MORLEY-IAS ZXa Quick start guide

Document No. 996-071, Revision: 1, Aug 99 © MORLEY-IAS
ZXa / Zxe
Commissioning Manual
ZXa
ZXe

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL CONTENTS
Document No. 996-071, Revision: 1, Aug 99 Page C.1
Contents
1INTRODUCTION.................................................................................................................................................................1
1.1 NOTICE..............................................................................................................................................................................1
1.2 WARNINGS AND CAUTIONS............................................................................................................................................1
1.3 NATIONALAPPROVALS...................................................................................................................................................1
1.4 EMC COMPATIBILITY.....................................................................................................................................................2
2USER CONTROL LEVELS...............................................................................................................................................3
2.1 LEVEL DEFINITION ..........................................................................................................................................................3
2.2 USER PASSWORDS............................................................................................................................................................3
3CONTROLS AND DISPLAYS ..........................................................................................................................................4
3.1 CONTROL KEYS................................................................................................................................................................4
3.2 FRONT PANEL LED INDICATIONS.................................................................................................................................5
3.3 ALPHANUMERIC DISPLAY INDICATIONS......................................................................................................................7
3.4 MEMORY LOCK................................................................................................................................................................7
3.5 ENABLING LEVEL 2 OR LEVEL 3 ACCESS.....................................................................................................................8
3.5.1 Selecting the commissioning option....................................................................................................................8
3.6 OVERVIEW OF MENU STRUCTURE ................................................................................................................................8
4COMMISSIONING A NEW INSTALLATION.........................................................................................................10
4.1 STEP 1 – GENERAL SETUP............................................................................................................................................10
4.2 STEP 2 – CONFIGURE EACH SIGNALING LOOP..........................................................................................................10
4.3 STEP 3 – CONFIGURE PERIPHERALS (IF REQUIRED)..................................................................................................10
4.4 STEP 4 – CONFIGURE OUTPUTS (SOUNDERS AND RELAYS).....................................................................................10
4.5 STEP 5 – CONFIGURE DAY MODE OPERATION (IF REQUIRED)...............................................................................11
4.6 STEP 6 – CONFIGURE NETWORK OPTIONS (IF REQUIRED)......................................................................................11
4.7 STEP 7 – COMMENCE NORMAL OPERATION..............................................................................................................11
5CONFIGURE OPTION.....................................................................................................................................................12
5.1 ACCESSING THE CONFIGURE OPTION.........................................................................................................................12
5.2 SIGNALING LOOPS.........................................................................................................................................................12
5.2.1 Auto Learn.............................................................................................................................................................13
5.2.2 Zones......................................................................................................................................................................13
5.2.3 Devices...................................................................................................................................................................14
5.3 PERIPHERALS..................................................................................................................................................................21
5.3.1 Auto Learn.............................................................................................................................................................21
5.3.2 Zones......................................................................................................................................................................22
5.3.3 Devices...................................................................................................................................................................22
5.4 SOUNDERS.......................................................................................................................................................................24
5.4.1 Sounder Output Types.........................................................................................................................................24
5.4.2 Allocating Sounders.............................................................................................................................................24
5.4.3 Detector loop addressable sounder circuit controller units(SCC)..............................................................27
5.4.4 Peripheral loop addressable sounder circuit controller units.....................................................................27
5.4.5 Sounder Fault Monitoring..................................................................................................................................28
5.5 RELAYS............................................................................................................................................................................28
5.5.1 Fault Relay............................................................................................................................................................28
5.6 PC (REMOTE PROGRAMMING).....................................................................................................................................28
6INSPECT OPTION.............................................................................................................................................................29

