift, allowing them to be accidentally
pulled, which may result in malfunction or damage to the module and the cables.
• The number of times to disconnect/connect the program cable for FX2N-32CCL-NP should be
kept to a minimum.
7) Condition
setting switch Sets the operation condition. (Default setting at shipment: All OFF)
Number Setting description Switch status
ON OFF
SW1 to
SW3 (Unusable) Always OFF
SW4 Input data status in data link faulty station Keep
(HLD) Clear
(CLR)
SW5 Number of occupied stations 4 1
SW6 to
SW8 (Unusable) Always OFF
8) Terminal block Connects dedicated CC-Link cables to enable data link. For the connection
method, refer to Section 2.3.
The terminals SLD and FG are connected inside.
9) Terminal block Connects the power supply to operate the master block.
10) Extensionbus
cable Connects the PLC.
11) Expansion
bus port Connects an extension equipment.
12) Program
port A connector for program cable
13) DIN rail
mounting
groove DIN46277: DIN rail mounting groove of 35 mm (1.38") in width
Number Name Description
HLD
1
SW
ON
CLR 4
OFF ON
12345678
2
1
3
4
6
5
7
8
SLD DG DA DB
24+
24-
FG
Guidelines for the safety of the user and protection of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK
• If in doubt at any stage during the installation of the FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL
BLOCK always consult a professional electrical engineer who is qualified and trained to the local
and national standards. If in doubt about the operation or use of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK please consult the nearest Mitsubishi Electric distributor.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.
Industrialautomation
Elincom Group
EuropeanUnion: www.elinco.eu
Russia:www.elinc.ru

FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL BLOCK
HARDWARE MANUAL
JY992D96001A
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX2N-32CCL-NP CC-Link SYSTEM LOCAL BLOCK. It should be read and
understood before attempting to install or use the unit. Further information can be found in the FX series
PLC hardware manuals.
Note’s on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the user’s personal safety and protect the integrity of the equipment.
Whenever any of the following symbols are encountered, its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
1. INTRODUCTION
The FX2N-32CCL-NP is the interface block that connects the FX series PLC to the CC-Link system.
It is connected as a local station.
Master station .................Station which controls the remote I/O station, remote device station, and local
stations
Remote I/O station..........Remote station which handles only on/off data
Remote device station ....Remote station which handles both on/off data and numeric data
Local station....................Station which has a CPU and can communicate with the master station and
other local stations
Protocolinterface
FX
2N
-232AW C-NP
R e m o te I/O s ta tio n
FX
2N
PLC
M asterStation
AJ65BT-G4
RS-422 RS-232C
Program m ing
softw are
Powersupply
FX
2N
PLC
C C -Link
FX
2N
-3 2 C C L
-N P
FX
2N
-3 2 C C L -N P
Program cable Program cable
1.1 Dimensions and Setting
Dimensions: mm (inches) MASS (Weight): 0.4 kg (0.88 lbs)
Number Name Description
1) LED
indicators 1 LED
name Description LED status
Normal Error
RUN ON : Module is normal.
OFF: Watchdog timer error has occurred. ON OFF
ERR.
Indicates the communication status with
the stations set in the parameters.
ON : Communication error has
occurred in all stations.
Flashing : Communication error has
occurred in some stations.
OFF ON or
flashing
L RUN ON : Data link is being executed
(host station). ON OFF
L ERR.
ON : Communication error has
occurred (host station).
Flashing : The settings of the switches 4)
to 7) are changed while the
power is ON.
OFF ON or
flashing
2) Power indictor POWER ON : 24V DC is supplied from the outside. ON OFF
3) LED
indicators 2 SW ERR. ON : Switch setting error has occurred. OFF ON
TEST 1 Test result indication OFF except during testTEST 2
TEST 3
LINE ERR.
ON : The cable is broken the transmission
route is affected by noise, etc. OFF ON
SD ON : Data is being transmitted. ON OFF
RD ON : Data is being received. ON OFF
4)
Station
numbersetting
switch
Sets the station number of the module. (Default setting at shipment: 00)
<Setting range>
Local station : 1 to 64
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn ON.
5) Mode setting
switch Sets the operation status of the module. (Default setting at shipment: 0)
Number Name Description
0 Online Sets connection to data link.
1 (Unusable)
2 Offline Sets disconnection from data link.
3 (Unusable)
4 (Unusable)
5 (Unusable)
6 Hardware test
7 (Unusable) Setting error (The SW LED indicator turns ON.)
