Advanced Quick Zone XL Guide

XL
4-12 Zone Conventional Control Panel
Installation, Commissioning & Operating
www.acornfiresecurity.com
www.acornfiresecurity.com

0832-CPD-2177
13
EN54-2: 1997 +A1:2006
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Provided options:
- Outputs to Fire Alarm Devices
- Investigation Delays to Outputs
- Dependency on more than one alarm signal
- Test Condition
EN54-4: 1997 +A1:2002 +A2:2006
Power supply equipment for fire detection and fire alarm
systems for buildings
QZXL-4, QZXL-8, QZXL-12
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND OBSERVE ALL ADVICE GIVEN
IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID E.S.D!
ATTENTION
IMPORTANT SAFETY NOTES
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualified and authorised to
do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance and
remedial work. This work must only be carried out by competent service personnel who are fully conversant with
the contents of the panel’s installation manual and have the necessary skills for maintaining this equipment.
This fi re alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to product
specifications at our discretion and without prior notice. E & O E.
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
544b/02
www.acornfiresecurity.com
www.acornfiresecurity.com

3
Table of Contents Page
1ABOUT THIS PANEL.....................................................................................................................................4
1.1 PRODUCT OVERVIEW .........................................................................................................................4
1.2 CABINET DETAILS ...............................................................................................................................5
1.3 CIRCUIT BOARDS ................................................................................................................................6
1.4 MAIN PCB TERMINALS........................................................................................................................8
1.5 ZONE CARD TERMINALS ....................................................................................................................9
1.6 TECHNICAL SPECIFICATION............................................................................................................10
1.7 POWER SUPPLY MODULE................................................................................................................11
2DESIGN CONSIDERATIONS.......................................................................................................................12
2.1 SYSTEM DESIGN &PLANNING.........................................................................................................12
2.1.1 CABLE TYPES & LIMITATIONS .....................................................................................................13
2.1.2 CABLING .........................................................................................................................................13
2.1.3 CABLE LENGTHS...........................................................................................................................13
2.1.4 MAINS PROVISION.........................................................................................................................13
2.2 GENERAL CONVENTIONAL SYSTEM SCHEMATIC........................................................................14
2.3 GENERAL TWIN WIRE SYSTEM SCHEMATIC..................................................................................15
3INSTALLATION............................................................................................................................................16
3.1 SAFETY ...............................................................................................................................................16
3.2 ESD PRECAUTION .............................................................................................................................17
3.3 GENERAL............................................................................................................................................17
3.4 MOUNTING THE CABINET.................................................................................................................17
3.5 MAINS CONNECTIONS ......................................................................................................................18
3.6 CONNECTING THE BATTERIES........................................................................................................19
3.7 BATTERY CHARGING VOLTAGE CHECKS......................................................................................19
4SETUP & PROGRAMMING .........................................................................................................................20
4.1 TWIN WIRE MODE ..............................................................................................................................20
4.2 ZONE INTERFACE FUNCTION ..........................................................................................................21
4.3 LEVEL 3ENGINEERING OPTIONS....................................................................................................22
4.4 OPTIONS INDEX .................................................................................................................................23
5OPERATING.................................................................................................................................................48
5.1 PANEL CONTROLS &INDICATIONS ................................................................................................48
5.1.1 Status LED Indicators ......................................................................................................................49
5.1.2 Keypad.............................................................................................................................................49
5.2 DISABLE MODE..................................................................................................................................50
5.3 TEST MODE.........................................................................................................................................51
5.4 FAULT DIAGNOSIS.............................................................................................................................52
5.5 FUNCTIONALITY DURING ASYSTEM FAULT .................................................................................53
5.6 USER INSTRUCTIONS........................................................................................................................53
6SERVICE & MAINTENANCE.......................................................................................................................54
6.1 THE NEED FOR MAINTENANCE .......................................................................................................54
6.2 DUTIES OF THE RESPONSIBLE PERSON........................................................................................54
6.3 ROUTINE MAINTENANCE &TESTING..............................................................................................54
6.3.1 DAILY...............................................................................................................................................54
6.3.2 WEEKLY..........................................................................................................................................54
6.4 PERIODIC INSPECTION &SERVICING.............................................................................................56
6.4.1 SCHEDULE OF TESTING LOG BOOK...........................................................................................57
6.4.2 FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK ........................................................61
www.acornfiresecurity.com
www.acornfiresecurity.com