MORLEY-IAS ZXa / Zxe
CONTENTS COMMISSIONING MANUAL
Page C.2Document No.996-071, Revision: 1, Aug 99
7TIME / DATE OPTION....................................................................................................................................................29
7.1 TIME / DATE...................................................................................................................................................................29
7.2 SYSTEM (CLEAR MEMORY)..........................................................................................................................................29
7.3 CRYSTAL .........................................................................................................................................................................30
8PROGRAM INTEGRITY OPTION..............................................................................................................................31
9POWER SUPPLIES OPTION.........................................................................................................................................32
10 PASSWORDS OPTION................................................................................................................................................32
11 DAY MODE OPTION...................................................................................................................................................33
11.1 DAY MODES....................................................................................................................................................................33
11.2 DELAYED MODE............................................................................................................................................................34
11.2.1 Commissioning Delayed Mode.........................................................................................................................34
11.3 SENSITIVITY MODE........................................................................................................................................................36
11.3.1 Commissioning Sensitivity Mode......................................................................................................................36
11.4 VERIFICATION MODE ....................................................................................................................................................37
11.4.1 Commissioning Verification Mode...................................................................................................................37
12 SETUP OPTION.............................................................................................................................................................38
12.1 EVENT LOG......................................................................................................................................................................39
13 NETWORKS OPTION.................................................................................................................................................40
13.1 PANEL NETWORKS.........................................................................................................................................................40
13.1.1 Network - Panel Network Address...................................................................................................................40
13.1.2 Standard Network Settings for shared zones..................................................................................................40
13.2 PORT B PROTOCOLS.......................................................................................................................................................41
14 SYSTEM EVENTS OPTION......................................................................................................................................43
14.1 EVENT MODES................................................................................................................................................................43
14.1.1 General Events.....................................................................................................................................................44
14.1.2 Event Logic...........................................................................................................................................................44
14.1.3 Define Event Outputs..........................................................................................................................................45
15 NORMAL OPERATION..............................................................................................................................................45
16 SUPPLEMENTARY INFORMATION....................................................................................................................46
16.1 LOCATING EARTH FAULTS...........................................................................................................................................46
16.2 OVERRIDING DELAYS ON INDIVIDUAL OUTPUTS......................................................................................................47
16.3 OPERATIONAL FEATURES.............................................................................................................................................47
16.3.1 Output to fire alarm devices :............................................................................................................................47
16.3.2 Delays to Outputs :..............................................................................................................................................47
16.3.3 Coincidence Detection :.....................................................................................................................................47
16.3.4 Fault Signals from points:..................................................................................................................................47
16.3.5 Disablement of addressable points:.................................................................................................................48
16.3.6 Test condition :...................................................................................................................................................48
16.4 PRINTER SET-UP OPTIONS............................................................................................................................................48

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL CONTENTS
Document No. 996-071, Revision: 1, Aug 99 Page C.3
Table of Figures
Figure 1 - ZXa Controls and Displays..........................................................................................................................................4
Figure 2 - ZXe Controls and Displays..........................................................................................................................................4
Figure 3 - System Control LED Display.......................................................................................................................................5
Figure 4 - Memory Lock Switch Location...................................................................................................................................7
Table of Tables
Table 1 – Control Key Functions...................................................................................................................................................4
Table 2 - Alphanumeric and Interactive Control Keys..............................................................................................................5
Table 3 - LED Functions.................................................................................................................................................................6
Table 4 - Menu Funtion Overview.................................................................................................................................................9
Table 5 - Alarm Threshold Setting..............................................................................................................................................17
Table 6 - List of Device Actions..................................................................................................................................................19
Table 7 - Day Mode Options........................................................................................................................................................33
Table 8 - Setup Options.................................................................................................................................................................39
Table 9 - Slave Panel Network Settings.....................................................................................................................................40
Table 10 - Master Panel Network Settings.................................................................................................................................41
Table 11 - Port B Protocol Settings.............................................................................................................................................42
Table 12 - General System Events...............................................................................................................................................44

MORLEY-IAS ZXa / Zxe
CONTENTS COMMISSIONING MANUAL
Page C.4Document No.996-071, Revision: 1, Aug 99
(This page has been intentionally left blank)

