Mitsubishi A1SJ71PB92D User manual

Mitsubishi Programmable Logic Controller
PROFIBUS-DP Interface Module
Type AJ71PB92D/A1SJ71PB92D
User,s Manual
PROFIBUS-DP Interface Module
Type AJ71PB92D/A1SJ71PB92D
User,s Manual
MODEL
MODEL
CODE
A1SJ71PB92D-U-S-E
13JL20
IB(NA)-66773-F(0404)MEE
Specifications subject to change without notice.
When exported from Japan, this manual does not require application to the
Ministry of Economy, Trade and Industry for service transaction permission.
HEAD OFFICE : 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212,JAPAN
NAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN


SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced
in this manual. Also pay careful attention to safety and handle the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the CPU module user’s manual for a
description of the PLC system safety precautions.
These •SAFETY PRECAUTIONS •classify the safety precautions into two categories: “DANGER” and
“CAUTION”.
DANGER Procedures which may lead to a dangerous condition and cause death or
serious injury if not carried out properly.
CAUTION Procedures which may lead to a dangerous condition and cause superficial
to medium injury, or physical damage only, if not carried out properly.
Depending on circumstances, procedures indicated by CAUTION may also be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always
forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
zWhen a communication error occurs in the PROFIBUS network, the status of the faulty station is as follows.
Configure an interlock circuit in the sequence program using the communication status information (input
X1, buffer memory 2040 to 2079) so that the system can operate safely.
Erroneous outputs and mis-operation could cause accidents.
(1) The input data of the master station maintains the data before abnormality of the communication.
(2) When the master station is down, the output state of each slave station will be in accordance with the
parameter settings.
(3) When any slave station is down, the output state of other slave stations will be in accordance with the
parameter settings of the master station.
zIf a stop error occurs in the CPU module, the communication status is as described below.
(1) Communication with the slave station is stopped.
(2) For the input data received from the slave station, the values at CPU module stop error occurrence are
held.
(3) The output data sent from the AJ71PB92D/A1SJ71PB92D to the slave station are cleared.
CAUTION
zWhen the PROFIBUS cable is laid, do not lay it close to main circuits or power lines.
They should be installed 100mm(3.9inch) or more from each other.
Not doing so could result in noise that would cause malfunctioning.

[INSTALLATION PRECAUTIONS]
CAUTION
zUse the module in the environment given in the general specifications of the CPU module’s User’s Manual.
Using the module outside the range of the general specifications may result in electric shock, fire or
malfunctioning, or may damage or degrade the module.
zInsert the tabs at the bottom of the module into the mounting holes in the base unit before installing the
module. (The AnS series module shall be fastened by screws in the base unit at the specified torque.)
Not installing the module correctly could result in malfunctioning, breakdowns or pieces of the product falling
zTighten the fixing screws of the PROFIBUS cable with the specified torque. If the screws are loose, it could
result in malfunction of the module.
zDo not touch the conductive area or electric parts of the module.
Doing so may cause module malfunctioning or breakdowns.
[WIRING PRECAUTIONS]
CAUTION
zSwitch all phases of the external power supply of the PLC system off before connecting the PROFIBUS
cable. Not doing so could cause failure or malfunctioning of the module.
zBe careful not to let foreign matter such as filings or wire chips get inside the module. These can cause fire,
breakdowns and malfunctioning.
zThe PROFIBUS cable which is connected to the module must be protected with a duct or secured in
position with clamps.
Unless the cable is thus protected or secured, the module or the cable could be damaged when the cable
swings, moves or it is strained with careless pulls, or it could cause malfunction when the cable contacts
with any undesirable objects.
zWhen disconnecting the PROFIBUS cable from the module, do not pull by holding the cable section. To
disconnect the cable, make sure to hold the connector which is coupled with the module. Do not attempt to
pull the cable to disconnect it from the module. It could damage the module or the cable, or cause
malfunction due to a poor contact of the cable.
[STARTING AND MAINTENANCE PRECAUTIONS]
DANGER
zSwitch all phases of the external power supply off before cleaning.
Not doing so could cause electric shock.

