MORLEY-IAS ZX1e User manual

ZX1e
ZX2e
Document No. 996-130 Issue 01
user
manual
ZX5e

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 2 of 28 Document No. 996-130, Revision: 01, User Manual
Table of Contents
1INTRODUCTION ......................................................................................................................... 4
1.1 NOTICE .................................................................................................................................. 4
1.2 WARNINGS AND CAUTIONS...................................................................................................... 4
1.3 NATIONAL APPROVALS............................................................................................................ 4
2USER CONTROL LEVELS......................................................................................................... 5
2.1 LEVEL DEFINITION .................................................................................................................. 5
2.2 USER PASSWORDS ................................................................................................................. 5
3CONTROLS AND DISPLAYS .................................................................................................... 6
3.1 CONTROL KEYS ...................................................................................................................... 6
3.2 FRONT PANEL LED INDICATIONS............................................................................................. 7
3.3 ALPHANUMERIC DISPLAY INDICATIONS..................................................................................... 9
3.3.1 Normal Condition .......................................................................................................... 9
3.3.2 Display Examples – Fire Alarms ................................................................................... 9
3.3.3 Display Examples – Faults............................................................................................ 9
4LEVEL 1 DISPLAY / CONTROL FUNCTIONS ........................................................................ 10
4.1 NORMAL CONDITIONS ........................................................................................................... 10
4.2 AC MAINS POWER FAIL CONDITIONS..................................................................................... 10
4.3 FIRE ALARM CONDITIONS...................................................................................................... 10
4.3.1 Override Delays .......................................................................................................... 10
4.4 FAULT CONDITIONS .............................................................................................................. 10
5LEVEL 2 CONTROL FUNCTIONS ........................................................................................... 11
5.1 POWER FAILURE CONDITION ................................................................................................. 11
5.1.1 AC Mains Power Failure Indication............................................................................. 11
5.1.2 Battery Low / Charger Failure ..................................................................................... 11
5.2 FAULT CONDITIONS .............................................................................................................. 12
5.2.1 Fault Indication............................................................................................................ 12
5.2.2 User Actions................................................................................................................ 12
5.3 FIRE ALARM CONDITIONS...................................................................................................... 12
5.3.1 Fire Alarm Indications ................................................................................................. 12
5.3.2 User Actions................................................................................................................ 12
5.4 USER OPTION FUNCTIONS .................................................................................................... 13
5.4.1 Test ............................................................................................................................. 14
5.4.1.1 LED Test ...............................................................................................................................14
5.4.1.2 LCD Test ...............................................................................................................................14
5.4.1.3 Zones Test ............................................................................................................................14
5.4.1.3.1 Configuring the Test........................................................................................................14
5.4.1.3.2 Terminating the Test .......................................................................................................15
5.4.1.3.3 Inspecting Other Conditions During a Walk Test.............................................................16
5.4.1.4 Output Test ...........................................................................................................................16
5.4.1.5 Audible Indicator Test ...........................................................................................................17
5.4.2 Time ............................................................................................................................17
5.4.3 Enable / Disable Functions ......................................................................................... 17
5.4.3.1 Enable or Disable Zones....................................................................................................... 18
5.4.3.2 Enable or Disable Inputs .......................................................................................................18
5.4.3.3 Enable or Disable Keys.........................................................................................................19
5.4.3.4 Enable or Disable Delayed Day Modes................................................................................. 20
5.4.3.4.1 Configure Day Mode Delay Period / Disable Operation .................................................. 20
5.4.3.4.2 Manual Override.............................................................................................................. 20
5.4.3.5 Enable or Disable Outputs ....................................................................................................21
5.4.3.6 Enable or Disable Delays ...................................................................................................... 21
5.4.4 Print............................................................................................................................. 22
5.4.5 View ............................................................................................................................23
6DELAYED DAY MODE OPERATION ...................................................................................... 24

