Multitek PowerSig M560-AT User manual

PowerSig
MULTIFUNCTION
TRANSDUCER
M560-AT*
OPERATING MANUAL
M560AT~1.PM5 01/08/101, 12:511

CONTENTS
Update: M560 Version 4
1. INTRODUCTION
2. PROGRAMMING PARAMETERS
3. PROGRAMMING ANALOGUE OUTPUTS
4. PROGRAMMING MODBUS REGISTER
SEQUENCE.
5. RS485 COMMUNICATION
6. INSTALLATION
7. CONNECTION DIAGRAMS
8. SPECIFICATION
Revision 4
Date 20-10-2011
Multitek Ltd. Lancaster Way, Earls Colne Business Park,
Earls Colne, Colchester, Essex. CO6 2NS. England.
Tel. (01787) 223228 Fax. (01787) 223607
E-MAIL: [email protected]
WEB SITE: WWW.multitek-ltd.com
2

M560 Version 4 update:
RS485 response time decreased to better than 10ms.
Choice of four Endian settings for floating point transmission.
Modbus 3X Register Order functions changed to 65 and 66.
Relay functions changed to 103 and 104.
Substitute MultiView for all references to Monitor95 or System Monitor.
Manual Ammendments:
Page 45: Changed 3X Modbus registers to odd numbers.
Page 50: Changed 4X Modbus registers to odd numbers.
Additional 4X registers:
40083 (0x0052) RESET Import kW.h Register (WO)
40085 (0x0054) RESET Export kW.h Register (WO)
40087 (0x0056) RESET Import kVAr.h Register (WO)
40089 (0x0058) RESET Export kVAr.h Register (WO)
40091 (0x005A) RESET kVA.h Register (WO)
40093 (0x005C) RESET Import A.h Register (WO)
For more information go to: www.multitek-ltd.com

M560 V4 Modbus 4X registers
Modbus Register Name Mode
40001 (0x0000) SYSTEM VOLTAGE (R/W)
40003 (0x0002) SYSTEM CURRENT (R/W)
40005 (0x0004) SYSTEM TYPE (RO)
40007 (0x0006) SYSTEM POWER (RO)
40009 (0x0008) DEMAND PERIOD (R/W)
40011 (0x000A) DEMAND STATUS (RO)
40013 (0x000C) Factoryuse (ILLEGAL)
40015 (0x000E) Factoryuse (ILLEGAL)
40017 (0x0010) RESET ALL ENERGY REGISTERS (WO)
40019 (0x0012) RESET DEMANDS (WO)
40021 (0x0014) CALIBRATE INPUT (WO)
40023 (0x0016) SET NODE ADDRESS (WO)
40025 (0x0018) Analogue o/p1 assignment (M560) (R/W)
40027 (0x001A) Analogue o/p1 nominal (M560) (R/W)
40029 (0x001C) Analogue o/p1 zero (M560) (R/W)
40031 (0x001E) Analogue o/p2 assignment (M560) (R/W)
40033 (0x0020) Analogue o/p2 nominal (M560) (R/W)
40035 (0x0022) Analogue o/p2 zero (M560) (R/W)
40037 (0x0024) Analogue o/p3 assignment (M560) (R/W)
40039 (0x0026) Analogue o/p3 nominal (M560) (R/W)
40041 (0x0028) Analogue o/p3 zero (M560) (R/W)
40043 (0x002A) RELAY ASSIGNMENT (R/W)
40045 (0x002C) RELAY DIVISOR (R/W)
40047 (0x002E) RELAY PULSE WIDTH (R/W)
40049 (0x0030) RESET FLASH/EEPROM DATA (WO)
40051 (0x0032) I/P V1 GAIN FACTOR (R/W)
40053 (0x0034) I/P V2 GAIN FACTOR (R/W)
40055 (0x0036) I/P V3 GAIN FACTOR (R/W)
40057 (0x0038) I/P I1 GAIN FACTOR (R/W)
40059 (0x003A) I/P I2 GAIN FACTOR (R/W)
40061 (0x003C) I/P I3 GAIN FACTOR (R/W)
40063 (0x003E) Factoryuse (ILLEGAL)
40065 (0x0040) Factoryuse (ILLEGAL)
40067 (0x0042) Factoryuse (ILLEGAL)
40069 (0x0044) Factoryuse (ILLEGAL)
40071 (0x0046) SET PASSCODE (WO)
40073 (0x0048) CALIBRATION PASSCODE (WO)
40075 (0x004A) DtoA PASSCODE(M560) (WO)
40077 (0x004C) DtoA1 OVERRIDE(M560) (WO)
40079 (0x004E) DtoA2 OVERRIDE(M560) (WO)
40081 (0x0050) DtoA3 OVERRIDE(M560) (WO)
40083 (0x0052) RESET Import kW.h Register (WO)
40085 (0x0054) RESET Export kW.h Register (WO)
40087 (0x0056) RESET Import kVAr.h Register (WO)
40089 (0x0058) RESET Export kVAr.h Register (WO)
40091 (0x005A) RESET kVA.h Register (WO)
40093 (0x005C) RESET Import A.h Register (WO)
40095 (0x005E) Future use (R/W)
40097 (0x0060) Future use (R/W)
40099 (0x0062) Future use (R/W)
40101 (0x0064) LOCK ACIA SETTINGS (WO)