CAUTION
zNever disassemble or modify the module.
This may cause breakdowns, malfunctioning, injury and/or fire.
zSwitch all phases of the external power supply off before mounting or removing the module. If you do not
switch off the external power supply, it will cause breakdowns or malfunction of the module.
zSet the ON/OFF select switch of the terminal resistor before the operation.
If the setting is switched during the operation, network error may occur, or error detection may not be
performed by error.
zBefore handling the module, always touch grounded metal, etc. to discharge static electricity from the
human body.
Failure to do so can cause the module to fail or malfunction.
[OPERATING PRECAUTIONS]
DANGER
zDo not write data into the "not usable" of the buffer memory of special function modules. Also, do not output
the "not usable" signal as the output signal to a special function module from the PLC CPU. Writing data
into the "not usable area" or outputting an "not usable" signal may cause system malfunctions in the PLC.
CAUTION
zThe online operations conducted for the CPU module being operated (especially when changing data or
operation status), shall be conducted after the manual has been carefully read and a sufficient check of
safety has been conducted.
Operation mistakes could cause breakdowns to or malfunction of the module.
[DISPOSAL PRECAUTIONS]
CAUTION
zWhen disposing of this product, treat it as industrial waste.

Revisions
* The manual number is noted at the lower left of the back cover.
Print Date *Manual Number Revision
May, 1997 IB (NA)-66773-A First printing
Sep., 1997 IB (NA)-66773-B Correction
Section 2.3, Chapter 3
Addition
Appendix 2
Oct., 1998 IB (NA)-66773-C Model Addition
AJ71PB92D
Correction
SAFTY PRECAUTIONS, Chapter 1, 2, 3, 4, Section 5.1, 5.2, 5.3, 5.5.1,
5.5.2, 5.6, 6.1, Chapter 7, 8, 9
Addition
Appendix 1
Chapter Alteration
Appendix 1 →Appendix 3
Jun., 2000 IB (NA)-66773-D Correction
Chapter 1, Section 2.1, 2.2, 2.3, 2.4, 2.5, 3.1, 3.2, 4.2.1, 4.2.2, 4.3.1, 5.5.1,
Appendix 1
Addition
Section 2.6, 4.4, 4.5, 8.6
Jun., 2003 IB (NA)-66773-E Correction
SAFTY PRECAUTIONS, Section 4.3.2, 6.1, 8.2.1, 8.2.2
Addition
Section 3.3.3, Appendix 2
Apr., 2004 IB (NA)-66773-F Correction
Section 1.2, 3.2, 3.3.3, 4.2.2, 4.3.1, 4.3.2, 4.6, 5.1, 5.3, 6.1, 6.2
Addition
SAFTY PRECAUTIONS, Chapter 9
Aug., 2004 IB (NA)-66773-G Correction
SAFTY PRECAUTIONS, Section 2.2, 3.3.2, 3.3.3, 4.3.2, 5.5.1, Chapter 8,
Section 8.2.2
Japanese Manual Version SH-3330-G
This manual does not imply guarantee or implementation right for industrial ownership or implementation
of other rights. Mitsubishi Electric Corporation is not responsible for industrial ownership problems caused
by use of the contents of this manual.
1998 Mitsubishi Electric Corporation