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 3 of 28
7LEVEL 3 PROGRAMMER FUNCTIONS...................................................................................24
8LOG BOOK ................................................................................................................................25
Table of Figures
FIGURE 1– ZX1E, ZX2E CONTROLS AND DISPLAYS...............................................................................6
FIGURE 2- ZX5E CONTROLS AND DISPLAYS...........................................................................................6
FIGURE 3- SYSTEM CONTROL LED DISPLAY ..........................................................................................7
Table of Tables
TABLE 1– CONTROL KEY FUNCTIONS.....................................................................................................6
TABLE 2- ALPHANUMERIC AND INTERACTIVE CONTROL KEYS ..................................................................7
TABLE 3- LED FUNCTIONS ....................................................................................................................8
TABLE 4- USER MENU OPTIONS ..........................................................................................................13
TABLE 5- VIEW MODE OPTIONS ...........................................................................................................23
TABLE 6- LOGBOOK REFERENCE DATA ................................................................................................25
TABLE 7- LOGBOOK EVENT DATA.........................................................................................................26

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 4 of 28 Document No. 996-130, Revision: 01, User Manual
1 Introduction
1.1 Notice
• The material and instructions covered in this manual have been carefully checked for accuracy and are
presumed to be correct. However, the manufacturer assumes no responsibility for inaccuracies and
reserves the right to modify and revise this document without notice.
• These instructions cover the use and operation of the Fire Alarm Control
Panel. Refer to the Installation Manual (P/N 996-131) for details of how to
install the system and refer to the Commissioning Manual (P/N 996-132) for
information on programming and Level 3 functions.
• The ZX1E, ZX2E and ZX5E Fire Alarm Control Panels are 1, 1-2 and 1-5 loop panels for use with
analogue addressable devices from the following detector manufacturer ranges: -
Apollo
S90
Hochiki
Morley-IAS
Nittan
System Sensor
1.2 Warnings and Cautions
These instructions contain procedures to follow in order to avoid injury and damage to
equipment. It is assumed that the user of this manual has been suitably trained and is
familiar with the relevant regulations.
All equipment is to be operated in accordance with the appropriate standards applicable
1.3 National Approvals
This equipment must be installed and operated in accordance with these instructions and the
appropriate national, regional and local regulations specific to the country and location of the
installation. Consult with the appropriate Authority Having Jurisdiction (AHJ) for confirmation of the
requirements.
For use with software
version 800 onwards

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 5 of 28
EN54
!
EN54-2 13.7
Maximum of 512
sensors / manual
call points per
panel.
• The ZX1E, ZX2E & ZX5E range of panels has many features, which if used
inappropriately, may contravene the requirements of EN54. Where such a
possibility may arise, a suitable warning is given with brief details of the
EN54 requirement and the relevant section it pertains to. A typical EN54
non-compliance warning is illustrated.
2 User Control Levels
2.1 Level Definition
• The ZX1E, ZX2E and ZX5E Fire Alarm Control Panels have three user control levels.
• At all three levels, the LED Displays indicate the condition of the installation, the Zone LED Displays
indicate the location of any fire alarm or fault and the alphanumeric display gives more detailed fire alarm
or fault information.
• At USER LEVEL 1, all the displays are functional but the front panel control keys are inhibited.
• At USER LEVEL 2, all front panel controls are functional and some system operation parameters and
functions can be changed. User Level 2 is reached by entering a password from level 1.
• At USER LEVEL 3, all front panel controls are functional and full system configuration and programming is
possible. User Level 3 is reached by entering a password from either Level 1 or Level 2. User Level 3 is
intended for use by the system installer / maintenance contractor.
2.2 User Passwords
• Up to ten USER LEVEL 2 passwords can be programmed into the panel.
• The USER LEVEL 2 passwords can be assigned / changed at Level 3 by the installer / maintenance
contractor. Level 2 passwords do not allow access to Level 3 functions.