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 1
Commissioning Manual
1Introduction
1.1 Notice
•The material and instructions covered in this manual have been carefully checked for accuracy and are presumed
to be correct. However, the manufacturer assumes no responsibility for inaccuracies and reserves the right to
modify and revise this document without notice.
•These instructions cover the commissioning and programming of both the ZXa and ZXe Fire Alarm Control
Panels. Refer to the Fire Alarm Control Panel Operator’s Manual for instructions on powering up and operating
the system. Refer to the relevant Installation Manual for instructions on installing the panel.
1.2 Warnings and Cautions
These instructions contain procedures to follow in order to avoid injury and damage to
equipment. It is assumed that the user of this manual is a suitably trained installer who is
familiar with the relevant regulations.
All equipment must be programmed to operate in accordance with the appropriate standards
and local regulations applicable to the installation.
Electro-static Sensitive Devices.
Take suitable ESD precautions when working inside the panel enclosure.
1.3 National Approvals
This equipment must be installed in accordance with these instructions and the appropriate national,
regional and local regulations specific to the country and location of the installation. Consult with the
appropriate Authority Having Jurisdiction (AHJ) for confirmation of the requirements.

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 2Document No.996-071, Revision: 1, Aug 99
1.4 EMC Compatibility
•This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate
radio frequency energy, and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. Operation of this equipment in a residential area is likely to cause harmful interference in
which case, the user will be required to correct the interference at his own expense.
•If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the
followingmeasures:
1. Reorient or relocate the receiving antenna.
2. Increase the separation between the equipment and the receiver.
3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 3
2User Control Levels
2.1 Level Definition
•The ZXa and ZXe Fire Alarm Control Panels have three user control levels.
•At all three levels, the LED Displays indicate the condition of the installation, the Zone LED Displays indicate the
location of any fire alarm or fault and the alphanumeric display gives more detailed fire alarm or fault information.
•At USER LEVEL 1, all the displays are functional but the front panel control keys are inhibited.
•At USER LEVEL 2, all front panel controls are functional and some system operation parameters and functions
can be changed. User Level 2 is reached by entering a password from level 1.
•At USER LEVEL 3, all front panel controls are functional and full system configuration and programming are
possible. User Level 3 is reached by entering a password from either Level 1 or Level 2. User Level 3 is intended
for use by the system installer / maintenance contractor.
2.2 User Passwords
•Up to ten USER LEVEL 2 passwords can be programmed into the panel.
•The USER LEVEL 2 passwords can be assigned / changed at Level 3 by the installer / maintenance contractor.
Level 2 passwords do not allow access to Level 3 functions.
The Default Level 2 password is 1234. At initialization, only one Level 2 password is enabled.
The Level 3 password is ####. This password cannot be changed. To ensure panel security,
do not set a Level 2 password to be the same as the Level 3 password.

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 4Document No.996-071, Revision: 1, Aug 99
3Controls and Displays
3.1 Control keys
•Each control panel has two groups of control keys.
•A bank of four keys contains the four system control keys: Sound Alarms, Silence / Resound, Mute / Accept and
System Reset.
•A bank of 17 keys contains interactive and alphanumeric keys. On the ZXa, opening the hinged panel gives
access these keys. This is located below the Zone LED Display.
XYZ
01 2345 678 9> <
A B C D EFGHIJKLM
NOPQRSTUVWX Y Z
s
h
i
f
t
FIRE
Disa blement
Fault/Te st
Disa bledZone
Fault
Accepte d
EarthFault
Relays Disabled
Delayed Mode
SounderFault
Test
SupplyFault
AlarmsSilen ce d
Sounde rsDisabled
System/CPUFau lt
FIRE
PowerSystemReset
Mute/Accep t
Silence/Resound
Soun d Alarms
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2010 11 12 13 14 15 16 17 18 19 20987654321
0..9Words
A..Z
E
n
t
e
r
N
o
Yes
Change XYZ
01 2345 678 9> <
A B C D EFGHIJKLM
NOPQRSTUVWX Y Z
shift
FIRE
Disa blement
Fault/Te st
Disa bledZone
Fault
Accepte d
EarthFault
Relays Disabled
Delayed Mode
SounderFault
Test
SupplyFault
AlarmsSilen ce d
Sounde rsDisabled
System/CPUFau lt
FIRE
PowerSystemReset
Mute/Accep t
Silence/Resound
Soun d Alarms
30 31 32 33 34 35 36 37 38 39 40292827262524232221
41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80
Zone
Zone
Zone
FIRE
Fault/Test
Disa bled
FIRE
Fault/Test
Disa bled
FIRE
Fault/Test
Disa bled
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2010 11 12 13 14 15 16 17 18 19 20987654321
0..9Words
A..Z
E
n
t
e
r
N
o
Y
e
s
Change
Figure 1- ZXa Controls and Displays Figure 2- ZXe Controls and Displays
Key Legend Function
Sound Alarms Press to Turn on ALL Sounder Outputs (i.e. evacuate building
manually).
Silence /
Resound Press to Turn off all activated sounders.
Press again to re-activate the sounders.
Mute / Accept Press to acknowledge events and silence the internal buzzer.
System Reset Press to cancel all alarm conditions and reset the panel.
Table 1– Control Key Functions
Alphanumeric Display
System Status LED
Display
Control Keys
Zone LED Display
Program / Interactive
Keys
Optional Zone LED
Display