Introduction
Thank you for purchasing the Mitsubishi Programmable Controller MELSEC-A Series.
Before using the equipment, plese read this manual carefully to develop full familiarity with the functions and
performance of the graphic operation terminal you have purchased, so as to ensure correct use.
Please forward a copy of this manual to the end user.
Table of Contents
About This Manual
1. OVERVIEW 1-1 to 1-2
1.1 Software Configuration......................................................................................................................................1- 1
1.2 AJ71PB92D/A1SJ71PB92D Features .............................................................................................................1- 2
2. SYSTEM CONFIGURATION 2-1 to 2-6
2.1 Whole System Configuration ............................................................................................................................2- 1
2.2 System Configuration Example.........................................................................................................................2- 2
2.3 Applicable CPU Modules ..................................................................................................................................2- 3
2.4 Installable Base Units .......................................................................................................................................2- 4
2.5 Combining with MELSECNET (II), MELSECNET/B, and MELSECNET/10.......................................................2- 4
2.6 Precautions for Configuring a System ..............................................................................................................2- 5
3. SPECIFICATIONS 3-1 to 3-10
3.1 General Specification........................................................................................................................................3- 1
3.2 Performance Specifications..............................................................................................................................3- 2
3.3 Network Configuration.......................................................................................................................................3- 3
3.3.1 Basic configuration ................................................................................................................................3- 3
3.3.2 Applicable configuration.........................................................................................................................3- 4
3.3.3 Number of connectable slaves ..............................................................................................................3- 8
4. FUNCTIONS 4-1 to 4-32
4.1 Functions for Exchanging with Slaves ..............................................................................................................4- 1
4.1.1 Exchange flow........................................................................................................................................4- 1
4.1.2 Global control functions.........................................................................................................................4- 2
4.2 I/O Signal..........................................................................................................................................................4- 5
4.2.1 I/O signal list..........................................................................................................................................4- 5
4.2.2 I/O signal detail description....................................................................................................................4- 6
4.3 Buffer Memory List............................................................................................................................................4- 9
4.3.1 Buffer memory/configuration..................................................................................................................4- 9
4.3.2 Buffer memory detailed description.......................................................................................................4-10
4.4 While-Run Operation Mode Changing Function...............................................................................................4-30
4.5 AJ71PB92D/A1SJ71PB92D's Remote Parameter Setting Function Using MELSEC ProfiMap
Configuration Software......................................................................................................................................4-31
4.6 E2PROM initialization function..........................................................................................................................4-32
5. PROCEDURES BEFORE SYSTEM OPERATION 5-1 to 5-10
5.1 Procedures before Operation............................................................................................................................5- 1
5.1.1 Parameter setting procedure.................................................................................................................5- 2
5.2 Handling Precautions........................................................................................................................................5- 3
5.3 Part Names and Settings..................................................................................................................................5- 4

5.4 Execution Method for Self-diagnosis.................................................................................................................5- 6
5.5 Wiring................................................................................................................................................................5- 7
5.5.1 PROFIBUS cable wiring.........................................................................................................................5- 7
5.5.2 Terminator switch ..................................................................................................................................5- 7
5.5.3 Precautions against wiring.....................................................................................................................5- 8
5.6 Maintenance and Inspection.............................................................................................................................5-10
6. COMMUNICATION TIME 6-1 to 6-4
6.1 Transmission Delay Time When There is One Master Station.........................................................................6- 1
6.2 Transmission Delay Time When There are Multiple Master Stations...............................................................6- 4
7. DDB FILE 7-1 to 7-2
8. PROGRAMMING 8-1 to 8-6
8.1 Initial Program...................................................................................................................................................8- 1
8.2 Data I/O with Slave ...........................................................................................................................................8- 2
8.2.1 Normal service mode (MODE switch : No. 0)........................................................................................8- 2
8.2.2 Extend service mode (MODE switch : No. E) ........................................................................................8- 3
8.3 Communication Trouble Area and Expansion Communication Trouble Area Clear.........................................8- 4
8.4 Address Information Read................................................................................................................................8- 4
8.5 Global Control...................................................................................................................................................8- 5
8.6 While-Run Operation Mode Changing..............................................................................................................8- 6
9. TROUBLESHOOTING 9-1 to 9-2
APPENDIX A-1 to A-10
Appendix 1 Differences between AJ71PB92D/A1SJ71PB92D Software Versions .................................................A- 1
Appendix 1.1 Differences between A1SJ71PB92D Software Versions...........................................................A- 1
Appendix 1.2 Restrictions on Use of A1SJ71PB92D Software Versions in the Same System.......................A- 2
Appendix 1.3 Differences between AJ71PB92D Software Versions...............................................................A- 2
Appendix 1.4 Restrictions on Use of AJ71PB92D Software Versions in the Same System ...........................A- 2
Appendix 2 Precautions for Replacing AJ71PB92 with A(1S)J71PB92D................................................................A- 3
Appendix 3 Extended Trouble Information of Mitsubishi's Slaves...........................................................................A- 7
Appendix 4 External Dimensions.............................................................................................................................A- 8