4
1 ABOUT THIS PANEL
1.1 PRODUCT OVERVIEW
The QuickZone XL panel is available from 4 to 12 Conventional and/or Twin Wire (sav-wire) zones.
For the fire alarm engineer, the QuickZone XL has been designed to minimise labour costs by providing ample
room for tasks such as wiring and changing batteries. Activation is via key switch or access code, which means
you should always be able to work on the panel and the one man walk tests will help reduce the cost of
maintaining the fire alarm system.
Simplicity is one of the most important aspects when considering the end user of a fire alarm panel. The colour
coded buttons and the 3 step silence functionality gives non-technical people the confidence to correctly
manage their fire alarm system.
All inputs and outputs are fully programmable and there are options to have delays to the outputs. The
programming features of the QuickZone XL also include 3 different modes to help reduce false alarms. Local
fire authorities are demanding this type of functionality to reduce unwanted callouts from alarm receiving centres
As standard, all QuickZone XL panels provide two monitored sounder circuits, Fire & Fault VFCO relays, Fire &
Fault switched negative outputs, class change and an alert input.
A fully functional repeater panel is available via a plug in comms PCB.
QuickZone XL panels support a large range of conventional detectors including, Apollo, Hochiki & Nittan.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
QuickZone XL panels are approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems –
Control & Indicating Equipment.
Quiesecent and alarm current details for standby battery calculations
Model
Standby Current
Alarm Current
QZXL-4
90mA
133mA
Add per Twin Wire circuit
N/A
9mA
QZXL-ZEC 4 Zone ext card std
43mA
47mA
QZXL-HAZEC 4 zone ext card, high spec
49mA
87mA
TPCA05 comms card
5.2mA
N/A
www.acornfiresecurity.com
www.acornfiresecurity.com

5
1.2 CABINET DETAILS
www.acornfiresecurity.com
www.acornfiresecurity.com

6
1.3 CIRCUIT BOARDS
QuickZone XL panels comprise of two main circuit boards plus optional ancillary boards
TPCA01-X4 Master PCB
TPCA03 - LED Display & Controls PCB
www.acornfiresecurity.com
www.acornfiresecurity.com

7
ANCILLARY CIRCUIT BOARDS
QZXL-HSZEC High spec 4 zone extension card
QZXL-ZEC Std spec 4 zone extension card
4 x conventional or Twin Wire
zone circuits
4 x conventional or Twin Wire
zone circuits
2 x switched –ve outputs
1 x Aux relay output
2 x monitored sounder circuits
Piggy backs on Main PCB for
connection to repeater panels
6 programmable switched –ve
outputs
TPCA05 Comms PCB
www.acornfiresecurity.com
www.acornfiresecurity.com

8
1.4 MAIN PCB TERMINALS
www.acornfiresecurity.com
www.acornfiresecurity.com

9
1.5 ZONE CARD TERMINALS
Drawing shows the high spec version of the
zone extension PCB (CZXL-HSZEC).
The std version does not contain the additional
outputs or sounder circuits shown at the
bottom.
www.acornfiresecurity.com
www.acornfiresecurity.com