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 5
•The alphanumeric keys normally function as a numeric keypad. During programming, these keys can be toggled
to Letter Keys by pressing the CHANGE key. This gives access to letters A-M. For access to letters N-Z, press
and hold the SHIFT key whilst pressing the appropriate letter key.
Key Legend Function
0 to 9 Press to enter numbers 0-9 or letters A-Z
>Press to scroll through fire alarms or faults manually on the display
<Press to scroll back through fire alarms or faults manually on the
display
Change Press to change a display option (where allowed)
Enter Press to confirm entry of a multiple digit number
No Press to answer No, or terminate a display option
Yes Press to answer Yes, or step through a display option
Shift Press to show user options on the display
Press, during programming, to allow entry of Letters N-Z
Table 2- Alphanumeric and Interactive Control Keys
•The control keys are disabled at USER LEVEL 1. Pressing the SHIFT key will cause the display to prompt for
entry of the Level 2 password. The password must be entered to re-enable the control keys at Level 2.
3.2 Front Panel LED Indications
•The Level 1 LED Indicators are divided into two sections.
•The upper array of LED Indicators shows the operational conditional of the panel and the installation.
•The lower array of Zone LED Indicators shows the location of a fire alarm or fault.
•The standard Zone LED Indicators provide identification for up to 20 zones. On the ZXe panel, this can be
extended by adding either a further 20 zones (to give a total of 40 zones) or a further 60 zones (to give a total of
80 zones).
•The LED Indicators illuminate as red, yellow or green to give a clear indication of the panel status as follows:
Figure 3- System Control LED Display
FIRE
Fault
Accepted
Disablement
Test
Sounder Fault
Delayed Mode
Relays Disabled
Earth Fault
Sounders Disabled
System / CPU Fault
Alarms Silenced
Supply Fault
Power

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 6Document No.996-071, Revision: 1, Aug 99
Indicator Colour Function How to Clear
FIRE Red The panel has detected a fire alarm
condition, or the ‘Sound Alarms’ key
has been pressed.
Correct the condition causing the
alarm and then perform a panel
reset.
Fault Yellow A fault has been detected by the
panel. Correct the condition causing the
faullt and then perform a panel reset.
Accepted Yellow A fault or alarm has been
acknowledged and the internal
buzzersilenced.
Correct the condition causing alarm
or fault and then perform a manual
reset. NOTE: If another alarm or fault
occurs, the internal buzzer
automatically resounds.
Disablement Yellow Part of the system, either input or
output, has been disabled manually
by the user.
Re-enable the device or devices.
The system automatically resets.
Test Yellow The system is in test mode. Zone
LED indicators show which zones
are being tested.
Cancel test when finished.
Sounder Fault Yellow This indicates a wiring fault with one
of the sounder output circuits. Correct the fault condition and then
perform a panel reset.
Delayed Mode Yellow This indicates that the system is
operating with delays to the sounder
outputs.
N/A
Relays Disabled Yellow The relay outputs have been
disabled. See Disablement.
Earth Fault Yellow An earth connection fault has
occurred on a cable. Correct the fault condition and then
perform a panel reset.
System / CPU Fault Yellow The CPU has reset or a system fault
has occurred. Correct the problem, if appropriate,
and then perform a panel reset.
Sounders Disabled Yellow The sounder outputs have been
disabled. See Disablement.
Alarms Silenced Yellow The sounder outputs have been
silenced. Correct the alarm condition and then
perform a panel reset. NOTE: Press
SILENCE / RESOUND again to
reactivate the sounders. If a new
alarm occurs, the alarms will
resound.
Supply Fault Yellow There is a problem with the power
supply, battery or supply input. Correct the fault condition and then
perform a panel reset.
Power Green STEADY: Indicates AC Power is
present. FLASHING: Indicates a loss
of AC Power.
See Supply Fault.
Zone FIRE Red FLASHING: The zone is in a fire
alarm condition. Correct the alarm condition and then
perform a panel reset.
Zone Fault Yellow FLASHING: The zone contains faulty
devices.
STEADY: The zone is either disabled
or in test mode.
Correct the fault condition and then
perform a panel reset.
Re-enable devices or cancel test
mode.
Table 3- LED Functions