About This Manual
The following are manuals related to this product.
Request for the manuals as needed according to the chart below.
Related Manual
Manual Name Article No.
MELSEC ProfiMap Configuration System for Open Networks Software Manual 65778-B
* Inquiries can be made to :
MITSUBISHI ELECTRIC EUROPE Factory Automation
Gothaer Strasse 8 D-40880 Ratingen Germany
Phone : +49(21 02)486-0
Fax : +49(21 02)486-717

1. OVERVIEW MELSEC-A
1-1
1. OVERVIEW
This is the user's manual for the AJ71PB92D/A1SJ71PB92D PROFIBUS-DP interface module
(hereafter abbreviated as " AJ71PB92D/A1SJ71PB92D. When explain separately, however,
abbreviated as AJ71PB92D, A1SJ71PB92D), which is used to connect a MELSEC-A/QnA/Q series
programmable controller to a PROFIBUS-DP network.
The AJ71PB92D/A1SJ71PB92D operates as a master station (class 1) in the PROFIBUS-DP network.
1.1 Software Configuration
FROM/TO
User Interface
Direct Data Link Mapper
FDL
PHY
(DDLM)
empty
FMA1/2
MELSEC A Series PC
Communication using a buffer memory
Portion where master
PCB is installed
Layer 3 to 7
Layer 2 Datalink layer
Layer 1 Physical layer
Portion where slave
PCB is installed
The AJ71PB92D/A1SJ71PB92D has a physical layer, data link layer, DDLM, and user interface that
conform to PROFIBUS-DP, and communicates data with the PLC CPU by using a buffer memory.
The main application of PROFIBUS-DP is networks that execute high-speed communication at the
level of sensors and actuators, and the AJ71PB92D/A1SJ71PB92D has been designed with this in
mind: its functions are mainly related to data I/O with slave stations.

1. OVERVIEW MELSEC-A
1-2
1.2 AJ71PB92D/A1SJ71PB92D Features
(1) Operates as a PROFIBUS-DP master (class 1) station.
(2) Makes possible the exchange of input and output data to and from the slave station
without the need to be aware of the PROFIBUS-DP protocol by using I/O signals X/Y and
the buffer memory.
(3) Supports 3M, 6M, 12M [bps] network communication speeds in addition to the 9.6k, 19.2k,
93.75k, 187.5k, 500k, and 1.5M [bps] supported by the AJ71PB92D/A1SJ71PB92D. These
can be selected using a configurator.
(4) Station Nos. from 0 to 125 can be set using the configurator.
(5) Trouble information can be read from the slave station using the I/O signal X/Y and the
buffer memory.
(6) The global control function makes it possible to maintain all slave I/O at the same time. In
addition, this can also be canceled.
(7) The module contains a self-diagnosis function that can be used to test the hardware such
as the internal memory.