3
1.1General
PowerSig M560 multifunction transducer is a complete
measuringsysteminasingle100mmDin rail mount case.
Measuring Phase Volts, Phase Current, Frequency, Active
Power, Reactive Power, Energy and Demand. The M560
provides up to 3 analogue outputs and the options of
RS485modbus outputand pulsed output.
PowerSystems :- Product code
1Ph. M560-AT1
1Ph.3Wire M560-AT1-3
3Ph. 3Wunbalanced load M560-AT4
3Ph. 4Wunbalanced load M560-AT9
Phase Voltage (V), Phase Current (I), Frequency (Hz),
Active Power per phase (W), System Active Power (W),
Reactive Power per phase (VAr), System Reactive Power
(VAr), Apparent Power per phase (VA), System Apparent
Power (VA), Import Active Energy (W.h), Export Active
Energy (W.h), Import Reactive Energy (VAr.h),
The M560 units are fully programmed by the factory and
no further programming is necessary. If the RS485 option is
ordered, the user can reprogram parameters to individual
requirements, such as the voltage and current ratios, relay
output,demandtimes aswellasassigndifferentparam-
eters to the outputs. These programming operations are
coveredinthismanual.
The M560 uses a high speed microprocessor and analogue
to digital conversion circuitry. Each phase current and
voltage is measured continuously and all other parameters
are derived from these measurements in the software.
Voltageand current measurementsare true RMS.
1.2ParametersMeasured
The M560 Measures the following parameters :
M560AT~1.PM5 01/08/101, 12:513

Export Reactive Energy (VAr.h), Power Factor per phase
(P.F.), System Power Factor (P.F.), Amp Demand, Watt
Demand, V A Demand, Maximum Amp Demand,
Maximum Watt Demand, Maximum VA Demand.
1.2 Memory
All data including energy registers, current and voltage
ratios and the calibration data is stored in a non volatile
e2prom. In power down (power loss) conditions all the
information is retained. The e2prom requires no battery or
other circuitry to maintain the stored data.
1.3RelayOutput(optional)
The relay output provides a pulsed output corresponding to
consumption Watt hour import or export, VAr hour import
or export, A.h or VA.h consumption. The relay can be
assigned to any of these parameters (see programming
section2.15.1).
The M560 automatically calculates the pulse rate and
whether the units are W.h, kW.h or MW.h (VAr.h, kVAr.h
or MVAr.h) etc from the nominal voltage and current
inputs.
The relay is a normally open contact.
Pulse widths can be programmed into the M560, between
20 msec and 200 msec in steps of 20 msec. (See section
2.15.2).
4
M560AT~1.PM5 01/08/101, 12:514