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 7
3.3 Alphanumeric Display Indications
•The alphanumeric liquid crystal display gives 80 characters of information on a 2-line display. The display is
illuminated to assist viewing under dim ambient light conditions.
•When the numeric keypad is not in use, the display will revert to automatically scrolling through any fire alarm or
fault conditions present on the panel. If there are no alarm or fault conditions, the display will show the date and
time.
•Pressing the SHIFT key will show a list of optional functions or prompt for the level 2 password.
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys?
3.4 Memory Lock
•To make changes that affect the configuration of
the system, such as adding detectors, the system
memory must first be unlocked.
•Open the enclosure door and move the memory
lock switch to the open position.
•The Memory Lock Switch is located on the CPU
Board.
•The figure opposite shows the interior of the ZXa
Fire Alarm Control Panel. The ZXe Fire Alarm
Control Panel uses the same CPU Board and has
a similar arrangement.
Memory Lock Switch
Printer Port
Figure 4- Memory Lock Switch Location
Ensure that the Memory Lock Switch is open prior to performing any programming.
Ensure that the Memory Lock Switch is closed before returning the panel to normal
operation.

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 8Document No.996-071, Revision: 1, Aug 99
3.5 Enabling Level 2 or Level 3 Access
•To enable Level 2 or Level 3 operation, press the SHIFT key. The display will then show:
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys?
•Press theYES key and the display will prompt for entry of the password.
[Panel ACTIVE Control Keys INHIBITED] [1]
Please Enter Password
•Enter the4-digit Level 2 password. The display then shows the Main Menu of user options.
[ACTIVE] 1)Commission 2)Test 3)Time [1]
4)Enable 5)Disable 6)Print 7)View
•If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display showing the
system status message. To re-show the menu display, press theSHIFT key.
•If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then Level 2
access will be automatically canceled. It will be necessary to re-enter the password to re-activate Level 2
functions.
•For detailed information on the Level 2 user options, refer to the User Manual (P/N 996-072).
3.5.1 Selecting the commissioning option
•To access the commissioning functions in the panel, press1to select the commission option.
•The display will prompt for entry of the Level 3 password. Enter the Level 3 password using the number keys and
then press ENTER.
•The display will then show the commissioning menu options.
3.6 Overview of Menu Structure
•The commissioning menu options are presented in three different screens (PAGES). When the commissioning
menu option is selected, the display will show:
PAGE 1
1)CONFIGURE YES)More Options [1]
2)Inspect 3)NORMAL OPERATION
•To move between the three commissioning screens, press theYES key.