2. SYSTEM CONFIGURATION MELSEC-A
2-1
2. SYSTEM CONFIGURATION
This section explains system configuration for the AJ71PB92D/A1SJ71PB92D
2.1 Whole System Configuration
(1) For the A1SJCPU
A1SJCPU (S3)
Extension cable
Extension base unit
A1SJ71PB92D
A1SC[ ]B
A1S6[ ]B(S1)/A1S5[ ]B(S1)
A1SJHCPU
(2) For the compact building block type CPU
Compact building block type
CPU
Extension cable
A1SC[ ]B
Extension base unit
Basic base unit
A1SJ71PB92D
A1S6[ ]B(S1)/A1S5[ ]B(S1)
A1S3[ ]B/A1S38HB
(3) For the building block type CPU
Building block type CPU
Extension cable
AC[ ]B
Extension base unit
Basic base unit
AJ71PB92D
A6[ ]B/A5[ ]B
A3[ ]B/A38HB

2. SYSTEM CONFIGURATION MELSEC-A
2-2
(4) For the Q series CPU
Q series CPU
Extension cable
QC[ ]B
Extension base unit
Basic base unit
A1SJ71PB92D QA1S6[ ]B
Q3[ ]B
2.2 System Configuration Example
The following describes the A1SJ71PB92D system configuration example.
A communication parameter file is created in Windows using the Configurator software package, this
parameter file can then be down-loaded via an RS-232C cable to the AJ71PB92D/A1SJ71PB92D.
Via RS-232C
AJ71PB92D
A1SJ71PB92D
RS-232C
Personal computer supporting Windows 3.1 or 95
MITSUBISHI ELECTRIC Corp.
MELSEC ProfiMap
(Ver. 3.0 or later)
PROFIBUS network
Point Refer to "About This Manual" for inquiry for MELSEC ProfiMap.
*: Version confirmation method of AJ71PB92D/A1SJ71PB92D
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
MODE
0:ONLINE 1
1:PRM SET
2:TEST
A1SJ71PB92D
RUN
SD/RD
TOKEN
READY
FROM/TO
PRM SET
RSP ERR.
FAULT
TEST
B6
B5
B4
B3
B2
B1
B0
S
T
.
N
O
.
BG
BG
Software version
Hardware version
E:ONLINE 2
Version
Hardware Software
AJ71PB92D A or later Cor later
A1SJ71PB92D B or later G or later
Model

2. SYSTEM CONFIGURATION MELSEC-A
2-3
2.3 Applicable CPU Modules
The following table shows the CPUs that the AJ71PB92D/A1SJ71PB92D can use.
(1) AJ71PB92D
Applicable CPU Modules
A1SCPUC24-R2
A1SJHCPU, A1SHCPU,
A2SHCPU, A2SHCPU-S1,
A1NCPU, A1NCPUP21,
A1NCPUP21-S3, A1NCPUR21,
A2NCPU, A2NCPUP21,
A2NCPUP21-S3, A2NCPUR21,
A2NCPU-S1, A2NCPUP21-S1,
A2NCPUP21-S4, A2NCPUR21,
A3NCPU, A3NCPUP21,
A3NCPUP21-S3, A3NCPUR21
A2ASCPU, A2ASCPU-S1,
A2ASCPU-S30, A2USHCPU-S1
A2ACPU, A2ACPUP21,
A2ACPUP21-S3, A2ACPUR21,
A2ACPU-S1, A2ACPUP21-S1,
A2ACPUP21-S4, A2ACPUR21,
A3ACPU, A3ACPUP21,
A3ACPUP21-S3, A3ACPUR21,
A2UCPU,A2UCPU-S1,
A3UCPU, A4UCPU
Q2ASCPU, Q2ASCPU-S1,
Q2ASHCPU, Q2ASHCPU-S1,
Q2ACPU, Q2ACPU-S1,
Q3ACPU, Q4ACPU, Q4ARCPU
(2) A1SJ71PB92D
Applicable CPU Modules
A1SCPUC24-R2
A1SJHCPU, A1SHCPU,
A2SHCPU, A2SHCPU-S1
A2ASCPU, A2ASCPU-S1,
A2ASCPU-S30, A2USHCPU-S1
Q2ASCPU, Q2ASCPU-S1,
Q2ASHCPU, Q2ASHCPU-S1
Q02CPU-A, Q02HCPU-A,
Q06HCPU-A