10
1.6 TECHNICAL SPECIFICATION
Electrical Specification Inputs & Outputs - TPCA01-X2/X4 Main PCB
Terminal capacity
0.5mm2to 2.5mm2solid or stranded wire
PSU @ output
Power supply voltage control line
For temperature compensation control
PSU Input + -
28VDC supply input. Diode protected for
reversal and independent short circuit. Max
current 3 Amps
Max input current 3 amps. Input voltage
22VDC to 32VDC
28v+, 0v- power output
28VDC supply output for fire alarm accessory
relays etc. Max continuous use = 400mA
Fused @ 500mA. Fuse = 500mA resettable
fuse
Common fire relay
Fire relay contact. Clean C/O. Max 3A @
30VDC
Unfused
Common fault relay
Maintained fault relay contact. Clean C/O.
Max 3A @ 30VDC
Unfused
Outputs; FR, FLT
Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52VDC.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL
Switched -ve inputs, connect to 0v to trigger.
Max input voltage = 28VDC. Non latching,
max resistance 100R.
Protected via 10K Ohm impedance, 3V6
zener diode
SNDR 1 –2
28VDC polarity reversal monitored sounder
outputs to fire alarm devices. 4K7 Ohm 5%
0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Zone 1 - 4
Fire alarm zone circuits. Conventionally
wired detection circuit or Twin Wire
combined detection / sounder circuit. 4K7
Ohm 5% 0.25W EOL resistor
Monitoring current limit 50mA, fused @
500mA. Typical max load 22 alarm devices
@ 18mA each per circuit. Ensure 2.4A is not
exceeded.
Electrical Specification Inputs & Outputs - TPCA01-X2/X4 Main PCB
Terminal capacity
0.5mm2to 2.5mm2solid or stranded wire
Zone A - D
Fire alarm zone circuits. Conventionally
wired detection circuit or Twin Wire
combined detection / sounder circuit. 4K7
Ohm 5% 0.25W EOL resistor
Monitoring current limit 50mA, fused @
500mA. Typical max load 22 alarm devices
@ 18mA each per circuit. Ensure 2.4A is not
exceeded.
Programmable Outputs OP A & OP B
Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52VDC.
Current limited 680R. Max load = 40mA
Programmable relay Output
Fire relay contact. Clean C/O. Max 3A @
30VDC
Unfused
SNDR A –B
28VDC polarity reversal monitored sounder
outputs to fire alarm devices. 4K7 Ohm 5%
0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Electrical Specification Inputs & Outputs - TPCA05- comms PCB
Comms A –B
RS485
Repeater Comms, fused @ 20mA
28V
Supply Output
Fused @ 500mA
Programmable outputs 1 –6
Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52VDC.
Current limited 680R. Max load = 40mA
General Specification
Enclosure
Steel IP30. Epoxy powder coated RAL7035
Cabling
Fire resistant screened cable, minimum size 1mm2. Max cable length
1km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance 1uF,
max inductance 1 millihenry).
Temperature range
-5°C to +40°C max RH 95%
Number of conventional/Twin Wire detection circuits
4 or 12
Conventional/Twin Wire detector compatibility
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
www.acornfiresecurity.com
www.acornfiresecurity.com

11
1.7 POWER SUPPLY MODULE
Power Supply Specification
Mains supply
230VAC +10% / -15% 50Hz max current 1A
Mains supply fuse
4 Amp (F4A 250V)
Not accessible for servicing. Internal to
switch mode power unit
Internal power supply rating
3.0 Amps total including battery charging
Maximum load shared between outputs =
2.4A
Power supply output voltage
21.27 –29.68VDC
Tolerance +/- 0.1%
Maximum continuous load for battery
standby (ImaxA)
ImaxA = 610mA
ImaxB not specified
Minimum current drawn by panel
(example)
4 Zone
I min = 85mA
12 Zone
I min = 188mA
Maximum ripple
120 mV p-p
Supply and charger fault monitored
Min/max battery size and type
2 x 7.0Ahr 12volt VRLA
Use Yuasa NP range batteries
Other equivalent batteries may be used but
have not been tested for the purposes of
EN54 approval.
Battery charging voltage
27.3VDC nominal at 20 deg C
Temperature compensated
Battery charging output current
3.0A PSU 1.34mA Current limited 4.7 Ohms
Battery high impedance fault (Batt Hi Z)
Resistance > 1 Ohm
1 hour reporting time
Max current drawn from batteries
3.15 Amps with main power source
disconnected. Battery fuse 3.15A LBC 20mm.
www.acornfiresecurity.com
www.acornfiresecurity.com