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 9
PAGE 2
1)Time/Date 2)Program Integrity [1]
3)Power Supplies 4)Passwords
PAGE 3
1)Day Modes 2)Setup Options 3)Network [1]
4)Events
Page Option Function
Configure To configure the connection and operation of the signaling loop devices, peripheral
devices, sounder circuits and relay outputs.
Also provides configuration for upload / download of configuration data from a PC.
Inspect Provides the same functionality as the configure option but with view only. This allows
the data to be inspected without risking any inadvertent changes.
1
Normal Operation To return the panel to normal operation – Level 2.
Time / Date To allow the date and time and other clock functions to be changed.
Also allows the system memory to be cleared to return the panel back to factory
defaultsettings.
Program Integrity To show the version of the software installed in the panel.
To show the status of the operating program and configuration memory.
Power Supplies Shows the current state of the AC Mains and Battery supply conditions.
NOTE: Should the AC Mains fail, the back lighting on the liquid crystal display will be
turned off to conserve battery power.
2
Passwords To define the number of User Level 2 passwords.
To define the value of each Level 2 password.
To define the maximum time the panel will remain at Level 2, without any key pressed,
before inhibiting the keys and returning to Level 1 operation.
Day Modes To define which, if any, of the following day modes are in operation.
1. Delayed Mode
2. Sensitivity Mode
3. Verification Mode
To define the effective times of operation, (i.e. start and finish).
Setup Options To define system setup parameters.
Network To define and configure the operation of the panel in a networked system.
3
Events To define system events that provide a more flexible cause and event function than
that available from standard zone based ringing options.
Table 4- Menu Funtion Overview

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 10 Document No.996-071, Revision: 1, Aug 99
4Commissioning a new Installation
•This section provides a guide to the steps that are required to commission a new installation.
•Precise details on how to perform each step, and on the functionality of each programming option, are given in
appropriate sections of this manual.
4.1 Step 1 – General Setup
•Ensure that the panel configuration memory is cleared and returned to factory settings. Refer to TIME / DATE –
SYSTEM CLEAR OPTION on Page 2 of the Commissioning Menus.
•Select the SETUP OPTION from Page 3 of the Commissioning Menus. PressYES to step through each item to
inspect the factory default settings and to make changes as required. For example, to enter service telephone
number and company name.
4.2 Step 2 – Configure Each Signaling Loop
•Select the CONFIGURE option from Page 1 of the Commission Menus and then perform the following.
1. Select “Signaling Loop 1”.
2. Perform an “Auto Learn”.
3. Select “Devices” and change sensor location text as required.
4. Assign Zones.
•Repeat actions 1-4 above for each signaling loop connected to the panel.
•Enter Zone descriptions.
•NOTE: If using a PC to program the panel, actions 3 and 4 above will already have been defined on the PC.
4.3 Step 3 – Configure Peripherals (if required)
•Select the CONFIGURE option from Page 1 of the Commission Menus and then perform the following.
1. Select “Peripheral”.
2. Perform an “Auto Learn”.
3. Select “Devices” and change the units’ location text as required.
4. Assign Zones and set the operation of the unit.
4.4 Step 4 – Configure Outputs (sounders and relays)
•Select the CONFIGURE option from Page 1 of the Commission Menus and then perform the following.
1. Select “Sounders”, if zonal ringing patterns are required and program accordingly.
2. Select “Relays”, if zonal operation is required and program accordingly.
•Finally, select the INSPECT option from Page 1 of the Commission Menus. Compare the commissioning data
entered against the installation sheets. This facility allows the data to be inspected without risking any inadvertent
changes.

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 11
4.5 Step 5 – Configure Day Mode Operation (If required)
•Select the DAY MODES option from Page 3 of the Commission Menus and then perform the following.
1. Select “Delayed Mode”, if the sounders and outputs are to be delayed.
2. Select “Sensitivity Mode”, if the detectors are to have different pre-alarm and fire alarm settings during day
/ night.
3. Select “Verification Mode”, if the analogue signals are to be verified before the panel registers a fire alarm.
•Program the required mode as required.
4.6 Step 6 – Configure Network Options (If required)
•Select the NETWORK option from Page 3 of the Commission Menus. PressYES to step through each item to
inspect the factory default settings and change as required. For example, panel address, number of slave panels,
etc.
4.7 Step 7 – Commence Normal Operation
•Before finally commencing normal operation, perform the following.
1. Select PASSWORDS from Page 2 of the Commission Menus. Set the number of Level 2 passwords and
define the value of each password.
2. Select PROGRAM INTEGRITY from Page 2 of the Commission Menus. Check and record the program
checksums.
•Select NORMAL OPERATION from Page 1 of the Commission Menus.
Remember to lock the memory.