1.4Communications(optional)
The M560 has the option of providing RS485 output of all
measuredparameters.
The serial port option enables remote reading and
programming of the M560 via a host computer, laptop etc.
The RS485 uses the Modbus protocol allowing multi-drop
with up to 32 M560s connected in parallel. The RS485
Modbus protocol allows the M560 to be used with PC,
PLC, RTU, Data loggers and Scada programs.
Softwareisavailableforprogramminganddisplaying
parameters. Contact your local distributor for a free copy
or visit our website www.multitek-ltd.com
1.5LEDindicator
The red LED on the front of the M560 serves three
purposes:
LED continually illuminated means that the power supply
is o.k.
LEDilluminated and flashing every10 seconds means that
the power supply o.k. and the M560 is communicating
correctly.
LEDilluminated andflashing everysecond and2 flashes
every 10 seconds means that the power supply o.k. and
that unit is communicating correctly, but there is no input
measuringvoltagesignal.
5
M560AT~1.PM5 01/08/101, 12:515

6
2.0PROGRAMMING
If the unit has not been provided with a communication
option this section is not relevant, please move to section 6
installation.
2.1 Using the M560 Software Monitor 95.
(M560 Software Monitor 95 can be obtained from your
Multitek distributor, or the Multitek website
www.Multitek-Ltd.com)
2.2 Open the Monitor95.exe file and the following screen
will be displayed.
The following functions displayed relate to the PC or
master node and are set by default to the following
settings, Response time = 300mS, Node = 1, Baud Rate =
9600, Parity = None. It may not be necessary to alter the
above settings but the communication port has to be
opened by clicking on start and following section 2.5.
M560AT~1.PM5 01/08/101, 12:516

ACTION : Click Response
Time Box.
COMMENTS:
Enter Value of response
time. Minimum value
300mSec.
2.4ChangingNodeNumber
ACTION:ClickNodeNo.
Box.
COMMENTS:
Enter Node Number any
number between 1 & 247.
2.5 Opening communication port.
ACTION:Click Start
Button.
COMMENTS:
Port selection box appears,
see below.
2.3 Changing Response Time
ACTION : Click Port Box.
COMMENTS:
Chose the PC's
communication port click
on Com 1 or Com 2
7
M560AT~1.PM5 01/08/101, 12:517

2.6ChangingBaud Rate.
ACTION:ClickBaudRate
Box.
COMMENTS:
Chose Baud Rate. Either
2400,4800,9600,19200.
2.7ChangingParity.
ACTION : Click Parity Box.
COMMENTS:
Choose Parity. Three
options Odd, Even or None.
2.8StartingCommunication
ACTION:OnceComms
Port, Baud Rate and parity
are set, Click on O.K.
COMMENTS:If
Communicationisworking
messagemodbusOK
appears in Modbus box.
COMMENTS:
M560andPC
communicating correctly.
COMMENTS:
M560andPCnot
communicating correctly.
8
M560AT~1.PM5 01/08/101, 12:518

NoteifwordinginModbusboxis"NOREPLYFROM
NODE". Check polarity connection of RS485 link at M560
and PC. Check that M560 has auxiliary power by checking
Red LED on front of M560. If LED continually
illuminatedpowersupplyo.k.IfLEDilluminatedand
flashing every 10 seconds, power supply ok M560
communicating ok. If LED flashing every second there is no
measuringinput voltagesignal.
9
2.9Displaying parametersbeing measured.
Once M560 is communicating with your PC you can now
monitordifferentreadings.
ACTION:None
COMMENTS:The6boxes
show line to line voltage and
line to neutral voltage for
each phase. Note if unit is 3
phase3wireM560-CT4
V1,V2,V3 are the same as
VL1-2,VL2-L3,VL3-1.
ACTION:Clickon
button.
COMMENTS: Thenext six
parameters being monitored
are displayed. e.g I1,I2,I3,
WSum,VASum,VARSum.
M560AT~1.PM5 01/08/101, 12:519

10
ACTION:Clickon
button.
COMMENTS:This button
moves forward one
parameter, anddisplaysthis
parameter in the sixth box
e.g. PF Avg is now shown.
ACTION:Clickon
button.
COMMENTS:This button
moves back one parameter.
e.g.nowI1isshownagain.
Note: The buttons work as follows:
This button scrolls up one parameter.
This button scrolls up six parameters.
This button scrolls down one parameter.
This button scrolls down six parameters.
M560AT~1.PM5 01/08/101, 12:5110

