MULTI MEASURING INSTRUMENTS CO.,LTD. MCL-4000F User manual

3CT METHOD LEAKAGE CURRENT METER
MCL-4000F
INSTRUCTION MANUAL
Thank you very much for selecting our model MCL-4000F
LeakageCurrentMeter.
Before use the instrument, read this instruction manual
completely and familiarize yourself thoroughly with all
functions.
Keepthisinstruction manual carefully to take out
wheneveryouneed.
MULTIMEASURINGINSTRUMENTSCO.,LTD.
Akihabara Murai Bldg. 7F 1-26, Kanda Sakuma-cho,
Chiyoda-ku, Tokyo, Japan, 101-0025
TEL : +81-3-3251-7013 FAX : +81-3-3253-4278
HomePage:http://www.mutimic.com/
E-mail:[email protected]

SAFETYSUMMARY observe by all means
● To use this instrument safely, read this "SAFETY SUMMARY" carefully and
apply the instrument correctly.
● The CAUTIONs and WARNINGs which appear on the following pages are stated
to prevent the operator & other people from the dangers and their properties from
the damages beforehand.
△ WARNING : This symbol indicates the contents "Possibilities of the death or
theseriouswoundcan be supposed" caused from mis-operations.
△ CAUTION : This symbol indicates the contents "Possibilities of the injury or
onlythematerialdamagecanbesupposed"causedfrommis-
operations.
○ OPERATION ENVIRONMENT
△ CAUTION
● Do not use or storage this instrument under the condition of direct rays of the
sun high temperature & humidity and or condensation, as it may cause the
deformation and or the isolation defect of the instrument.
● Do not use this instrument in the environment influenced by acids, alkalis,
organic solutions. corrosive gas, etc.
● Do not use or storage this instrument where the mechanical vibration can be
directly transmitted, as it may cause defect of the instrument.
● Do not use this instrument nearby the appliances which generate strong
magnetic field and or electric field, as it may cause mis-movement of the
instrument.
● This instrument does not have the water / dust-proof structure. Do not use this
instrument in the environment with a lot of dust and drops of water, as it may
cause defect of the instrument.
○ OPERATION CONDITION & CONNECTION
△ WARNING
POSSIBLE ELECTRICAL SHOC
K
● This instrument is for the use of low voltage circuit.
Do not make measurements of power lines carrying more than AC 500V.
Before use, check and confirm the voltage of circuit to be measured.
● Apply only the coated cables and do not clamp bare cables.
POSSIBLE ELECTRICAL SHOCK OR ACCIDENT
● Do not handle the instrument in the rain, at humid place, with a drop of water
and or with wet hands.
● Do not use the instrument if the CT or CT case are damaged and if something is
wrong with the CT cables.
● If excessive current is applied to the CT, the instrument will be heated and
damaged. Use the CT according to the rating current.

1.GENERAL
3CT/4CT Method Leakage Current Meter (Model MCL-4000F) measures the leakage
current and or the line current in low voltage circuit. The ordinary clamp can measure
the leakage current by clamping CT to the conductors en bloc but the actual measuring
fields where CT can be clamped en bloc are very limited. This model MCL-4000F can
measure the leakage current by clamping CTs respectively to each phase of conductors.
2.SPECIFICATIONS
2-1 Current Detection CT
Inside Diameter of CT :φ36mm
Remanence Current : less than 10mA at 100A of 3P/3W in balance
Withstanding Voltage : AC2000V, 1 minute between CT core and outer case
Dimension & Weight : 96(W)x120(H)x42(D)mm, 430g
2-2 Measuring Part
Measuring Function :Leakage Current (4CT/3CT/2CT & grounding line) and
Line Current
Measuring Method : Clamp CT Method
MeasuringRange :0~20mA/2000mA (Leakage)
0~800A (Line Current)
RangeSwitch :3rangemanual
AC Conversion : Average Rectification
ADConversion :DoubleIntegrationMethod
SamplingRate :2times/second
Display : LCD, max. reading 1999 with annunciator
Over Range Indication : Blanking of all digit except MSD 1 (except 800A range)
Data Hold Function : "DH" sign on the display
Low Battery Indication : "B" sign on the display
Output Signal for Recorder: DC100mV full scale to each range except 800A
(DC40mV to 800A range)
Output Impedance : Less than 10KΩ
High Frequency Cut : Low Pass Filter (130Hz)
‐1‐