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 6 of 28 Document No. 996-130, Revision: 01, User Manual
3 Controls and Displays
3.1 Control keys
• The control panel has two groups of control keys.
• A bank of five keys contains the four system control keys: Sound Alarms, Silence / Resound, Mute,
Accept and System Reset.
• A bank of 17 keys contains interactive and alphanumeric keys.
1 2 3 4 5 6 7 8 9 101112131415 161718 19 20
ZM
9
WJ
>
X
K
<
YL
6
TG
7
UH
8
VI
3
QD
4
RE
5
SF
0
NA
1
OB
2
PC
1 2 3 4 5 6 7 8 9 1011121314151617181920
41 4 2 43 44 45 4 6 4 7 4 8 49 5 0 51 52 53 5 4 55 56 5 7 58 59 60
ZM
9
WJ
>
X
K
<
YL
6
TG
7
UH
8
VI
3
QD
4
RE
5
SF
0
N
A
1
OB
2
PC
21 2 2 23 24 25 2 6 2 7 2 8 29 3 0 31 32 33 3 4 35 36 3 7 38 39 40
61 6 2 63 64 65 6 6 6 7 6 8 69 7 0 71 72 73 7 4 75 76 7 7 78 79 80
Figure 1 – ZX1E, ZX2E Controls and Displays Figure 2 - ZX5E Controls and Displays
Key Legend Symbol Function
Sound Alarms
Press to Turn on ALL Sounder Outputs (i.e. evacuate building
manually).
Silence /
Resound
Press to Turn off all activated sounders.
Press again to re-activate the sounders.
Mute Buzzer
Press to silence the internal buzzer.
Accept
Press to accept a Stage 1 Investigation Delay Alarm
System Reset
Press to cancel all alarm conditions and reset the panel.
Table 1 – Control Key Functions
• The alphanumeric keys normally function as a numeric keypad. During programming, these keys can be
toggled to Letter Keys by pressing the CHANGE key. This gives access to letters A-M. For access to
letters N-Z, press and hold the SHIFT key whilst pressing the appropriate letter key.
Alphanumeric Display
System Status LED
Display
Control Keys
Zone LED Display
Program / Interactive
Keys
Optional Zone LED
Display

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 7 of 28
Key Legend Symbol Function
0 to 9 Press to enter numbers 0-9 or letters A-J (N-W with Shift)
> Press to scroll through fire alarms or faults manually on the display or
letter K (X with Shift)
< Press to scroll back through fire alarms or faults manually on the
display or letter L (Y with Shift)
Change
ZM
Press to change a display option (where allowed)
or letter M (Z with Shift)
Enter
Press to confirm entry of a multiple digit number
No
Press to answer No, or terminate a display option
Yes
Press to answer Yes, or step through a display option
Shift
Press to show user options on the display
Press, during programming, to allow entry of Letters N-Z
Table 2 - Alphanumeric and Interactive Control Keys
• The control keys are disabled at USER LEVEL 1. Pressing the SHIFT key will cause the display to prompt
for entry of the Level 2 password. The password must be entered to re-enable the control keys at Level 2.
3.2 Front Panel LED Indications
• The Level 1 LED Indicators are divided into two
sections.
• The upper array of LED Indicators shows the
operational conditional of the panel and the
installation.
• The lower array of Zone LED indicators shows
the location of a fire alarm or fault.
• The standard Zone LED Indicators provide
identification for up to 20 zones. On the ZX5E
panel, this can be extended by adding either a
further 20 zones (to give a total of 40 zones) or a
further 60 zones (to give a total of 80 zones).
• The LED Indicators illuminate as red, yellow or
green to give a clear indication of the panel
status as follows:
FIR
E
FAUL
T
System / CPU Faul
t
A
cknowledge
d
Earth Faul
t
Disablemen
t
Tes
t
Sounder Faul
t
Delayed Mode
Relays Disable
d
Powe
r
Supply Faul
t
A
larms Silence
d
Sounders Disable
d
Figure 3 - System Control LED Display