8 to A (Unusable) Used in PLC internal operations.
B to F (Unusable) Setting error (The SW LED indicator turns ON.)
6) Transmission
speed setting
switch
Sets the transmission speed of the module. (Default setting at shipment: 0)
Number Setting contents
0 156 kbps
1 625 kbps
2 2.5 Mbps
3 5 Mbps
4 10 Mbps
5 to 9 Setting error (The SW and L ERR. LED indicators turn ON.)
RUN
ERR.
L E R R .
L R U N
POW ER
SW ERR.
TEST 1
TEST 2
TEST 3
LIN E ER R .
SD
RD
×10
×1
STATION
NO.
MODE
B RATE
1
3
2
4
156K
625K
2.5M
5M
10M
0
HLD
41
ONOFF
SW
1
2
3
--
-
-
-
-
4
5
6
7
8
-
-
--
-
-
CLR
FX
2N
-3 2 C C L -N P
0
1
2
3
4
5
6
7
8
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
12345678
ON
RUN
ERR.
L R U N
L E R R .
POW ER
SW ERR.
TEST 1
TEST 2
TEST 3
LIN E ER R .
SD
RD
85(3.34)
90(3.5)
87(3.43)
9(0.35)
FX2N -3 2 C C L -N P
2-
φ4.5
80(3.15)
75(2.95)
MITSUBISHI
1)
2)
3)
4)
5)
6)
8)
7)
9)
10)
11)
13)
Inside oftop cover
24+
24-
FG
SLD D G DA DB
12)
RUN
ERR.
L RUN
L ERR
SW ERR.
TEST 1
TEST 2
TEST 3
LINE ERR.
SD
RD
STATION NO.
×10
×1
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
MODE
12
3
4
5
6
7
8
9
0
A
B
C
D
E
F
B RATE
0
2
1
3
4
156K
625K
2.5M
5M
10M
1
2
3
4
5
6
7
8
9
0
2. Installation and wiring
INSTALLATION PRECAUTIONS
• Use the module in the environment described in the HARDWARE MANUAL General Specification.
Do not use the PLC in a place with dust, soot, conductive dust, corrosive gas or combustible gas,
place exposed to high temperature, condensation, wind or rain or place with vibration or impact.
Using the module outside the range of the general specification may result in electrical shock, fire,
malfunctions, or may damage the PLC.
• When drilling screw holes or performing wiring, make sure that cutting chips, wire chips or
other foreign matter does not enter the ventilation window of the module.
Such matter may cause fire, failure or malfunction.
• When the installation work is completed, remove the dust protection sheet from the ventilation
window of the PLC.
If the sheet remains attached, it may cause fire, failure or malfunction.
• Securely connect extension cables to specified connectors.
Poor contact may cause malfunction.
WIRING PRECAUTIONS
• Before beginning any installation or wiring work, make sure all phases of the power supply
have been shut down from the outside.
Incomplete shutdown of thepower supply phases may cause electrical shock or damage in the
module.
• Following an installation or wiring work, when turning on the power supply and operating the
PLC, make sure that the terminal cover provided as an accessory has been attached to the
module.
A missing cover may cause electrical shock.
• For the CC-Link system, use dedicated cables specified by the manufacturer.
The performance of the CC-Link system cannot be guaranteed with any cable other than the
ones specified by the manufacturer.
With wiring outside the specification range, normal data transfer cannot be guaranteed.
• Make sure to fix communication cables and power cables connected to the module by placing
them in the duct or clamping them.
Cables not placed in duct or not clamped may hang or shift, allowing them to be accidentally
pulled, which may result in malfunction or damage to the module and the cables.
• The number of times to disconnect/connect the program cable for FX2N-32CCL-NP should be
kept to a minimum.
7) Condition
setting switch Sets the operation condition. (Default setting at shipment: All OFF)
Number Setting description Switch status
ON OFF
SW1 to
SW3 (Unusable) Always OFF
SW4 Input data status in data link faulty station Keep
(HLD) Clear
(CLR)
SW5 Number of occupied stations 4 1
SW6 to
SW8 (Unusable) Always OFF
8) Terminal block Connects dedicated CC-Link cables to enable data link. For the connection
method, refer to Section 2.3.
The terminals SLD and FG are connected inside.
9) Terminal block Connects the power supply to operate the master block.
10) Extensionbus
cable Connects the PLC.
11) Expansion
bus port Connects an extension equipment.
12) Program
port A connector for program cable
13) DIN rail
mounting
groove DIN46277: DIN rail mounting groove of 35 mm (1.38") in width
Number Name Description
HLD
1
SW
ON
CLR 4
OFF ON
12345678
2
1
3
4
6
5
7
8
SLD DG DA DB
24+
24-
FG
Guidelines for the safety of the user and protection of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK
• If in doubt at any stage during the installation of the FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL
BLOCK always consult a professional electrical engineer who is qualified and trained to the local
and national standards. If in doubt about the operation or use of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK please consult the nearest Mitsubishi Electric distributor.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.

FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL BLOCK
HARDWARE MANUAL
JY992D96001A
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX2N-32CCL-NP CC-Link SYSTEM LOCAL BLOCK. It should be read and
understood before attempting to install or use the unit. Further information can be found in the FX series
PLC hardware manuals.
Note’s on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the user’s personal safety and protect the integrity of the equipment.
Whenever any of the following symbols are encountered, its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
1. INTRODUCTION
The FX2N-32CCL-NP is the interface block that connects the FX series PLC to the CC-Link system.
It is connected as a local station.
Master station .................Station which controls the remote I/O station, remote device station, and local
stations
Remote I/O station..........Remote station which handles only on/off data
Remote device station ....Remote station which handles both on/off data and numeric data
Local station....................Station which has a CPU and can communicate with the master station and
other local stations
Protocolinterface
FX
2N
-232AW C-NP
R e m o te I/O s ta tio n
FX
2N
PLC
M asterStation
AJ65BT-G4
RS-422 RS-232C
Program m ing
softw are
Powersupply
FX
2N
PLC
C C -Link
FX
2N
-3 2 C C L
-N P
FX
2N
-3 2 C C L -N P
Program cable Program cable
1.1 Dimensions and Setting
Dimensions: mm (inches) MASS (Weight): 0.4 kg (0.88 lbs)
Number Name Description
1) LED
indicators 1 LED
name Description LED status
Normal Error
RUN ON : Module is normal.
OFF: Watchdog timer error has occurred. ON OFF
ERR.
Indicates the communication status with
the stations set in the parameters.
ON : Communication error has
occurred in all stations.
Flashing : Communication error has
occurred in some stations.
OFF ON or
flashing
L RUN ON : Data link is being executed
(host station). ON OFF
L ERR.
ON : Communication error has
occurred (host station).
Flashing : The settings of the switches 4)
to 7) are changed while the
power is ON.
OFF ON or
flashing
2) Power indictor POWER ON : 24V DC is supplied from the outside. ON OFF
3) LED
indicators 2 SW ERR. ON : Switch setting error has occurred. OFF ON
TEST 1 Test result indication OFF except during testTEST 2
TEST 3
LINE ERR.
ON : The cable is broken the transmission
route is affected by noise, etc. OFF ON
SD ON : Data is being transmitted. ON OFF
RD ON : Data is being received. ON OFF
4)
Station
numbersetting
switch
Sets the station number of the module. (Default setting at shipment: 00)
<Setting range>
Local station : 1 to 64
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn ON.
5) Mode setting
switch Sets the operation status of the module. (Default setting at shipment: 0)
Number Name Description
0 Online Sets connection to data link.
1 (Unusable)
2 Offline Sets disconnection from data link.
3 (Unusable)
4 (Unusable)
5 (Unusable)
6 Hardware test
7 (Unusable) Setting error (The SW LED indicator turns ON.)
8 to A (Unusable) Used in PLC internal operations.
B to F (Unusable) Setting error (The SW LED indicator turns ON.)
6) Transmission
speed setting
switch
Sets the transmission speed of the module. (Default setting at shipment: 0)
Number Setting contents
0 156 kbps
1 625 kbps
2 2.5 Mbps
3 5 Mbps
4 10 Mbps
5 to 9 Setting error (The SW and L ERR. LED indicators turn ON.)
RUN
ERR.
L E R R .
L R U N
POW ER
SW ERR.
TEST 1
TEST 2
TEST 3
LIN E ER R .
SD
RD
×10
×1
STATION
NO.
MODE
B RATE
1
3
2
4
156K
625K
2.5M
5M
10M
0
HLD
41
ONOFF
SW
1
2
3
--
-
-
-
-
4
5
6
7
8
-
-
--
-
-
CLR
FX
2N
-3 2 C C L -N P
0
1
2
3
4
5
6
7
8
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
12345678
ON
RUN
ERR.
L R U N
L E R R .
POW ER
SW ERR.
TEST 1
TEST 2
TEST 3
LIN E ER R .
SD
RD
85(3.34)
90(3.5)
87(3.43)
9(0.35)
FX2N -3 2 C C L -N P
2-
φ4.5
80(3.15)
75(2.95)
MITSUBISHI
1)
2)
3)
4)
5)
6)
8)
7)
9)
10)
11)
13)
Inside oftop cover
24+
24-
FG
SLD D G DA DB
12)
RUN
ERR.
L RUN
L ERR
SW ERR.
TEST 1
TEST 2
TEST 3
LINE ERR.
SD
RD
STATION NO.
×10
×1
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
MODE
12
3
4
5
6
7
8
9
0
A
B
C
D
E
F
B RATE
0
2
1
3
4
156K
625K
2.5M
5M
10M
1
2
3
4
5
6
7
8
9
0
2. Installation and wiring
INSTALLATION PRECAUTIONS
• Use the module in the environment described in the HARDWARE MANUAL General Specification.
Do not use the PLC in a place with dust, soot, conductive dust, corrosive gas or combustible gas,
place exposed to high temperature, condensation, wind or rain or place with vibration or impact.
Using the module outside the range of the general specification may result in electrical shock, fire,
malfunctions, or may damage the PLC.
• When drilling screw holes or performing wiring, make sure that cutting chips, wire chips or
other foreign matter does not enter the ventilation window of the module.
Such matter may cause fire, failure or malfunction.
• When the installation work is completed, remove the dust protection sheet from the ventilation
window of the PLC.
If the sheet remains attached, it may cause fire, failure or malfunction.
• Securely connect extension cables to specified connectors.
Poor contact may cause malfunction.
WIRING PRECAUTIONS
• Before beginning any installation or wiring work, make sure all phases of the power supply
have been shut down from the outside.
Incomplete shutdown of thepower supply phases may cause electrical shock or damage in the
module.
• Following an installation or wiring work, when turning on the power supply and operating the
PLC, make sure that the terminal cover provided as an accessory has been attached to the
module.
A missing cover may cause electrical shock.
• For the CC-Link system, use dedicated cables specified by the manufacturer.
The performance of the CC-Link system cannot be guaranteed with any cable other than the
ones specified by the manufacturer.
With wiring outside the specification range, normal data transfer cannot be guaranteed.
• Make sure to fix communication cables and power cables connected to the module by placing
them in the duct or clamping them.
Cables not placed in duct or not clamped may hang or shift, allowing them to be accidentally
pulled, which may result in malfunction or damage to the module and the cables.
• The number of times to disconnect/connect the program cable for FX2N-32CCL-NP should be
kept to a minimum.
7) Condition
setting switch Sets the operation condition. (Default setting at shipment: All OFF)
Number Setting description Switch status
ON OFF
SW1 to
SW3 (Unusable) Always OFF
SW4 Input data status in data link faulty station Keep
(HLD) Clear
(CLR)
SW5 Number of occupied stations 4 1
SW6 to
SW8 (Unusable) Always OFF
8) Terminal block Connects dedicated CC-Link cables to enable data link. For the connection
method, refer to Section 2.3.
The terminals SLD and FG are connected inside.
9) Terminal block Connects the power supply to operate the master block.
10) Extensionbus
cable Connects the PLC.
11) Expansion
bus port Connects an extension equipment.
12) Program
port A connector for program cable
13) DIN rail
mounting
groove DIN46277: DIN rail mounting groove of 35 mm (1.38") in width
Number Name Description
HLD
1
SW
ON
CLR 4
OFF ON
12345678
2
1
3
4
6
5
7
8
SLD DG DA DB
24+
24-
FG
Guidelines for the safety of the user and protection of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK
• If in doubt at any stage during the installation of the FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL
BLOCK always consult a professional electrical engineer who is qualified and trained to the local
and national standards. If in doubt about the operation or use of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK please consult the nearest Mitsubishi Electric distributor.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.

HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 TELEX : J24532 CABLE MELCO TOKYO
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
• When disconnecting a communication/power cable connected to the module, do not hold the
cable area.
For a cable with connector, hold the connector attached to the module.
For a cable connected to a terminal block, loosen screws of the terminal block,then disconnect
the cable.
If a cable is pulled while it is connected to a module, the module may malfunction or the
module and the cable may be damaged.
WIRING PRECAUTIONS
• Perform Class D grounding (solid grounding) with a wire of 2 mm2or more to the grounding
terminal in the PLC main units. However, never perform common grounding with a high voltage
system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
2.1 Installation
Install the FX
2N
-32CCL-NP on the right side of an FX
2N
Series main unit, extension unit, or other extension
block.
The FX
2N
-32CCL-NP can be installed using a DIN rail (DIN 46277, width: 35 mm (1.38 in.)) or directly with
M4 (0.16 in.) screws.
In the case of direct installation, provide space of 1 to 2 mm (0.04 to 0.08 in.) between units.
2.2 Dedicated CC-Link Cable
Use dedicated CC-Link cables in the CC-Link system.
If any other cable is used, the performance of the CC-Link system cannot be guaranteed.
2.3 Module Wiring with Dedicated CC-Link Cables
This section describes the connection method of dedicated CC-Link cables.
• The cables can be connected without regard to the station number.
• Make sure to connect a terminal resistor (offered as an accessory of the module) between the DA and
DB terminals in the modules at both ends.
• In the CC-Link system, the terminal resistor to be connected varies depending on the cable used.
- When a dedicated CC-Link cable is used: 110 Ω, 1/2 W (brown, brown and brown)
- When a dedicated high-performance CC-Link cable is used: 130 Ω, 1/2 W (brown, orange and
brown)
• Star connection is not allowed.
• The figure below shows the connection method.
Important
Make sure to use only one type of cable (dedicated CC-Link cables OR dedicated CC-Link high-
performance cables).
If both types of cables are used together, normal data transmission cannot be guaranteed.
Point
The shielded dedicated CC-Link cable should go through the terminals SLD and FG in each
module, and both ends should be grounded (Class D = solid grounding).
The terminals SLD and FG are connected inside the module.
PLC Another
equipment PLC Another
equipment
PLC Another
equipment
Common grounding
(allowed) Common grounding
(not allowed)
Dedicated grounding
(best)
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
Dedicated CC-Link cable Dedicated CC-Link cable
Master module Remote module Remote module
Terminal
resistor
Terminal
resistor
2.4 Connection diagram of program cable
Length: 1 m (3.3 ft)
3. SPECIFICATION
3.1 General Specification
Dielectric strength: 500V AC for 1 minute (between the case and the PLC ground)
Other specification is equivalent to that of the PLC main unit.
3.2 Performance Specification
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be used at the
same time. Only one type of cable can be used simultaneously.
Attach a terminal resistor in accordance with the cable type.
Item Specification
Applicable function Local station function (The master station and standby master station
functions are not provided.)
CC-Link version Ver.1.10
Transmission speed Selectable (by rotary switch) among 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps
and 10 Mbps
Station number 1 to 64 (set by rotary switch)
Maximum total cable
length (maximum
transmission distance)
1,200 m maximum
Varies depending on the transmission speed.
Number of link points
per station
Remote I/O station : Remote I/O = 32/32 (RX/RY) points
Remote device station : Remote I/O = 32/32 (RX/RY) points
Remote register = 4 (RWw) points
Remote register = 4 (RWr) points
Transmission path type Bus (RS-485)
Connection cable Dedicated CC-Link cable/Dedicated high-performance CC-Link cable *1
RAS function • Automatic return function
• Offline test
• Error detection by link special relay/register
Applicable PLC FX2N Series PLC
Number of occupied
I/O points 8 I/O points of FX Series PLC (8 points in total. The ratio between inputs and
outputs is arbitrary.)
Communication with PLC
By FROM/TO instructions via the buffer memory
Note
• Scan method: Asynchronous mode
• Automatic refresh: Not provided
• Master station function: Not provided
• Standby master station function: Not provided
Operation indication
POWER : Lit while 24V DC is supplied from outside.
L RUN : Lit while communication is normal.
L ERR : Lit when communication error has occurred.
SD : Lit while data is being transmitted.
RD : Lit while data is being received.
Program forwarding and
monitoring
With AJ65BT-G4 and FX2N-232AWC-NP, sequence programs can be
forwarded and monitored through CC-Link.
Applicable software:GX Developer
FX-PCS/WIN-E
24V DC external power
supply Supplied from 24V DC (150 mA) external terminal blocks.
5V DC internal power
supply 5V DC power is converted from the input power.
The 5V DC PLC bus is not used.
Accessories Program cable Lengths 1.0 m (3.2 ft)
Special block number label
MASS (Weight) 0.4 kg (0.88 lbs)
PLC main unit
programming
port
8
1FX2N-32CCL-NP
RUN
ERR
5
1
2
3
46
7
8
(1)
(2)
(8)
(2) (3)
(4)
(6)
(5) (5)
(6)
(1)
(3) (7)
(8)
(4)
(7)
Blue
Blue
Blue
Blue
Red
Red
Red
Red
(Case)
3.3 Buffer Memory List
3.4 I/O Signals to PLC
BFM number Item Description
Hex. Dec.
#AH to #BH #10 to #11 I/O signal Refer to 3.4
#1CH #28
FROM/TO instruction
access error judgement time
Set the FROM/TO instruction access
error judgement time
(unit:10ms).Default:200ms
#1EH #30 Model code K7041
#E0H to #15FH #224 to #351 Remote input (RX) Stores the input status from a remote
station.
#160H to #1DFH #352 to #479 Remote output (RY) Stores the output status from a
remote station.
#1E0H to #2DFH #480 to #735 Remote register(RWw) Stores the transmission data to a
remote station.
#2E0H to #3DFH #736 to #991 Remote register(RWr) Stores the received data from a
remote station.
#5E0H to #5FFH #1504 to #1535 Link special relay (SB) Stores the data link status.
#600H to #7FFH #1536 to #2047 Link special register (SW) Stores the data link status.
PLC to local block Write (when TO instruction is used)
BFM number Write bit Output signal name
Hex. Dec.
#AH #10
b0 Refresh command
b1 to b3 (Prohibited to use)
b4 Request for module reset
b5 to b15 (Prohibited to use)
#BH #11 b0 to b15 (Prohibited to use)
PLC to local block Read (when FROM instruction is used)
BFM number Read bit Input signal name
Hex. Dec.
#AH #10
b0 Module error
b1 Data link status in host station
b2 (Prohibited to use)
b3 Data link status in other stations
b4 Module reset acceptance completion
b5 to b14 (Prohibited to use)
b15 Module ready
#BH #11 b0 to b15 (Prohibited to use)
Manual number: JY992D96001
Manual revision: A
Date : April 2001
JY992D96001A Effective Apr. 2001
Specificationsare subjectto
change without notice

HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 TELEX : J24532 CABLE MELCO TOKYO
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
• When disconnecting a communication/power cable connected to the module, do not hold the
cable area.
For a cable with connector, hold the connector attached to the module.
For a cable connected to a terminal block, loosen screws of the terminal block,then disconnect
the cable.
If a cable is pulled while it is connected to a module, the module may malfunction or the
module and the cable may be damaged.
WIRING PRECAUTIONS
• Perform Class D grounding (solid grounding) with a wire of 2 mm2or more to the grounding
terminal in the PLC main units. However, never perform common grounding with a high voltage
system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
2.1 Installation
Install the FX
2N
-32CCL-NP on the right side of an FX
2N
Series main unit, extension unit, or other extension
block.
The FX
2N
-32CCL-NP can be installed using a DIN rail (DIN 46277, width: 35 mm (1.38 in.)) or directly with
M4 (0.16 in.) screws.
In the case of direct installation, provide space of 1 to 2 mm (0.04 to 0.08 in.) between units.
2.2 Dedicated CC-Link Cable
Use dedicated CC-Link cables in the CC-Link system.
If any other cable is used, the performance of the CC-Link system cannot be guaranteed.
2.3 Module Wiring with Dedicated CC-Link Cables
This section describes the connection method of dedicated CC-Link cables.
• The cables can be connected without regard to the station number.
• Make sure to connect a terminal resistor (offered as an accessory of the module) between the DA and
DB terminals in the modules at both ends.
• In the CC-Link system, the terminal resistor to be connected varies depending on the cable used.
- When a dedicated CC-Link cable is used: 110 Ω, 1/2 W (brown, brown and brown)
- When a dedicated high-performance CC-Link cable is used: 130 Ω, 1/2 W (brown, orange and
brown)
• Star connection is not allowed.
• The figure below shows the connection method.
Important
Make sure to use only one type of cable (dedicated CC-Link cables OR dedicated CC-Link high-
performance cables).
If both types of cables are used together, normal data transmission cannot be guaranteed.
Point
The shielded dedicated CC-Link cable should go through the terminals SLD and FG in each
module, and both ends should be grounded (Class D = solid grounding).
The terminals SLD and FG are connected inside the module.
PLC Another
equipment PLC Another
equipment
PLC Another
equipment
Common grounding
(allowed) Common grounding
(not allowed)
Dedicated grounding
(best)
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
Dedicated CC-Link cable Dedicated CC-Link cable
Master module Remote module Remote module
Terminal
resistor
Terminal
resistor
2.4 Connection diagram of program cable
Length: 1 m (3.3 ft)
3. SPECIFICATION
3.1 General Specification
Dielectric strength: 500V AC for 1 minute (between the case and the PLC ground)
Other specification is equivalent to that of the PLC main unit.
3.2 Performance Specification
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be used at the
same time. Only one type of cable can be used simultaneously.
Attach a terminal resistor in accordance with the cable type.
Item Specification
Applicable function Local station function (The master station and standby master station
functions are not provided.)
CC-Link version Ver.1.10
Transmission speed Selectable (by rotary switch) among 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps
and 10 Mbps
Station number 1 to 64 (set by rotary switch)
Maximum total cable
length (maximum
transmission distance)
1,200 m maximum
Varies depending on the transmission speed.
Number of link points
per station
Remote I/O station : Remote I/O = 32/32 (RX/RY) points
Remote device station : Remote I/O = 32/32 (RX/RY) points
Remote register = 4 (RWw) points
Remote register = 4 (RWr) points
Transmission path type Bus (RS-485)
Connection cable Dedicated CC-Link cable/Dedicated high-performance CC-Link cable *1
RAS function • Automatic return function
• Offline test
• Error detection by link special relay/register
Applicable PLC FX2N Series PLC
Number of occupied
I/O points 8 I/O points of FX Series PLC (8 points in total. The ratio between inputs and
outputs is arbitrary.)
Communication with PLC
By FROM/TO instructions via the buffer memory
Note
• Scan method: Asynchronous mode
• Automatic refresh: Not provided
• Master station function: Not provided
• Standby master station function: Not provided
Operation indication
POWER : Lit while 24V DC is supplied from outside.
L RUN : Lit while communication is normal.
L ERR : Lit when communication error has occurred.
SD : Lit while data is being transmitted.
RD : Lit while data is being received.
Program forwarding and
monitoring
With AJ65BT-G4 and FX2N-232AWC-NP, sequence programs can be
forwarded and monitored through CC-Link.
Applicable software:GX Developer
FX-PCS/WIN-E
24V DC external power
supply Supplied from 24V DC (150 mA) external terminal blocks.
5V DC internal power
supply 5V DC power is converted from the input power.
The 5V DC PLC bus is not used.
Accessories Program cable Lengths 1.0 m (3.2 ft)
Special block number label
MASS (Weight) 0.4 kg (0.88 lbs)
PLC main unit
programming
port
8
1FX2N-32CCL-NP
RUN
ERR
5
1
2
3
46
7
8
(1)
(2)
(8)
(2) (3)
(4)
(6)
(5) (5)
(6)
(1)
(3) (7)
(8)
(4)
(7)
Blue
Blue
Blue
Blue
Red
Red
Red
Red
(Case)
3.3 Buffer Memory List
3.4 I/O Signals to PLC
BFM number Item Description
Hex. Dec.
#AH to #BH #10 to #11 I/O signal Refer to 3.4
#1CH #28
FROM/TO instruction
access error judgement time
Set the FROM/TO instruction access
error judgement time
(unit:10ms).Default:200ms
#1EH #30 Model code K7041
#E0H to #15FH #224 to #351 Remote input (RX) Stores the input status from a remote
station.
#160H to #1DFH #352 to #479 Remote output (RY) Stores the output status from a
remote station.
#1E0H to #2DFH #480 to #735 Remote register(RWw) Stores the transmission data to a
remote station.
#2E0H to #3DFH #736 to #991 Remote register(RWr) Stores the received data from a
remote station.
#5E0H to #5FFH #1504 to #1535 Link special relay (SB) Stores the data link status.
#600H to #7FFH #1536 to #2047 Link special register (SW) Stores the data link status.
PLC to local block Write (when TO instruction is used)
BFM number Write bit Output signal name
Hex. Dec.
#AH #10
b0 Refresh command
b1 to b3 (Prohibited to use)
b4 Request for module reset
b5 to b15 (Prohibited to use)
#BH #11 b0 to b15 (Prohibited to use)
PLC to local block Read (when FROM instruction is used)
BFM number Read bit Input signal name
Hex. Dec.
#AH #10
b0 Module error
b1 Data link status in host station
b2 (Prohibited to use)
b3 Data link status in other stations
b4 Module reset acceptance completion
b5 to b14 (Prohibited to use)
b15 Module ready
#BH #11 b0 to b15 (Prohibited to use)
Manual number: JY992D96001
Manual revision: A
Date : April 2001
JY992D96001A Effective Apr. 2001
Specificationsare subjectto
change without notice

HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 TELEX : J24532 CABLE MELCO TOKYO
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
• When disconnecting a communication/power cable connected to the module, do not hold the
cable area.
For a cable with connector, hold the connector attached to the module.
For a cable connected to a terminal block, loosen screws of the terminal block,then disconnect
the cable.
If a cable is pulled while it is connected to a module, the module may malfunction or the
module and the cable may be damaged.
WIRING PRECAUTIONS
• Perform Class D grounding (solid grounding) with a wire of 2 mm2or more to the grounding
terminal in the PLC main units. However, never perform common grounding with a high voltage
system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
2.1 Installation
Install the FX
2N
-32CCL-NP on the right side of an FX
2N
Series main unit, extension unit, or other extension
block.
The FX
2N
-32CCL-NP can be installed using a DIN rail (DIN 46277, width: 35 mm (1.38 in.)) or directly with
M4 (0.16 in.) screws.
In the case of direct installation, provide space of 1 to 2 mm (0.04 to 0.08 in.) between units.
2.2 Dedicated CC-Link Cable
Use dedicated CC-Link cables in the CC-Link system.
If any other cable is used, the performance of the CC-Link system cannot be guaranteed.
2.3 Module Wiring with Dedicated CC-Link Cables
This section describes the connection method of dedicated CC-Link cables.
• The cables can be connected without regard to the station number.
• Make sure to connect a terminal resistor (offered as an accessory of the module) between the DA and
DB terminals in the modules at both ends.
• In the CC-Link system, the terminal resistor to be connected varies depending on the cable used.
- When a dedicated CC-Link cable is used: 110 Ω, 1/2 W (brown, brown and brown)
- When a dedicated high-performance CC-Link cable is used: 130 Ω, 1/2 W (brown, orange and
brown)
• Star connection is not allowed.
• The figure below shows the connection method.
Important
Make sure to use only one type of cable (dedicated CC-Link cables OR dedicated CC-Link high-
performance cables).
If both types of cables are used together, normal data transmission cannot be guaranteed.
Point
The shielded dedicated CC-Link cable should go through the terminals SLD and FG in each
module, and both ends should be grounded (Class D = solid grounding).
The terminals SLD and FG are connected inside the module.
PLC Another
equipment PLC Another
equipment
PLC Another
equipment
Common grounding
(allowed) Common grounding
(not allowed)
Dedicated grounding
(best)
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
Dedicated CC-Link cable Dedicated CC-Link cable
Master module Remote module Remote module
Terminal
resistor
Terminal
resistor
2.4 Connection diagram of program cable
Length: 1 m (3.3 ft)
3. SPECIFICATION
3.1 General Specification
Dielectric strength: 500V AC for 1 minute (between the case and the PLC ground)
Other specification is equivalent to that of the PLC main unit.
3.2 Performance Specification
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be used at the
same time. Only one type of cable can be used simultaneously.
Attach a terminal resistor in accordance with the cable type.
Item Specification
Applicable function Local station function (The master station and standby master station
functions are not provided.)
CC-Link version Ver.1.10
Transmission speed Selectable (by rotary switch) among 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps
and 10 Mbps
Station number 1 to 64 (set by rotary switch)
Maximum total cable
length (maximum
transmission distance)
1,200 m maximum
Varies depending on the transmission speed.
Number of link points
per station
Remote I/O station : Remote I/O = 32/32 (RX/RY) points
Remote device station : Remote I/O = 32/32 (RX/RY) points
Remote register = 4 (RWw) points
Remote register = 4 (RWr) points
Transmission path type Bus (RS-485)
Connection cable Dedicated CC-Link cable/Dedicated high-performance CC-Link cable *1
RAS function • Automatic return function
• Offline test
• Error detection by link special relay/register
Applicable PLC FX2N Series PLC
Number of occupied
I/O points 8 I/O points of FX Series PLC (8 points in total. The ratio between inputs and
outputs is arbitrary.)
Communication with PLC
By FROM/TO instructions via the buffer memory
Note
• Scan method: Asynchronous mode
• Automatic refresh: Not provided
• Master station function: Not provided
• Standby master station function: Not provided
Operation indication
POWER : Lit while 24V DC is supplied from outside.
L RUN : Lit while communication is normal.
L ERR : Lit when communication error has occurred.
SD : Lit while data is being transmitted.
RD : Lit while data is being received.
Program forwarding and
monitoring
With AJ65BT-G4 and FX2N-232AWC-NP, sequence programs can be
forwarded and monitored through CC-Link.
Applicable software:GX Developer
FX-PCS/WIN-E
24V DC external power
supply Supplied from 24V DC (150 mA) external terminal blocks.
5V DC internal power
supply 5V DC power is converted from the input power.
The 5V DC PLC bus is not used.
Accessories Program cable Lengths 1.0 m (3.2 ft)
Special block number label
MASS (Weight) 0.4 kg (0.88 lbs)
PLC main unit
programming
port
8
1FX2N-32CCL-NP
RUN
ERR
5
1
2
3
46
7
8
(1)
(2)
(8)
(2) (3)
(4)
(6)
(5) (5)
(6)
(1)
(3) (7)
(8)
(4)
(7)
Blue
Blue
Blue
Blue
Red
Red
Red
Red
(Case)
3.3 Buffer Memory List
3.4 I/O Signals to PLC
BFM number Item Description
Hex. Dec.
#AH to #BH #10 to #11 I/O signal Refer to 3.4
#1CH #28
FROM/TO instruction
access error judgement time
Set the FROM/TO instruction access
error judgement time
(unit:10ms).Default:200ms
#1EH #30 Model code K7041
#E0H to #15FH #224 to #351 Remote input (RX) Stores the input status from a remote
station.
#160H to #1DFH #352 to #479 Remote output (RY) Stores the output status from a
remote station.
#1E0H to #2DFH #480 to #735 Remote register(RWw) Stores the transmission data to a
remote station.
#2E0H to #3DFH #736 to #991 Remote register(RWr) Stores the received data from a
remote station.
#5E0H to #5FFH #1504 to #1535 Link special relay (SB) Stores the data link status.
#600H to #7FFH #1536 to #2047 Link special register (SW) Stores the data link status.
PLC to local block Write (when TO instruction is used)
BFM number Write bit Output signal name
Hex. Dec.
#AH #10
b0 Refresh command
b1 to b3 (Prohibited to use)
b4 Request for module reset
b5 to b15 (Prohibited to use)
#BH #11 b0 to b15 (Prohibited to use)
PLC to local block Read (when FROM instruction is used)
BFM number Read bit Input signal name
Hex. Dec.
#AH #10
b0 Module error
b1 Data link status in host station
b2 (Prohibited to use)
b3 Data link status in other stations
b4 Module reset acceptance completion
b5 to b14 (Prohibited to use)
b15 Module ready
#BH #11 b0 to b15 (Prohibited to use)
Manual number: JY992D96001
Manual revision: A
Date : April 2001
JY992D96001A Effective Apr. 2001
Specificationsare subjectto
change without notice

FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL BLOCK
HARDWARE MANUAL
JY992D96001A
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX2N-32CCL-NP CC-Link SYSTEM LOCAL BLOCK. It should be read and
understood before attempting to install or use the unit. Further information can be found in the FX series
PLC hardware manuals.
Note’s on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the user’s personal safety and protect the integrity of the equipment.
Whenever any of the following symbols are encountered, its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
1. INTRODUCTION
The FX2N-32CCL-NP is the interface block that connects the FX series PLC to the CC-Link system.
It is connected as a local station.
Master station .................Station which controls the remote I/O station, remote device station, and local
stations
Remote I/O station..........Remote station which handles only on/off data
Remote device station ....Remote station which handles both on/off data and numeric data
Local station....................Station which has a CPU and can communicate with the master station and
other local stations
Protocolinterface
FX
2N
-232AW C-NP
R e m o te I/O s ta tio n
FX
2N
PLC
M asterS tation
AJ65BT-G4
RS-422 RS-232C
Program m ing
softw are
Powersupply
FX
2N
PLC
C C -Link
FX
2N
-3 2 C C L
-N P
FX
2N
-3 2 C C L -N P
Program cable Program cable
1.1 Dimensions and Setting
Dimensions: mm (inches) MASS (Weight): 0.4 kg (0.88 lbs)
Number Name Description
1) LED
indicators 1 LED
name Description LED status
Normal Error
RUN ON : Module is normal.
OFF: Watchdog timer error has occurred. ON OFF
ERR.
Indicates the communication status with
the stations set in the parameters.
ON : Communication error has
occurred in all stations.
Flashing : Communication error has
occurred in some stations.
OFF ON or
flashing
L RUN ON : Data link is being executed
(host station). ON OFF
L ERR.
ON : Communication error has
occurred (host station).
Flashing : The settings of the switches 4)
to 7) are changed while the
power is ON.
OFF ON or
flashing
2) Power indictor POWER ON : 24V DC is supplied from the outside. ON OFF
3) LED
indicators 2 SW ERR. ON : Switch setting error has occurred. OFF ON
TEST 1 Test result indication OFF except during testTEST 2
TEST 3
LINE ERR.
ON : The cable is broken the transmission
route is affected by noise, etc. OFF ON
SD ON : Data is being transmitted. ON OFF
RD ON : Data is being received. ON OFF
4)
Station
numbersetting
switch
Sets the station number of the module. (Default setting at shipment: 00)
<Setting range>
Local station : 1 to 64
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn ON.
5) Mode setting
switch Sets the operation status of the module. (Default setting at shipment: 0)
Number Name Description
0 Online Sets connection to data link.
1 (Unusable)
2 Offline Sets disconnection from data link.
3 (Unusable)
4 (Unusable)
5 (Unusable)
6 Hardware test
7 (Unusable) Setting error (The SW LED indicator turns ON.)
8 to A (Unusable) Used in PLC internal operations.
B to F (Unusable) Setting error (The SW LED indicator turns ON.)
6) Transmission
speed setting
switch
Sets the transmission speed of the module. (Default setting at shipment: 0)
Number Setting contents
0 156 kbps
1 625 kbps
2 2.5 Mbps
3 5 Mbps
4 10 Mbps
5 to 9 Setting error (The SW and L ERR. LED indicators turn ON.)
RUN
ERR.
L ER R .
L R U N
POW ER
SW ERR.
TEST1
TEST2
TEST3
LINE E R R .
SD
RD
×10
×1
STATION
NO.
MODE
B RATE
1
3
2
4
156K
625K
2.5M
5M
10M
0
HLD
41
ONOFF
SW
1
2
3
--
-
-
-
-
4
5
6
7
8
-
-
--
-
-
CLR
FX
2N
-32 C CL -N P
0
1
2
3
4
5
6
7
8
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
12345678
ON
RUN
ERR.
L R U N
L ER R .
POW ER
SW ERR.
TEST1
TEST2
TEST3
LINE E R R .
SD
RD
85(3.34)
90(3.5)
87(3.43)
9(0.35)
FX2N -3 2 C C L -N P
2-
φ4.5
80(3.15)
75(2.95)
MITSUBISHI
1)
2)
3)
4)
5)
6)
8)
7)
9)
10)
11)
13)
Inside oftop cover
24+
24-
FG
SLD DG DA DB
12)
RUN
ERR.
L RUN
L ERR
SW ERR.
TEST 1
TEST 2
TEST 3
LINE ERR.
SD
RD
STATION NO.
×10
×1
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
MODE
12
3
4
5
6
7
8
9
0
A
B
C
D
E
F
B RATE
0
2
1
3
4
156K
625K
2.5M
5M
10M
1
2
3
4
5
6
7
8
9
0
2. Installation and wiring
INSTALLATION PRECAUTIONS
• Use the module in the environment described in the HARDWARE MANUAL General Specification.
Do not use the PLC in a place with dust, soot, conductive dust, corrosive gas or combustible gas,
place exposed to high temperature, condensation, wind or rain or place with vibration or impact.
Using the module outside the range of the general specification may result in electrical shock, fire,
malfunctions, or may damage the PLC.
• When drilling screw holes or performing wiring, make sure that cutting chips, wire chips or
other foreign matter does not enter the ventilation window of the module.
Such matter may cause fire, failure or malfunction.
• When the installation work is completed, remove the dust protection sheet from the ventilation
window of the PLC.
If the sheet remains attached, it may cause fire, failure or malfunction.
• Securely connect extension cables to specified connectors.
Poor contact may cause malfunction.
WIRING PRECAUTIONS
• Before beginning any installation or wiring work, make sure all phases of the power supply
have been shut down from the outside.
Incomplete shutdown of the power supply phases may cause electrical shock or damage in the
module.
• Following an installation or wiring work, when turning on the power supply and operating the
PLC, make sure that the terminal cover provided as an accessory has been attached to the
module.
A missing cover may cause electrical shock.
• For the CC-Link system, use dedicated cables specified by the manufacturer.
The performance of the CC-Link system cannot be guaranteed with any cable other than the
ones specified by the manufacturer.
With wiring outside the specification range, normal data transfer cannot be guaranteed.
• Make sure to fix communication cables and power cables connected to the module by placing
them in the duct or clamping them.
Cables not placed in duct or not clamped may hang or shift, allowing them to be accidentally
pulled, which may result in malfunction or damage to the module and the cables.
• The number of times to disconnect/connect the program cable for FX2N-32CCL-NP should be
kept to a minimum.
7) Condition
setting switch Sets the operation condition. (Default setting at shipment: All OFF)
Number Setting description Switch status
ON OFF
SW1 to
SW3 (Unusable) Always OFF
SW4 Input data status in data link faulty station Keep
(HLD) Clear
(CLR)
SW5 Number of occupied stations 4 1
SW6 to
SW8 (Unusable) Always OFF
8) Terminal block Connects dedicated CC-Link cables to enable data link. For the connection
method, refer to Section 2.3.
The terminals SLD and FG are connected inside.
9) Terminal block Connects the power supply to operate the master block.
10) Extensionbus
cable Connects the PLC.
11) Expansion
bus port Connects an extension equipment.
12) Program
port A connector for program cable
13) DIN rail
mounting
groove DIN46277: DIN rail mounting groove of 35 mm (1.38") in width
Number Name Description
HLD
1
SW
ON
CLR 4
OFF ON
12345678
2
1
3
4
6
5
7
8
SLD DG DA DB
24+
24-
FG
Guidelines for the safety of the user and protection of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK
• If in doubt at any stage during the installation of the FX
2N
-32CCL-NP CC-Link SYSTEM LOCAL
BLOCK always consulta professional electrical engineer who is qualified and trained to the local
and national standards. If in doubt about the operation or use of the FX
2N
-32CCL-NP CC-Link
SYSTEM LOCAL BLOCK please consult the nearest Mitsubishi Electric distributor.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.

HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 TELEX : J24532 CABLE MELCO TOKYO
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
• When disconnecting a communication/power cable connected to the module, do not hold the
cable area.
For a cable with connector, hold the connector attached to the module.
For a cable connected to a terminal block, loosen screws of the terminal block, then disconnect
the cable.
If a cable is pulled while it is connected to a module, the module may malfunction or the
module and the cable may be damaged.
WIRING PRECAUTIONS
• Perform Class D grounding (solid grounding) with a wire of 2 mm2or more to the grounding
terminal in the PLC main units. However, never perform common grounding with a high voltage
system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
2.1 Installation
Install the FX
2N
-32CCL-NP on the right side of an FX
2N
Series main unit, extension unit, or other extension
block.
The FX
2N
-32CCL-NP can be installed using a DIN rail (DIN 46277, width: 35 mm (1.38 in.)) or directly with
M4 (0.16 in.) screws.
In the case of direct installation, provide space of 1 to 2 mm (0.04 to 0.08 in.) between units.
2.2 Dedicated CC-Link Cable
Use dedicated CC-Link cables in the CC-Link system.
If any other cable is used, the performance of the CC-Link system cannot be guaranteed.
2.3 Module Wiring with Dedicated CC-Link Cables
This section describes the connection method of dedicated CC-Link cables.
• The cables can be connected without regard to the station number.
• Make sure to connect a terminal resistor (offered as an accessory of the module) between the DA and
DB terminals in the modules at both ends.
• In the CC-Link system, the terminal resistor to be connected varies depending on the cable used.
- When a dedicated CC-Link cable is used: 110 Ω, 1/2 W (brown, brown and brown)
- When a dedicated high-performance CC-Link cable is used: 130Ω, 1/2 W (brown, orange and
brown)
• Star connection is not allowed.
• The figure below shows the connection method.
Important
Make sure to use only one type of cable (dedicated CC-Link cables OR dedicated CC-Link high-
performance cables).
If both types of cables are used together, normal data transmission cannot be guaranteed.
Point
The shielded dedicated CC-Link cable should go through the terminals SLD and FG in each
module, and both ends should be grounded (Class D = solid grounding).
The terminals SLD and FG are connected inside the module.
PLC Another
equipment PLC Another
equipment
PLC Another
equipment
Common grounding
(allowed) Common grounding
(not allowed)
Dedicated grounding
(best)
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
Dedicated CC-Link cable Dedicated CC-Link cable
Master module Remote module Remote module
Terminal
resistor
Terminal
resistor
2.4 Connection diagram of program cable
Length: 1 m (3.3 ft)
3. SPECIFICATION
3.1 General Specification
Dielectric strength: 500V AC for 1 minute (between the case and the PLC ground)
Other specification is equivalent to that of the PLC main unit.
3.2 Performance Specification
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be used at the
same time. Only one type of cable can be used simultaneously.
Attach a terminal resistor in accordance with the cable type.
Item Specification
Applicable function Local station function (The master station and standby master station
functions are not provided.)
CC-Link version Ver.1.10
Transmission speed Selectable (by rotary switch) among 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps
and 10 Mbps
Station number 1 to 64 (set by rotary switch)
Maximum total cable
length (maximum
transmission distance)
1,200 m maximum
Varies depending on the transmission speed.
Number of link points
per station
Remote I/O station : Remote I/O = 32/32 (RX/RY) points
Remote device station : Remote I/O = 32/32 (RX/RY) points
Remote register = 4 (RWw) points
Remote register = 4 (RWr) points
Transmission path type Bus (RS-485)
Connection cable Dedicated CC-Link cable/Dedicated high-performance CC-Link cable*1
RAS function • Automatic return function
• Offline test
• Error detection by link special relay/register
Applicable PLC FX2N Series PLC
Number of occupied
I/O points 8 I/O points of FX Series PLC (8 points in total. The ratio between inputs and
outputs is arbitrary.)
Communication with PLC
By FROM/TO instructions via the buffer memory
Note
• Scan method: Asynchronous mode
• Automatic refresh: Not provided
• Master station function: Not provided
• Standby master station function: Not provided
Operation indication
POWER : Lit while 24V DC is supplied from outside.
L RUN : Lit while communication is normal.
L ERR : Lit when communication error has occurred.
SD : Lit while data is being transmitted.
RD : Lit while data is being received.
Program forwarding and
monitoring
With AJ65BT-G4 and FX2N-232AWC-NP, sequence programs can be
forwarded and monitored through CC-Link.
Applicable software:GX Developer
FX-PCS/WIN-E
24V DC external power
supply Supplied from 24V DC (150 mA) external terminal blocks.
5V DC internal power
supply 5V DC power is converted from the input power.
The 5V DC PLC bus is not used.
Accessories Program cable Lengths 1.0 m (3.2 ft)
Special block number label
MASS (Weight) 0.4 kg (0.88 lbs)
PLC main unit
programming
port
8
1FX2N-32CCL-NP
RUN
ERR
5
1
2
3
46
7
8
(1)
(2)
(8)
(2) (3)
(4)
(6)
(5) (5)
(6)
(1)
(3) (7)
(8)
(4)
(7)
Blue
Blue
Blue
Blue
Red
Red
Red
Red
(Case)
3.3 Buffer Memory List
3.4 I/O Signals to PLC
BFM number Item Description
Hex. Dec.
#AH to #BH #10 to #11 I/O signal Refer to 3.4
#1CH #28
FROM/TO instruction
access error judgement time
Set the FROM/TO instruction access
error judgement time
(unit:10ms).Default:200ms
#1EH #30 Model code K7041
#E0H to #15FH #224 to #351 Remote input (RX) Stores the input status from a remote
station.
#160H to #1DFH #352 to #479 Remote output (RY) Stores the output status from a
remote station.
#1E0H to #2DFH #480 to #735 Remote register(RWw) Stores the transmission data to a
remote station.
#2E0H to #3DFH #736 to #991 Remote register(RWr) Stores the received data from a
remote station.
#5E0H to #5FFH #1504 to #1535 Link special relay (SB) Stores the data link status.
#600H to #7FFH #1536 to #2047 Link special register (SW) Stores the data link status.
PLC to local block Write (when TO instruction is used)
BFM number Write bit Output signal name
Hex. Dec.
#AH #10
b0 Refresh command
b1 to b3 (Prohibited to use)
b4 Request for module reset
b5 to b15 (Prohibited to use)
#BH #11 b0 to b15 (Prohibited to use)
PLC to local block Read (when FROM instruction is used)
BFM number Read bit Input signal name
Hex. Dec.
#AH #10
b0 Module error
b1 Data link status in host station
b2 (Prohibited to use)
b3 Data link status in other stations
b4 Module reset acceptance completion
b5 to b14 (Prohibited to use)
b15 Module ready
#BH #11 b0 to b15 (Prohibited to use)
Manual number: JY992D96001
Manual revision: A
Date : April 2001
JY992D96001A Effective Apr. 2001
Specificationsare subject to
change without notice
Table of contents
Other Mitsubishi Recording Equipment manuals

Mitsubishi
Mitsubishi DX-TL5000E series User guide

Mitsubishi
Mitsubishi MAC-567IF-E User manual

Mitsubishi
Mitsubishi MAC-397IF-E User manual

Mitsubishi
Mitsubishi DX-TL1600EM User manual

Mitsubishi
Mitsubishi DX-TL1600U User manual

Mitsubishi
Mitsubishi MAC-568IF-E User manual

Mitsubishi
Mitsubishi AJ71E71 User manual

Mitsubishi
Mitsubishi A1SJ71PB92D User manual

Mitsubishi
Mitsubishi FX-485PC-IF User manual

Mitsubishi
Mitsubishi m5l8255ap-5 User manual