12
2 DESIGN CONSIDERATIONS
2.1 SYSTEM DESIGN & PLANNING
What is a detection zone?
In order to direct those responding to a fire alarm signal, particularly the fire service, to the area of a fire, all
buildings, other than very small buildings, need to be divided into detection zones. Detection zones need to be
small enough for a fire to be located quickly.
• If the total floor area of the building is greater than 300m2, each zone should be restricted to a single storey
• If the total floor area of the building is less than 300m2a zone may cover more than a single storey
• For voids above or below the floor area of a room, these may be included within the same zone of the room,
provided that the void and the room constitute a single fire compartment
• The floor area of a single zone should not exceed 2000m2.
Detectors
• A person searching a zone for a fire in a non- addressable fire system should not have to travel more than
60m to identify the source of a fire
• The sensing element of a smoke detection device should not be less than 25mm and not more than 600mm
below ceiling
• The sensing element of a heat detector should not be less than 25mm and not more than 150mm below ceiling
• When mounted on a flat ceiling, smoke detection devices have an individual coverage of 7.5m radius.
However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be
represented by a square measuring 10.6m x 10.6m giving an actual coverage of 112m2per device
• When mounted on a flat ceiling, heat detection devices have an individual coverage of 5.3m radius. However
these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented
by a square measuring 7.5m x 7.5m giving an actual coverage of 56.3m2per device.
Call Points
• A person should not have to travel more than 45m along an escape route to reach a Manual Call Point (25m if
disabled person to operate, or rapid fire development is likely). Manual Call Points should be sited at all stair
wells and exits from the building.
• The frangible element of the manual call point should be positioned 1.4m (+/- 200mm) from the floor level.
(Unless a wheelchair user is likely to be the first person to raise the alarm).
Sounders
• Sounder device cabling should be arranged so that in the event of a fault, at least one sounder will remain
operational during a fire condition.
• The minimum sound level should be 65dB(A) or 5dB(A) above a background noise which is louder than
60dB(A) (if lasting more than 30 seconds) and at a frequency of between 500Hz and 1000Hz.
The maximum sound level should not be greater than 120dB(A) at any normally accessible point. This may be
reduced to 60dB(A) in stairways, enclosures up to 60m2and specific points of limited extent.
• For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at the bed-head
with all doors shut. In buildings providing sleeping accommodation for a significant number of people, all
bedrooms should have both audible and visual alarms.
Beacons
• Visual alarms such as beacons should always be mounted at a minimum height of 2.1m from floor level.
This guide is intended as an aid to
designers and installers of fire
detection systems. It is NOT to be
used as a substitute to BS5839
which should be read in full.
A few handy tips
www.acornfiresecurity.com
www.acornfiresecurity.com

13
General
• Fire Alarm Control Panels should be installed at a location appropriate for staff and fire fighters
• All mains supply isolators must be double pole and suitably marked
• All joints to be fire resisting, junction boxes to be labelled ‘FIRE ALARM’.
• All cables to be fire resisting with a minimum cross-sectional area of 1mm2.
• Cable using trunking as a means of containment must be clipped using fire resistant supports WITHIN THE
TRUNKING.
• Zone charts should be fitted in all appropriate locations (adjacent to control equipment and repeaters).
2.1.1 CABLE TYPES & LIMITATIONS
To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical interference
in the system wiring, we recommend the use of screened cables throughout the installation.
Acceptable, commonly available, screened cables, which can be used on both the sounder and detector circuits
include, NoBurn™ FP200™, Firetuff™, Firecel™, MICC (Pyro™) or any other cable complying with BS 6387
categories C, W, Z.. Refer to BS 5839 pt1 clause 26 for detailed information on cables wiring and
interconnections.
2.1.2 CABLING
Suitable cables should be brought into the cabinet using the knockouts provided via a suitable cable gland
recommended for use with that cable. The screen or drain wire of circuits should be bonded to earth at one
location only, and should be continuous throughout the circuit. Drain wires should be terminated in the cabinet
using the earthing terminal provided.
2.1.3 CABLE LENGTHS
The maximum recommended cable length for a zone or sounder circuit is 1Km. This, however, is highly
dependent on the number and type of devices connected.
If in doubt, cable load and resistance calculations should be undetaken to ensure devices are working within
specified limits.
2.1.4 MAINS PROVISION
The mains supply to the fire alarm panel should be hard wired, using suitable three core cable (no less than 1.0
mm² and no more than 2.5mm²) or a suitable three conductor system that meets the appropriate national wiring
regulations. The panel should be fed from an isolating switched fused spur, supplied directly from the Main
Distribution Board, fused at 3A. This should be secure from unauthorised operation and be marked ‘FIRE
ALARM’.
The mains supply must be exclusive to the fire panel.
As an alternative to a switched fused spur, an appropriately fused double pole isolating device may be used
providing it meets the appropriate national wiring regulations.
All system wiring should be installed to meet BS5839 Pt 1: 2002 and BS7671
(Wiring Regulations). Other national standards of installation should be used where
applicable.
www.acornfiresecurity.com
www.acornfiresecurity.com