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 8 of 28 Document No. 996-130, Revision: 01, User Manual
Indicator Colour Function How to Clear
FIRE Red The panel has detected a fire alarm
condition, or the ‘Sound Alarms’ key
has been pressed.
Correct the condition causing the
alarm and then perform a panel
reset.
Fault Yellow The panel has detected a fault. Correct the condition causing the
fault and then perform a panel reset.
Acknowledged Yellow A fault or alarm has been
acknowledged and the internal
buzzer silenced.
Correct the condition causing alarm
or fault and then perform a manual
reset. NOTE: If another alarm or fault
occurs, the internal buzzer
automatically resounds.
Disablement Yellow Part of the system, either input or
output, has been disabled manually
by the user.
Re-enable the device or devices.
Refer to Disablement Function.
Test Yellow The system is in test mode. Zone
LED indicators show which zones
are being tested.
Cancel test when finished.
Sounder Fault Yellow This indicates a wiring fault with one
of the sounder output circuits.
Correct the fault condition and then
perform a panel reset.
Delayed Mode Yellow This indicates that the system is
operating with delays to the sounder
outputs and the delays are active (in
force).
The delays may be enabled or
disabled. Refer to Disablement
Function.
Relays Disabled Yellow The relay outputs have been
disabled.
Refer to Disablement Function.
Earth Fault Yellow An earth connection fault has
occurred on a cable.
Correct the fault condition and then
perform a panel reset.
System / CPU Fault Yellow The CPU has reset or a system fault
has occurred.
Correct the problem, if appropriate,
and then perform a panel reset.
Sounders Disabled Yellow The sounder outputs have been
disabled.
Refer to Disablement Function.
Alarms Silenced Yellow The sounder outputs have been
silenced.
Correct the alarm condition and then
perform a panel reset. NOTE: Press
SILENCE / RESOUND again to
reactivate the sounders. If a new
alarm occurs, the alarms will
resound.
Supply Fault Yellow There is a problem with the power
supply, battery or supply input.
Correct the fault condition and then
perform a panel reset.
Power Green STEADY: Indicates AC Power is
present. FLASHING: Indicates a loss
of AC Power.
See Supply Fault.
Zone FIRE Red FLASHING: The zone is in a fire
alarm condition.
Correct the alarm condition and then
perform a panel reset.
Zone Fault Yellow FLASHING: The zone contains faulty
devices.
STEADY: The zone is either disabled
or in test mode.
Correct the fault condition and then
perform a panel reset.
Re-enable devices or cancel test
mode.
Table 3 - LED Functions

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 9 of 28
3.3 Alphanumeric Display Indications
• The alphanumeric liquid crystal display gives 80 characters of information on a 2-line display. The display
is illuminated to assist viewing under dim ambient light conditions.
• When the numeric keypad is not in use, the display will revert to automatically scrolling through any fire
alarm or fault conditions present on the panel. If there are no alarm or fault conditions, the display will
show the date and time.
• Pressing the SHIFT key will show a list of optional functions or prompt for the level 2 password.
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys?
3.3.1 Normal Condition
03-Oct-2001 11.38
All devices are inside working limits.
3.3.2 Display Examples – Fire Alarms
1 of 1 FIRE [1]
ALARM RAISED FROM CONTROL PANEL
2 of 2 FIRE MCP L2 A002 [1]
< - Zone Text - > < - Device Text - >
3.3.3 Display Examples – Faults
1 of 1 [1]
OPEN CIRCUIT ON SOUNDER B
2 of 8 No reply L2 A001 [1]
< - Zone Text - > < Device Text - >
This number is the
panel address number
assigned to the panel
in a network system.

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 10 of 28 Document No. 996-130, Revision: 01, User Manual
4 Level 1 Display / Control Functions
• At Level 1, the panel operates in a display only mode with the control keys disabled.
• If fire alarm or fault conditions exist, the LED Indicators will show these. Detailed information will be
scrolled on the alphanumeric display.
• The information on the alphanumeric display can be scrolled manually by pressing either the >(forward)
or the <(back) keys.
4.1 Normal Conditions
• When the system is in a normal condition, the green AC Power LED will be illuminated. The alphanumeric
display will show the time and date and will alternate between a user programmed text message and a
system status message.
4.2 AC Mains Power Fail Conditions
• If the AC MAINS power source is interrupted, the AC Power LED will flash. In addition, the internal buzzer
will sound.
• The back light illumination of the alphanumeric display will be turned off, the display will show an “AC Fail”
message and the Supply Fault LED and Fault LED Indicators will be lit.
• If both the AC MAINS input and the Battery Standby Input fail then all LED and alphanumeric display
indicators will be off.
4.3 Fire Alarm Conditions
• If the control panel initiates an alarm condition, the FIRE LED Indicators will be illuminated and, if
appropriate, the relevant ZONE FIRE LED Indicators will flash. The internal buzzer will sound and the
alphanumeric display will give detailed information regarding the fire alarm location.
• If more than one fire alarm condition is present, the alphanumeric display will either automatically scroll
through or, can be manually scrolled through, the fire alarms registered.
4.3.1 Override Delays
EN54
9
EN54-2 7.11d
Override delays at
Level 1
• If the ZX1E, ZX2E and ZX5E control panels are
configured to operate with delays to outputs, a
manual call point (MCP) will be located next to the
panel.
• To override any delays and immediately activate the
bells and other fire alarm output devices, break the
glass in the call point.
BREAK GLASS
Press Here
FIRE
4.4 Fault Conditions
• If the panel detects a fault, the FAULT LED is illuminated along with other appropriate system condition
LED Indicators. The alphanumeric display gives detailed information regarding the nature of the fault and
the panel buzzer will sound.
• If more than one fault condition is present, the alphanumeric display will either automatically scroll through
or, can be manually scrolled through, the faults registered.