2. SYSTEM CONFIGURATION MELSEC-A
2-4
2.4 Installable Base Units
The base modules that can be installed in the AJ71PB92D/AISJ71PB92D are shown below.
(1) AJ71PB92D
Installable Base Units
Basic base unit Extension base unit
A32B, A32B-S1, A35B, A38B, A38HB A52B, A55B, A58B, A62B, A65B, A68B
(2) A1SJ71PB92D
Installable Base Units
Basic base unit Extension base unit *1
A1S32B, A1S33B, A1S35B, A1S38B,
A1S38HB A1S52B (S1), A1S55B (S1), A1S58B (S1),
A1S65B (S1), A1S68B (S1),QA1S65B,
QA1S68B
*1: The no power supply module extension base unit A1S5 [ ] B (S1) may not have sufficient power
supply capacity, so use the A1S6 [ ] B (S1) when installing a AJ71PB92D/A1SJ71PB92D in the
extension base unit.
When the A1S5 [ ] B (S1) must be installed, do so after referring to the chapter covering power
supplies in the respective CPU Module User’s Manual.
2.5 Combining with MELSECNET (II), MELSECNET/B, and
MELSECNET/10
The AJ71PB92D/A1SJ71PB92D can be installed in the MELSECNET (II) and MELSECNET/B master
stations and local stations, and in the MELSECNET/10 control stations and normal stations.
However, the AJ71PB92D/A1SJ71PB92D cannot be installed in the MELSECNET (II),
MELSECNET/B, and MELSECNET/10 remote stations, so be careful.

2. SYSTEM CONFIGURATION MELSEC-A
2-5
2.6 Precautions for Configuring a System
(1) There are the following restrictions on the AJ71PB92D/A1SJ71PB92D according to the
applied CPU module and used configuration software.
Parameter File Write Path Max. I/O Data Length
CPU
Module Configuration
Software
Via
AJ71PB92D/
A1SJ71PB92D
RS-232C
interface
Via
CPU module
RS-232C/
RS-422
interface
Normal service
mode Extended
service mode
SW0D5F-
PROFIMAP 32 bytes each for
input and output
MELSEC-
PROFIMAP 2.0
Q series
CPU MELSEC-
PROFIMAP 3.0
244 bytes each
for input and
output*1
SW0D5F-
PROFIMAP 32 bytes each for
input and output
MELSEC-
PROFIMAP 2.0
Write disabled
A/QnA
series
CPU MELSEC-
PROFIMAP 3.0
Write enabled
Write enabled*1
32 bytes each for
input and output
244 bytes each
for input and
output*1
*1: The software version usable by the AJ71PB92D/A1SJ71PB92D is AJ71PB92D (A or
later) or A1SJ71PB92D (E or later).
When A1SJ71PB92D (software version D or earlier) is used, write is disabled and the
max. data length is 32 bytes each for input and output.
(2) Precautions for using the parameters preset for extended service mode to operate the
module in normal service mode.
The following table gives the operating conditions (conditions per one slave station) for the time
when the parameters preset for the extended service mode are used to operate the
AJ71PB92D/A1SJ71PB92D preset for the normal service mode/extended service mode.
: Operable 5: Inoperable
Parameter Size Exchange Data LengthOperating Condition
AJ71PB92D
A1SJ71PB92D 122 bytes max 244 bytes max 32 bytes max 244 bytes max.
AJ71PB92D software version A
or later and normal service
mode setting
5
A1SJ71PB92D software version
E or later and normal service
mode setting
5
A1SJ71PB92D software version
D or earlier and extended
service mode setting
5 5
(3) In either of the following cases, the AJ71PB92D/A1SJ71PB92D buffer memory must be
accessed by a sequence program when the module ready signal X1D of the
AJ71PB92D/A1SJ71PB92D is ON.
•The operation mode is changed using Y11/X11 in the sequence program.
•Parameter setting is made with ProfiMap connected to other than the RS-232C port of
the AJ71PB92D/A1SJ71PB92D. (For example, parameter setting is made with ProfiMap
connected to the RS-422/RS-232 connector of the CPU module.)
If the buffer memory is accessed with the X1D status ignored, the CPU module may detect
the "SP UNIT DOWN" error, stopping the sequence operation.