14
2.2 GENERAL CONVENTIONAL SYSTEM SCHEMATIC
www.acornfiresecurity.com
www.acornfiresecurity.com

15
2.3 GENERAL TWIN WIRE SYSTEM SCHEMATIC
www.acornfiresecurity.com
www.acornfiresecurity.com

16
3 INSTALLATION
3.1 SAFETY
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974 to
ensure as reasonably as is practical that the article will be safe and without risk to health when properly used.
An article is not regarded as properly used if it is used “without regard to any relevant information or advice”
relating to its use made available by the supplier.
It is assumed that the system, of which this control panel is a part, has been designed by a competent fire alarm
system designer in accordance with BS 5839 Part 1 and with regard to BS EN 54 parts 2 and 4 in the case of
control equipment and power supplies. Design drawings should be provided to clearly show the position of any
field devices and ancillary equipment.
This product should be installed, commissioned and maintained by, or under the supervision of, competent
persons according to good engineering practice and,
(i) BS 7671 (IEE wiring regulations for electrical installations)
(ii) Codes of Practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to
ensure that any appropriate information about this product is made available by you to anyone concerned with
its use.
This equipment is designed to be operated from 230VAC 50/60 Hz mains supplies and is of Class I construction.
As such it must be connected to a protective earthing conductor in the fixed wiring of the installation. Failure to
ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will
render the equipment unsafe.
These panels are designed to comply with the requirements of EN 54 part 2.
Installation of the panel should only be carried out by qualified personnel. The electronic components within the
panel can be damaged by static charge. Suitable precautions must be taken when handling circuit boards.
Never insert or remove boards or components, or connect cables, with the mains power on or batteries
connected.
This equipment must only be installed and maintained by a suitably skilled and
technically competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and
commissioned in accordance with the laid down national standards by an approved and
competent person or organisation.
This product has been manufactured in conformance with the requirements of all
applicable EU Council Directives
www.acornfiresecurity.com
www.acornfiresecurity.com

17
3.2 ESD PRECAUTION
Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD
wrist strap, suitably grounded, should be worn at all times when handling pcbs. These wrist
straps are designed to prevent the build-up of static charges, not only within a person’s body,
but on many other materials.
ESD damage is not always evident immediately; faults can manifest themselves at any time in the future.
All pcbs should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the control
panel.
3.3 GENERAL
Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely to
induce electrical interference. Earth links should be maintained on all system cables and grounded in the control
panel. The detection and sounder circuit cabling is classed as extra low voltage and must be segregated away
from mains voltage.
• Any junction boxes used should be clearly labelled FIRE ALARM.
• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control equipment.
3.4 MOUNTING THE CABINET
The site chosen for the location of the panel should be clean, dry and not subject to shock or vibration. Damp,
salt air or environments where water ingress or extremes of temperature may affect the panel must be avoided.
The temperature should be in the range -5° to +40°C, and the relative humidity should not exceed 95%.
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to re-connect
them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted level
and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove any
knockouts and ensure the cabinet is clear of swarf etc prior to refitting the PCB. Always ensure that if a
knockout is removed, the hole is filled with a good quality cable gland. Any unused knockouts must be securely
blanked off.
Knockouts should be removed with a sharp tap at the rim of the
knockout using a flat 6mm broad bladed screwdriver.
Use of excessive force will damage the enclosure around the knockout.
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
www.acornfiresecurity.com
www.acornfiresecurity.com