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 11 of 28
5 Level 2 Control Functions
• All of the functions and operational features described for Level 1 user are available and are the same for
a Level 2 user.
• To enable Level 2 operation, press the SHIFT key. The display will then show:
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys?
• Press the YES key and the display will prompt for entry of the password.
[Panel ACTIVE Control Keys INHIBITED] [1]
Please Enter Password
• Enter the 4-digit Level 2 password. The display then shows the Main Menu of user options.
[ACTIVE] 1)Commission 2)Test 3)Time [1]
4)Enable 5)Disable 6)Print 7)View
• If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display
showing the system status message. To re-show the menu display, press the SHIFT key.
• If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then
‘Level 2’ access will be automatically cancelled. It will be necessary to re-enter the password to re-activate
Level 2 functions.
5.1 Power Failure Condition
5.1.1 AC Mains Power Failure Indication
• If the AC MAINS input is interrupted, the AC Power LED will flash and the panel buzzer will sound.
• The back light illumination of the alphanumeric display will be turned off, the alphanumeric display will
show an ‘AC Fail’ message and the Supply Fault LED Indicator will be lit.
• If both the AC MAINS input and the Battery Standby Input fail then all LED and alphanumeric display
indicators will be off.
• To silence the panel buzzer, press the MUTE BUZZER key.
• When the AC MAINS is restored, the AC Power LED returns to steady on.
• To clear the latched AC MAINS Fault, press the SYSTEM RESET key.
• When MUTED, the buzzer will continue to sound a short beep every 30 seconds. This gives an on-going
warning of the continued AC Mains Failure condition.
5.1.2 Battery Low / Charger Failure
• If the battery becomes disconnected or the battery voltage is less than 21V DC or if there is a failure in the
circuitry that charges the battery, then the panel shows a ‘Battery Low / Charger Failure’ message.
• To silence the panel buzzer, press the MUTE BUZZER key.
• To clear the latched Fault, press the SYSTEM RESET key. If the fault is still present it will be redisplayed.

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 12 of 28 Document No. 996-130, Revision: 01, User Manual
5.2 Fault Conditions
5.2.1 Fault Indication
• If the panel detects a fault, the FAULT LED is illuminated along with other appropriate system condition
LED Indicators. The alphanumeric display gives detailed information regarding the nature of the fault and
the panel buzzer will sound.
5.2.2 User Actions
• To acknowledge the event and to silence the panel buzzer, press the MUTE BUZZER key. The
ACCEPTED LED will then be illuminated.
• The panel will not allow a reset until the source of the fault is corrected. If necessary, the panel allows the
disabling of individual points and zones.
• After correcting the problem, press the SYSTEM RESET key. The FAULT, ACCEPTED and other
appropriate system status LED Indicators will be turned off. The alphanumeric display returns to normal
mode.
5.3 Fire Alarm Conditions
• The panel will indicate a fire alarm condition if it detects an alarm condition or if the SOUND ALARMS key
is pressed.
5.3.1 Fire Alarm Indications
• If the control panel initiates an alarm condition, the FIRE LED Indicator will be illuminated and, if
appropriate, the relevant ZONE FIRE LED Indicators will flash. The internal buzzer will sound and the
alphanumeric display will give detailed information regarding the fire alarm location.
• To test the alarm system, or to evacuate the building, press the SOUND ALARMS key. The panel will
activate all the sounder output circuits, will illuminate the FIRE LED Indicator and the alphanumeric
display will indicate a ‘Manual Evacuation’.
5.3.2 User Actions
• Press the MUTE BUZZER key to acknowledge the event and to turn off the internal buzzer. The
ACCEPTED LED is turned on.
• Press the SILENCE / RESOUND key to silence the sounder output circuits. The SOUNDERS SILENCED
LED is turned on. Press the SILENCE / RESOUND key again to reactivate the sounder outputs.
• Press the SYSTEM RESET key to reset the system.