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 12 Document No.996-071, Revision: 1, Aug 99
5Configure Option
5.1 Accessing the Configure Option
•Page 1 of the Commission menu is shown below:
1)CONFIGURE YES)More Options [1]
2)Inspect 3)NORMAL OPERATION
•The CONFIGURE option allows the Signaling Loops, peripherals, sounders and relays to be programmed. It also
enables the function to allow the panel to be programmed by a PC.
•Press 1 to select the CONFIGURE option.
The CONFIGURE option and all sub menu options require the Memory Lock to be open.
•The display then shows a menu of options as follows:
CONFIGURE : Loop 1) 2) 3) 4) 5) [1]
6)Peripherals 7) Sounders 8)Relays 9)PC
•NOTE: The menu will only show the number of signaling loops programmed during setup (Refer to the Setup
Option. The ZXa can only have two loops maximum.
5.2 Signaling Loops
•After selecting a loop from the configure menu, the display will present a list of options as follows:
CONFIGURE : Loop 1) 1)Zones [1]
2)Devices 3)Auto Learn 4)Calibrate
The top left-hand corner of the display provides a reminder that panel is in configure mode
with loop 1 selected.
•Select the required option by pressing the appropriate numeric key.
•When commissioning a new panel, start by performing an “Auto Learn”. This will cause the panel to search for all
devices installed on the loop.

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 13
5.2.1 Auto Learn
•This facility saves considerable time and effort when installing a system, or when changing sensor configuration.
It allows the system to learn for itself what devices have been installed on a particular loop.
•Press 3from the configure menu to select "Auto "Learn". The display will respond with the message :-
Auto Learn finds ALL device addresses
and types on loop 1. Shall I do this ?
•To proceed with "Auto Learn", press theYES key. The system will confirm your command with the message
"Program Running" on the display. It may take up to half a minute to learn a complete loop. Each possible sensor
address is checked to see if any detector is installed at that address. If a detector has been installed, the panel
determines the type of the detector. If more than one detector is located at a single address, or the detector type
code is invalid, a warning message will appear on the display.
•Do not press any key until the display changes from the “program running” message.
•Once the system has finished learning, it will respond with a display giving a summary of the detectors found on
the loop. For example.
Ion Opto Temp Sounder MCP Zone-Mon Other
37 24 2 8 14 2 3
•This display should be checked, against the installation sheets, to ensure that the system has found the correct
number of devices.
•Pressing any key then restores the display to the normal commissioning menu.
•The Auto Learn sequence should be repeated for each loop on the system. It can be used as many times as
required and does not affect the text description used to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the "Devices" option to
obtain detailed information on the device type and to see the address of each device found
on the loop.
5.2.2 Zones
•The system can be divided into 20, 40 or 80 "zones" for the ZXe panel & 20 “zones” for the ZXa panel. Each
zone may contain one or more devices. The zone assignment option allows the commissioning engineer to
quickly assign the sensors to the appropriate zone. It defaults so that all devices are in zone 1.
•Press 1from the configure menu to select the “zones” option. The display will then show:
All devices on Loop 01 from address
[001] to address [126] are in zone [01]
•This display shows several pieces of information. To avoid ambiguity as to what can be modified, the display will
flash the item that can be changed. If you want to change it, then simply type the new value over the top. For
example:
•The "from address" number (i.e. 001) will be flashing to show this item can be changed, if required. To make this
address 24, enter "024”. The display will then show the new zonal range as :-