2. SYSTEM CONFIGURATION MELSEC-A
2-6
(4) Do not make parameter setting via buffer memory and parameter setting from the RS-
232C port of the AJ71PB92D/A1SJ71PB92D at the same time.
If they are made simultaneously, ProfiMap which started parameter write earlier wins the
parameter write right after the operation mode is changed to the parameter setting mode, and
the other ProfiMap cannot perform parameter write and detects an error.
This status will be automatically cleared 15 seconds after completion of parameter write if
parameter write via the CPU module is valid, or 3 seconds after completion of parameter write
if parameter write from RS-232C is valid.
(5) Do not make simultaneous access to the AJ71PB92D/A1SJ71PB92D from multiple
ProfiMap's.
If such access is made, the AJ71PB92D/A1SJ71PB92D may not be accessed properly.
(6) If remote parameter setting is performed from MELSEC ProfiMap to the
AJ71PB92D/A1SJ71PB92D which is making data exchange, note that PROFIBUS data
exchange will stop during parameter setting.
(7) In a system where remote parameter setting is made from MELSEC ProfiMap, do not
execute the mode changing function using the program.
If the mode changing function is executed in the program, an interlock with the remote
parameter setting is not provided and therefore the mode may not be changed.

3. SPECIFICATIONS MELSEC-A
3-1
3. SPECIFICATIONS
This section explains the AJ71PB92D/A1SJ71PB92D the general specifications, performance
specifications, and transmission specifications.
3.1 General Specification
This section explains the AJ71PB92D/A1SJ71PB92D general specifications.
Table 3.1 General Specification
Item Specification
Usage environment
temperature 0 to 55°C
Storage environment
temperature -20 to 75°C
Usage environment humidity 10 to 90%RH, No condensation formation
Storage environment
humidity 10 to 90%RH, No condensation formation
When there is intermittent vibration
Frequency Acceleration Amplitude Sweep count
10 to 57Hz — 0.075mm
(0.003in.)
Anti-vibration 57 to 150Hz 9.8m/s2—
Where there is continuous vibration
10 to 57Hz — 0.035mm
(0.001in.)
57 to 150Hz 4.9m/s2—
Anti-shock Complies with JIS B3501, IEC61131-2
(147m/s2, 3 times in the direction for each of X, Y, Z)
Usage environment No corrosive gas, etc.
Usage altitude 2000m or less
Installation location Inside the control panel
Over voltage category *1II or less
Pollution level *22 or less
Cooling method Self cooling
*1 Shows if an estimate has been made for which distribution areas the connections will be done for
the equipment from the public power grid to the equipment installation area inside the
configuration.
Category II applies to equipment that receives its power from fixed facilities. The surge
resistance voltage for equipment rated to 300V is 2500V
*2 Shows the index for inductive matter generation in the environment in which the equipment is
used. Pollution level 2 is for dirt that is non-inductive. However, occasionally inductance can be
generated in the environment by condensation.
Complies with JIS
B3501, IEC61131-2 10 times in each direction
for X, Y, Z (80 minutes)