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 13 of 28
5.4 User Option Functions
[ACTIVE] 1)Commission 2)Test 3)Time [1]
4)Enable 5)Disable 6)Print 7)View
• The optional functions available to the user at Level 2 are as follows:
Function Description
Commission This option is not available to Level 2 users. It requires the entry of
the Level 3 password before the programming mode can be entered.
Test Allows the user to test parts of the system. The following tests can be
performed:
LED To test the LED indicator lamps. This test will
automatically test each zone indicator and then
terminate.
LCD To test the alphanumeric display.
ZONES To perform a ‘Walk Test’ on one or more zones.
OUTPUTS To test the relay and sounder outputs connected to the
system. This test is only available to Level 3 users.
Time To change the date and time in the panel.
Enable To enable zones, inputs, outputs, delays and day mode operation.
Disable To disable zones, inputs, outputs, keys, delays and day mode
operation.
Print To print various reports on an internal or remote printer.
View To view devices and system status conditions.
Table 4 - User Menu Options

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 14 of 28 Document No. 996-130, Revision: 01, User Manual
5.4.1 Test
• To display the Test Menu, press ‘2’ and the display shows:
1)LEDs 2)LCD 3)Zones 4)Outputs
5)Audible Indicator
• The test menu allows the user to test:
1. The LED’s on the front panel display.
2. The alphanumeric (liquid crystal) display.
3. The detection and alarm initiating devices connected to the signaling loop.
4. The sounder outputs and other alarm condition output devices connected to the system.
5. The internal buzzer.
5.4.1.1 LED Test
• To select the option, press ‘1’.
• To terminate the test, press No.
• The panel will flash all of the indicators on the LED Display and will step through all of the Zone FIRE and
FAULT indicators.
5.4.1.2 LCD Test
• To select the option, press ‘2’.
• To terminate the test, press No.
• The alphanumeric display will flash all displayable characters in all positions of the display and then return
to the menu.
5.4.1.3 Zones Test
5.4.1.3.1 Configuring the Test
• The ‘Walk Test’ option allows the user to conveniently test the detection and alarm initiating devices
without having to continually reset the panel.
• To select the option, press ‘3’.
If no action is taken at this point, the display will automatically revert to the normal display
after 1 minute. Pressing SHIFT or > will return the display to the test display.
• The display will then prompt for whether the sounder outputs should ring:
Ring Bells?
• Press Yes and the sounders (dependent on their programming) will ring for a few seconds and then be
reset automatically when a device is tested. (NOTE: Relay Outputs are never activated).
• Press No and the sounders will not ring.
• The panel can be set to test a range of zones. The display will prompt for the first zone to be tested:

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 15 of 28
Test from zone?
(Please key in number, then press “Enter”)
• Key in the number of the first zone to be tested. For example, for zone 12, press ’12 ENTER’.
• The display then prompts the last zone to be tested:
Test from zone 12 to zone ?
(Please key in number, then press “Enter”)
• Key in the number of the last zone to be tested. For example, for zone 15, press ‘15 ENTER’.
• The ‘Walk Test’ is then entered and the display will show a scrolling ‘W’ alternating with a ‘Press No to
Exit’ on the bottom line:
Test from zone 12 to zone 15
-----W-------------------------------------
When the display indicates that the panel is in ‘Walk Test’, the display will continue to show
that walk test mode is active.
• In the above example, any detector or initiating device going into alarm condition in zones 12, 13, 14 or 15
will:
1. Display an activation message on the alphanumeric display, write the event in the event log, sound
the panel buzzer and illuminate the appropriate zone FIRE LED.
2. Turn on the LED at the sensor that initiated the alarm
3. After a few seconds, the panel will be automatically be reset and the detector LED turned off. The
panel is then ready to test the next detector. (Note: Up to 30 seconds is allowed for smoke
detectors to clear).
• If an alarm signal is received from a zone other than those under test, then all sounder output and relay
output circuits will activate as programmed for the zone in alarm. The sounders will continue to ring until
silenced from the panel.
5.4.1.3.2 Terminating the Test
EN54
9
EN54-2 10.1 b
Walk Test:
• To terminate the walk test mode the ‘NO’ key MUST be pressed.
• On exiting the walk test function, the panel shows the following message for 20 seconds:
Walk Test Terminating
Please wait
• This operation is to ensure that the test conditions (for example, smoke in the detector chamber) have
cleared before returning the panel to normal operation, thereby avoiding unexpected fire alarm conditions.