18
Typical panel layout
Drawing shows typical internal layout of the panel cabinet with two 3.2Ah, 12v batteries fitted
3.5 MAINS CONNECTIONS
Do not connect the mains supply to the panel until you are fully
conversant with the layout and features of the equipment.
A rating plate is attached to the power supply module describing the
nature of the supply permitted.
The incoming mains supply should be brought into the panel via one
of the knockouts provided.
A suitable cable gland must be used to secure the outer sheath of the
cable used. The earth must first be connected to the primary earth
stud (peg) marked with a symbol, using the ring crimp provided.
Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the
terminal block while leaving the earth connection intact.
www.acornfiresecurity.com
www.acornfiresecurity.com

19
3.6 CONNECTING THE BATTERIES
Batteries of even very small capacity are capable of delivering very high currents which can cause fire or injury,
therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series using the white
jumper lead provided. See diagram.
To optimise the service life of the batteries, the battery charger
output voltage varies with temperature.
N.B.
In the event of mains failure, the battery charger circuit will
protect the batteries from full discharge by disconnecting them
when they reach below 19V. When the mains supply is restored
the batteries will be automatically reconnected.
NOTE:
If the AC Mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute
until the monitoring cycle has finished polling. This is normal. If the fault doesn’t clear after 1 minute, check
connections.
3.7 BATTERY CHARGING VOLTAGE CHECKS
The battery charging voltage is factory calibrated to 27.3VDC +/- 0.2V @ 20oC. This should not normally require
adjustment. Where battery problems are experienced, the following information should be considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to
intelligent battery controls.
b) Check the power supply voltage at the 28V & 0V supply output terminals. With the batteries disconnected the
voltage should be 27.6VDC +/- 0.2V @ between 11oC - 40°C.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the battery
voltage. This should be 26.8V for a good battery or 22V for a flat battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see page 9),
checking at the 28V & 0V output terminals with a calibrated volt meter. Batteries should be disconnected and
the Access Level 3 DIL switch should be set to ‘ON’ (see page 17), which will override the temperature
compensation controls. Carefully adjust the voltage to 27.6VDC +/- 0.2V. When completed, switch off Access
Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the batteries
increase gradually. If this is not occurring, the batteries or the panel may be faulty.
www.acornfiresecurity.com
www.acornfiresecurity.com

20
4 SETUP & PROGRAMMING
4.1 TWIN WIRE MODE
What is Twin Wire?
Twin Wire is what is often referred to as Sav Wire. The technology enables sounders and beacons to be
connected to the same circuit as the detectors and call points. This can result in greatly reduced installation time
and cost.
How does it work?
In Twin Wire configuration the fire zone circuits reverse polarity in alarm condition to power the sounders and
beacons. For this reason the sounders and beacons need to be wired in opposite polarity to the detectors and
call points, i.e. zone positive wire connects to detector base and call point positive terminals but sounder and
beacon negative terminals.
Twin Wire systems require special ‘sav-wire’ detector bases and polarised call points but standard sounders.
Most modern, non-addressable, low current, polarised sounders, bells and beacons are compatible, Cooper
Fulleon, Besson, Klaxon etc.
To set Twin Wire mode for zones 1-4 on the main circuit
board, move switches 1-4 on the 7 way DIL switch located on
the main PCB to the ‘ON’ position.
Each zone can be independently set to Twin Wire, switch 1
relating to zone 1 etc.
To set Twin Wire mode for zones A-D on the zone extension circuit
boards, move switches A-D on the 4 way DIL switch located on the
zone card to the ‘ON’ position.
Each zone can be independently set to Twin Wire, switch A relating
to zone A etc.
www.acornfiresecurity.com
www.acornfiresecurity.com
Table of contents
Other Advanced Control Panel manuals

Advanced
Advanced Lux Intelligent LX-9400 User manual

Advanced
Advanced MxPro 5 Installation and operating instructions

Advanced
Advanced LIFELINE Px-100 User manual

Advanced
Advanced MxPro 4 4100S User manual

Advanced
Advanced MxPro4 Series User manual

Advanced
Advanced ExGo Series User manual

Advanced
Advanced LIFELINE Px-100 User manual

Advanced
Advanced MxPro4 Mx-4200 User manual

Advanced
Advanced Ex-3001 User manual

Advanced
Advanced Mx-5101xR User manual