MORLEY-IAS ZXa / Zxe
COMMISSIONING MANUAL
Page 14 Document No.996-071, Revision: 1, Aug 99
All devices on Loop 01 from address
[024] to address [126] are in zone [01]
•The ">" & "<" keys can be used to move across the display. For example, if the ‘126’ in the "to address" field is
flashing, then the ‘zone’ field can be modified by pressing the">" key to make the zone number flash and then
entering the desired value.
•The backspace"<" key also moves back one digit - useful for correcting errors when entering numbers.
•The configuration shown on the display becomes effective immediately after the "Enter" or "Yes" key is pressed.
Pressing the "No" key will abort the operation and return to the commissioning menu.
•If the "to address" value is less than 126, the "Yes" or "Enter" key automatically advances to the next zone to be
defined.
•When all of the devices for the loop being configured are assigned to zones, then the program will advance to the
zone description - text entry menu.
•Each zone can have a description assigned to it to identify the area covered by the zone. This description will
appear on the liquid crystal display if a fault or fire is detected by any sensor in the zone.
Zone 01 is named = “SOUTH ANNEXE “
•The description can be amended by highlighting the location text (using the‘>‘ and ‘<‘ keys), pressing "Change"
and entering either, letters, numbers or keywords. This procedure is identical to that used for editing the sensor
location text described in section5.2.3.2 below.
5.2.3 Devices
•The "Devices" option from the display gives information on the various types of device fitted on a loop.
•Press 2 to select the "Devices" option. The system will ask which address you want to start at :-
Begin inspection at address number 1 ?
•If you would like to start at a different address, then press the "Change" key and enter your required address,
otherwise say "Yes" to continue.
•The display then gives detailed information about the Device at the chosen address.
L1 Z003 A086 RESEARCH ROOM 52 “ Ev106
Ion Smoke Signal= 26 (Inputs 2..0=LLH)
Loop Zone Address Location Text Event
Device Type Analogue Signal
Digital input status (Apollo only)
H=Logic HighL=Logic Low

ZXA / ZXE MORLEY-IAS
COMMISSIONING MANUAL
Document No. 996-071, Revision: 1, Aug 99 Page 15
5.2.3.1 Changing Device Information
•Changes are made by first pressing the "Change" key. A menu of items that can be changed will appear
according to the type of device, For example.
•An ionization smoke detector will allow changes on :-
1)Sensor Text 2)Zone 3)Event
4)Alarm thresholds 7)Group
•A call-point will allow changes on :-
1)Sensor Text 2)Zone 3)Event
6)Action 7)Group
•Press the appropriatenumber to select the required option. Press ‘No’ to return to the device information display.
•NOTE: This change facility is only available while in the configure mode. It cannot be invoked from the INSPECT
option, thus preventing inadvertent changes to the system.
5.2.3.2 Location Text
•To enter or modify the location text assigned to a device, press1to select the "Sensor Text" option. The display
will show the current location text and provide additional information to assist in making any changes.
•Three modes of text entry are available - "KeyWords", "Numbers" and "Letters". The mode currently in use is
always shown in square brackets in the top right hand corner of the display. The required mode is selected by
pressing either theYes (Keyword) button or theNo (Letters/Numbers) button.
Text = “FLOOR 2 ROOM 86_ “ [Numbers ]
Type in number 0..9
A) Numbers
•The number mode allows you to add numbers 0 to 9 on the display.
•Advance and Backspace editing keys are also available in this mode.
•For example, to change from "ROOM 86" to "ROOM 87", first press the backspace key once to erase the "6",
then press key “7”. The display will immediately show the new description as below :-
Text = “FLOOR 2 ROOM 87_ “ [Numbers ]
Type in number 0..9
•The cursor symbol "_", indicates where you are on the line. It will not appear in the description shown on the
device display.
This manual suits for next models
1
Table of contents
Other MORLEY-IAS Control Panel manuals
Popular Control Panel manuals by other brands

Gecko
Gecko Aeware k-35-in Quick reference card

AGS
AGS Parksafe Control Panel Installation operation & maintenance

HEIDENHAIN
HEIDENHAIN POSITIP 8000 operating instructions

Steamist
Steamist TSC-250 Installation and operating instructions

Advanced Electronics
Advanced Electronics Mx-5000 Series manual

Erreka
Erreka VIVO-M203 installation guide

Leviton
Leviton EZ-MAX PLUS series installation guide

Zeta Alarm Systems
Zeta Alarm Systems SIMPLICITY PLUS manual

Kidde
Kidde 23911-K087 (4+1) Operation and maintenance manual

INSBUD
INSBUD IB-TRON 4000 SOL instruction manual

Ness
Ness pro-lx user manual

Truma
Truma Panel BC (616) Operating instructions & installation instructions