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 16 of 28 Document No. 996-130, Revision: 01, User Manual
5.4.1.3.3 Inspecting Other Conditions During a Walk Test
EN54
9
EN54-2 5.1
Display of
functional
conditions:
• To inspect Fire, Fault or Disablement Conditions whilst a walk test is in
progress, press the ‘>’ key.
• This returns the display to the menu options from which all other operating conditions can be inspected.
• To cancel the walk test, re-select the Zones Test Option. The display will then return to the normal walk
test view, showing the current walk test in operation. For example:
Test from zone 12 to zone 15
-----W-------------------------------------
• Then press the ‘NO’ key to cancel the test.
5.4.1.4 Output Test
Access to this test option is only available to users with the Level 3 password.
• To select the option, press ‘4’ and then enter the password ‘####’.
• To terminate the test, press No.
• The output test allows the relays and sounders to be individually operated. The first six outputs are
reserved for the panel’s own onboard relay and sounder circuits as shown below:
Output 1 – Onboard Relay 1
Output 2 – Onboard Relay 2
Output 3 – Onboard Sounder A
Output 4 – Onboard Sounder B
Output 5 – Onboard Sounder C (Only available on ZX5E panel!)
Output 6 – Onboard Sounder D (Only available on ZX5E panel!)
• On entering the test, the display will show the current state of the first output:
RELAY OPERATED
1
• To advance to the next output, press the >or the YES key.
RELAY NOT OPERATED
2
• To change the output state, press the CHANGE key. The display will show the new state:

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 17 of 28
RELAY OPERATED
2
The onboard sounder circuits are constantly monitored for correct end-of-line termination. A
sounder error will be reported if one of the sounders is left in the operated test state for
more than 5 seconds.
5.4.1.5 Audible Indicator Test
• To select the option, press ‘5’.
• The buzzer will beep.
5.4.2 Time
• To change the date and time shown on the alphanumeric display, press ‘3’ from the main user option
menu.
On multi-panel systems, it is only necessary to change the time at the Master Panel. All of
the other panels will synchronize their date and time to that of the master panel when a reset
is performed on the master panel.
5.4.3 Enable / Disable Functions
• To select the enable or disable menu options, press ‘4’ or press ‘5’ as required from the user main menu.
The display shows for each option:
ENABLE 1)Zone 2)Input 3)Keys
4)Day Mode 5)Outputs 6)Delays
DISABLE 1)Zone 2)Input 3)Keys
4)Day Mode 5)Outputs 6)Delays
• The options available in each menu are identical. This allows the user to enable or disable:
1. Zones
2. Individual devices
3. Panel Keys
4. Day Modes
5. Outputs (Sounders or relays)
6. Delays
• Whenever an enable operation is performed, the action is carried out but the disablement is not removed
from the LCD. The following is shown momentarily on the display.
Press RESET to clear disablements from
scrolling event display
• To clear the entries from the display event history, press the “SYSTEM RESET” button.

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 18 of 28 Document No. 996-130, Revision: 01, User Manual
5.4.3.1 Enable or Disable Zones
• To enable or disable input devices by zone, select option 1.
Any loop driven output devices such as sounders or relay modules will still activate as
programmed even if disabled. Only the input signal from these devices will be ignored.
• Press ‘1’ and the display will prompt for the required zone number.
Disable Zone ?
( Enter number or use “>” to scroll )
• Key in the zone number and then press the ENTER key. Or use the > key to scroll through the zones.
Disable Zone 14 OK ?
• The display will then repeat the zone number and ask for confirmation (OK?). Press the YES key to
confirm.
• The panel will enable or disable all of the input devices in the zone including smoke, temperature and call
points.
• When a zone is disabled, the DISABLEMENT LED and the corresponding yellow Zone FAULT LED will
be illuminated.
(NOTE: If the panel is installed and programmed to operate in accordance with BS5839 then disabling a
zone does NOT disable call points within that zone).
5.4.3.2 Enable or Disable Inputs
• To enable or disable individual input devices, select option 2.
Any loop driven output devices such as sounders or relay modules will still activate as
programmed even if disabled. Only the input signal from these devices will be ignored.
• Press ‘2’ and the display will prompt for the signalling loop circuit number where the device is located.
Loop _
• Enter the required loop number (1 for ZX1E, 1-2 for ZX2E or 1-5 for ZX5E) and the display will prompt for
the numeric address of the device:
Loop 2 Address ____

ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS
User Manual Document No. 996-130, Revision: 01, Page 19 of 28
• Enter the address of the device required. If the address is less than 3-digits long (for example address
34), this can be entered as either 034 or 34 followed by ENTER.
• The display will then ask for confirmation (OK?).
Loop 2 Address 34 OK ?
• Press the Yes key to confirm.
• When an individual point is disabled, the DISABLEMENT LED will be illuminated.
• The corresponding Zone FAULT LED will only be illuminated if all devices in the zone are disabled.
Networked Panels
• Master panels are able to command other panels to enable or disable individual devices.
• In this case, the display will prompt with an additional, opening question requesting the panel (CPU)
number.
CPU __
• Enter the address of the required panel. The display will then prompt for the loop and device address
information as described above.
5.4.3.3 Enable or Disable Keys
• To disable the panel control keys, press ‘3’ from the disable menu.
• The user Level 2 password will then be required to re-enable the panel control keys and provide access to
the User Option Functions.
The panel keys will be automatically disabled if a key has not been pressed for a pre-
programmed period.

MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels
Page 20 of 28 Document No. 996-130, Revision: 01, User Manual
5.4.3.4 Enable or Disable Delayed Day Modes
• The Delayed Day Mode operation is configured at Level 3 by the installer / maintenance contractor.
• For example, the Delayed Day Mode may be set to be active between 8:00 and 17:00. Outside of these
hours, a fire alarm condition will immediately sound the bells and activate outputs.
• The Delayed Day Mode causes the panel to respond to high sensor signals by sounding the panel buzzer
and displaying a warning message on the alphanumeric display. The panel delays the activation of the
alarm condition outputs (sounders or relays) for a programmed period.
• The user may enable or disable the operation of the Delayed Day Mode through the Enable or Disable
Menus.
• To select Delayed Day Mode, press ‘4’ from the Enable or Disable Menus. The display now presents two
options:
Disable:
1)Configure the Day Mode Delay Period
2)Temporary Override – Turn Off Delays
Enable:
1)Disable the Day Mode Delay Period
2)Temporary Override – Turn On Delays
5.4.3.4.1 Configure Day Mode Delay Period / Disable Operation
• To select configure or disable options, press ‘1’.
• When enabling the operation of the Delayed Day Mode function, the display prompts for the number of
days the Delayed Day Mode is to be in operation.
Use day mode for the next 2 days OK ?
• If the prompted number of days is not as required, press the CHANGE key and then enter the required
number of days.
• In the above example, the Delayed Day Mode will be effective for today and tomorrow. The day after
tomorrow, the panel will go immediately into a full fire alarm condition on receiving a high signal from a
device.
• The number of days can be selected in the range 001 to 199. To permanently enable the Delayed Day
Mode operation, enter the number of days as 200.
• When Disable Day Mode Delay is selected, the Stage 1 / 2 Day Mode Delay Function is completely turned
off.
5.4.3.4.2 Manual Override
• The manual override facility provides a means to override the scheduled time clock for operation of the
stage 1 / 2 Day Mode Delay.
• If the Turn-On Delays option is selected, the Stage 1 / 2 function will be turned on immediately. It will
automatically turn off again at the end of the next scheduled time.
• If the Turn-Off Delays option is selected, the Stage 1 / 2 function will be immediately turned off. It will
automatically turn on at the start of the next scheduled time.
Other manuals for ZX1e
1
This manual suits for next models
2
Table of contents
Other MORLEY-IAS Control Panel manuals
Popular Control Panel manuals by other brands

KitchenAid
KitchenAid KESS300B reference guide

CAME
CAME zl92 installation manual

Technicolor - Thomson
Technicolor - Thomson LDK 4629/00 Technical manual

MSA
MSA M1 operating manual

THOMSON
THOMSON Grass Valley Triton installation manual

WindowMaster
WindowMaster CompactSmoke WSC 104 S AR installation instructions