3. SPECIFICATIONS MELSEC-A
3-2
3.2 Performance Specifications
Item Specifications
Model AJ71PB92D A1SJ71PB92D
Electrical standards and characteristics Complies with EIA-RS485
Medium Shielded twisted cable
Network configuration Bus (however, tree type when a repeater is used)
Data link method •Token passing method (master side)
•Polling method (master/slave side)
Transmission encoding method NRZ
Transmission speed Transmission distance [m/segment] Maximum transmission distance
when 3 repeaters are used
[m/network]
9.6 [kbps]
19.2 [kbps] 1200 4800
Transmission speed/maximum 93.75 [kbps]
transmission distance *1 *2 187.5 [kbps] 1000 4000
500 [kbps] 400 1600
1.5 [Mbps] 200 800
3 [Mbps]
6 [Mbps] 400
12 [Mbps] 100 *3
Maximum number of repeaters/network 3 units *2
Maximum number of stations/segment 32 stations *3 (See "Point")
Maximum number of slave stations/master
station 60 slaves
Number of connection nodes (number of
repeaters) 32, 62 (1), 92 (2), 126 (3)
Transmittable data 32 bytes/1 station (Normal service mode)
244 bytes/1 station (Extemded service mode)
Number of occupied I/O 32 points (I/O allocation : special 32 points)
5VDC Internal current consumption 0.54 A 0.56 A
Noise durability, dielectric withstand voltage
insulation resistor Depending on the AJ71PB92D/A1SJ71PB92D installation system power supply module
specifications. (refer to the CPU Module User's Manual.)
External dimensions 250 mm (9.84 in.)(H) ×37.5 mm (1.48 in.)(W)
×106 mm (4.17 in.)(D) 130 mm (5.12 in.)(H) ×34.5 mm (1.36 in.)(W)
×93.6 mm (3.69 in.)(D)
Weight 0.37 kg 0.27 kg
*1 Transmission speed control within +/- 0.3% (PROFIBUS part 1)
*2 Distance that the transmission distance can be expanded by (m/network) using repeaters
Maximum transmission distance (m/network) = (number of repeaters + 1) ×transmission distance (m/segment)
*3 The *3 restriction will cease to exist when the system is configured exclusively by the master and slave stations of
the hardware version B or later versions.
Point
*3 When using 12Mbps transmission speed, restriction of the cable length and the number of connector stations
described below is necessary.
1) Minimum length of the cable between stations is greater than or equal to one meter.
2) Maximum number of the connection stations are smaller than or equal to 11.
Master Slave Slave Slave Slave
2)
1)1) 1)
100
Transmission specification
s

3. SPECIFICATIONS MELSEC-A
3-3
3.3 Network Configuration
3.3.1 Basic configuration
1) Equipment types
•Class 1 master
•Configurator
•Slave
•Repeater
2) Number of units that can be connected to the entire network (when repeaters are used)
Master+slave ≤126 units
3) Number that can be connected for 1 segment
Master+slave+repeaters ≤32 units
4) Communications can be conducted via a maximum of 3 repeaters from an arbitrary master or
arbitrary slave to an arbitrary master or arbitrary slave (Not 3 units in the entire network).
5) The maximum number of slaves that can be connected to 1 AJ71PB92D/A1SJ71PB92D is 60
stations.
CPU module
Master (class 1)
AJ71PB92D
A1SJ71PB92D
Configurator
Slave Slave Slave
•The PROFIBUS-DP cable is provided by the user.
This manual suits for next models
1
Table of contents
Other Mitsubishi Recording Equipment manuals

Mitsubishi
Mitsubishi AL-ASI-BD User manual

Mitsubishi
Mitsubishi FX-485PC-IF User manual

Mitsubishi
Mitsubishi MAC-397IF-E User manual

Mitsubishi
Mitsubishi DX-TL5000E series User guide

Mitsubishi
Mitsubishi QJ71MT91 User manual

Mitsubishi
Mitsubishi AJ71E71 User manual

Mitsubishi
Mitsubishi FX2N-32CCL-NP User manual

Mitsubishi
Mitsubishi DX-TL1600U User manual

Mitsubishi
Mitsubishi MR-J2-10A Installation instructions

Mitsubishi
Mitsubishi MELSEC QJ71E71-100 User manual