2-3 General Specification
Limitation of Circuit Voltage : Low Voltage Circuit less than AC500V
Withstanding Voltage : AC2000V, 1 minute
Operating Temperature : 0~40℃, less than 80%RH ( non-condensing)
Storage Temperature : -10~60℃, less than 80%RH ( non-condensing)
PowerSupply :UM-4(1.5V)x2
Consumption Current : 2mA (approx. 200h continuous)
Dimension & Weight : 130(W)x172(H)x38(D)mm, 380g
Standard Accessories : Battery/2, Carrying Case/1, Detection CT/3,
Instruction Manual/1
Option : CT for 3P/4W ( Model No. MCL-4000F-NCT )
2-4 Accuracy
Function Range Resolution Accuracy(45~65Hz)
Leakage
Current
200mA 0.1mA
1.0%±5dgt
2000mA 1mA
Line Current 800A 1A 1.0%±5dgt
Output Signal for Recorder ±1.5% F.S.
‐2‐

3. NAME OF PART & EXPLANATION
①Power On/Off Switch : Switch to supply the power to the instrument
②LINE/LEAK Switch : “LINE” for line current measurement and
“LEAK”forleakagecurrentmeasurement
③Range Switch : Manual range switch to select 200mA/2000mA
④FL(Filter)Switch :Switchtocuthighfrequencycomponent
⑤DataHoldSwitch :Switchtoholdthedisplayedvalue
⑥LCD Display : Display of measured value, symbol and sign
⑦BatteryCover :Toreplace the battery, remove this part
⑧TerminalStand :Forconnection of CT, according to wiring method
Wiring Method
①Leakage of Grounding Line : Connect “R” phase CT
and Line Current to “N” phase terminal
②3P/3W Leakage Current : Connect each “R”, “S” &
”T” phase CT to the
respective terminals
③1P/2W Leakage Current : Connect each “R”&“S”
phase CT to the
respective terminals
‐3‐

④1P/3W Leakage Current : Connect each “R”, “S”&”T” phase CT to the respective
terminals
⑤3P/4W Leakage Current : Connect each “R”, “S”, ”T”&”N” phase CT to the
respectiveterminals
MCL-4000FCT
4. OPERATION PROCEDURE
4-1 Measurement of Line Current
①Set power switch "ON".
②Connect "R" phase CT to “N” terminal.
③Set LINE/LEAK switch to “LINE”.
④Clamp CT to one of conductors to be
measured.
Red “R” phase CT
4-2 Measurement of Leakage Current (Grounding Line)
①Set power switch "ON".
②Connect "R" phase CT to “N” terminal.
③Set LINE/LEAK switch to “LEAK”.
④Clamp CT to the grounding line and measure leakage current.
⑤If necessary, change the measuring range by range switch.
⑥Where the circuit contains many high-frequency waves, use filter switch.
△ CAUTION
It may cause damage to the instrument.
●In case of applying the excessive current to CT at the time of line current
measurement, it may cause damage to the instrument by heating. Do not apply
more than AC 800A to CT.
‐4‐

4-3 Measurement of Leakage Current (3P/3W)
①Connect each "R" phase, “S” phase &
“T” phase CT to the respective terminals.
②Set LINE/LEAK switch to “LINE”.
③Set power switch "ON".
④Clamp CTs to one of conductors
respectively (make “K” side of CT
toward power supply side).
⑤Set LINE/LEAK switch to “LEAK” to
measure the leakage current.
⑥Where the circuit contains many
high-frequency waves, use filter switch.
In case of the field where the measured
value hardly can be seen, use data hold switch.
⑦After finished the measurement, set LINE/LEAK
switch to “LINE” and remove CTs from the conductors.
4-4 Measurement of Leakage Current (1P/2W)
①Connect "R" phase CT and “S” phase
CT to the respective terminals.
②Set LINE/LEAK switch to “LINE”.
③Set power switch "ON" and clamp
CTs to the conductors (“R” phase
CT to L1 and “S” phase CT to N).
④Measure the leakage current in
the same manner as ⑤~⑦ of
3P/3W.
‐5‐

4-5 Measurement of Leakage Current (1P/3W)
①Connect "R" phase, “S” phase &
“T” phase CT to the respective
terminals.
②Set LINE/LEAK switch to “LINE”.
③Set power switch "ON" and clamp
CTs to the conductors (“R” phase
CT to L1, “S” phase CT to N, “T”
phase CT to L2) and make “K”
side of each CT toward power
supply side.
④Measure the leakage current in
the same manner as ⑤~⑦ of
3P/3W.
4-6 Measurement of Leakage Current (3P/4W)
①Connect each "R" phase, “S” phase,
“T” phase & “N” phase CT to the
respective terminals.
②Set LINE/LEAK switch to “LINE”.
③Set power switch "ON" and clamp
CTs to the conductors (“R” phase
CT to “R” Line, “S” phase CT to “S”
Line, “T” phase CT to “T” Line, “N
phase CT to “N” Line) and make “K”
side of each CT toward power supply
side .
④Measure the leakage current in
the same manner as ⑤~⑦ of
3P/3W. RECORDER Analog DC
Output
△CAUTION
1. In case that the phase balance is wrong in 1P/3W, there may be an error in the
measurement.
2. Be sure to set LINE/LEAK switch to LINE whenever clamping or removing CTs.
In case of clamping or removing CTs leaving LINE/LEAK switch to LEAK at the
measurement of 2CT~4CT method, it may cause the internal resister burning.
‐6‐

4-7 Signal Output for Recorder
This instrument has the signal output function for recorder which enables the long
period measurement. As to the recorder, use one with the input impedance more than
1MΩ.
4-8 Change of Batteries
●Confirm the power switch is “OFF”
and remove the screws by + driver
and take off the battery cover.
●Take out the exhausted batteries and
install new ones, not to mistake the
polarity.
the battery cover and tighten the screws.
※ When the batteries are exhausted and the voltage gets lower than operation, “B”
sign appears on LCD.
※ Replace the batteries to new ones immediately but do not mix the new and old
one and or different kinds.
△ WARNING
POSSIBLE ELECTRICAL SHOCK OR ACCIDENT
●Do not use the instrument absolutely, keeping the battery cover off.
△ CAUTION
●In case of not using the instrument for a long period, keep it without batteries
installed. It may cause liquid leakage of batteries and may cause the damage to
the instrument.
●Do not lose the screw for battery cover and not mistake to put them into the
instrument.
‐7‐

5.REPAIRSERVICE
When requesting for repair service, please bring the instrument directly to the dealer
where you bought.
When mailing the instrument, always pack it in its original or equivalent packing
materials to avoid any damage during the transportation and also put together with
documents showing your name, address, phone number and defect point.
6. WARRANTY
This instrument is sent out from our factory after the sufficient internal inspections
but if you find any defect due to the fault in our workmanship or the original parts,
please contact the dealer where you bought the instrument.
The warranty period is 12 months from the date of purchase and the instrument shall
be repaired at free of charge, provided that we judge the cause of defect is obviously
resulted from our responsibility.
GURANTEE REGULATIONS
1.This instrument is warranted for the operation under normal use for 12 months from
the date of purchase.
2.This warranty does not cover the following defects:
a. Defect caused from the improper use and operation.
b. Defect caused from the use, operation and storage beyond the original
specifications, designs and conditions.
c. Defect caused from the renovations or repairs done by someone else than us or our
representatives.
d. Defect not caused from our responsibilities.
‐8‐
Table of contents
Other MULTI MEASURING INSTRUMENTS CO.,LTD. Measuring Instrument manuals