11
2.10Stopping andpausing communication.
2.10.1Topausecommunication.
ACTION: Clickon Pause
button.
COMMENTS:The
communicationpauses.
ACTION: Clickon Continue
button.
COMMENTS:The
communicationrestarts.
2.10.2 To restart communication.
2.10.3 To stop communication.
ACTION:ClickonStop
button.
COMMENTS:The
communication stops.
ACTION:Click Start
button.
COMMENTS:Follow
instructions in section 2.8
i.e. click on O.K. button in
port set up box and
communication will start.
M560AT~1.PM5 01/08/101, 12:5111

12
2.11Startingtimer.
The timer is real time clock provided by the Monitor
program. It is useful for checking Watt hour readings etc.
ACTION : Click Stop
button.
COMMENTS:Thetimer
stops and gives option of
resettingorcontinuing.
ACTION : Click Reset
button.
COMMENTS:Thetimer
resets to zero.
ACTION: Click Continue
button.
COMMENTS:Thetimer
continues to count,
displaying the total time
fromwhencounterinitially
started.
ACTION:Click Start
button.
COMMENTS:Thetimer
starts.
M560AT~1.PM5 01/08/101, 12:5212

13
2.12.1EnteringGeneralPassCode
ACTION:Click General
Pass Code Button
COMMENTS:
Enter value box is
displayed.
2.12 Security code. (General Pass Code)
To program different CT & VT ratios, demand times, etc.
theGeneralPassCodemustbeentered.TheGeneralPass
Code is 080453. This is general pass code and is only
applicable to Multitek M560 software. Pass Codes
necessary for use with other software are listed in Section 4
page45ofthismanual.
ACTION:Enter value
COMMENTS:Enter
security code 080453 and
click on OK button
M560AT~1.PM5 01/08/101, 12:5213

14
2.13.2 To Unlock M560 communications settings.
ACTION:Click Unlock
Button.
COMMENTS:
M560 communication port is
nowunlocked.
ACTION : Click Lock
Button.
COMMENTS:
M560 communication port
will be locked onto existing
networksettings.
2.13.1 To Lock communications setting into the M560
EEPROM.
ResponseTime,NodeNumber,CommunicationPort,Baud
Rate and Parity are dependant on the system and PC etc.
that is being used. When connected to an existing Modbus
network the M560 will automatically detect and configure
itself to the network's settings. These settings can be locked
into the EEPROM of the M560 to prevent unnecessary
hunting. For a more detailed explanation of this facility see
help file in the Monitor95 Software.
2.13CommunicationsLock.
M560AT~1.PM5 01/08/101, 12:5214

2.14Programming of nominalvoltageand current inputs
andratios.
The program allows the user to program the nominal
voltage and current inputs and ratios. Please note the ratios
can be changed as long as the secondary (the input to the
M560) stays as shown on the data label which is on the side
of the product. For example if the M560 had been set by the
factory to have a C.T. ratio 200/5A and the change required
was for the input C.T. ratio to be 500/5A this can be
achieved by program changes. But if the change required
was for a C.T. ratio 500/1A then the unit would have to be
returned to the factory or distributor to have the internal
C.T. changed from 5A to 1A. The same applies to the
voltage if the M560 input voltage is 110 Volts L.L then an
external voltage transformer ratio can be programmed as
long as the nominal input to the M560 stays at 110V L-L
2.14.1ChangingVT ratio.
ACTION:None
COMMENTS:M560 is
programmed for 6600V
(6.6kV)
ACTION : Click Voltage
Button.
COMMENTS:EnterValue
boxisdisplayed.
15
For example if the input was originally programmed for
6.6kV/110and a V.T. of 11kVwas required then this change
could be achieved through software. (See example below)
M560AT~1.PM5 01/08/101, 12:5215

ACTION : Enter value
COMMENTS:Enter
11000(11kV).Click on
O.K.
2.14.2ChangingCTratio.
For example to change for 200/5A change to 400/5 :-
ACTION:Click Current
Button.
COMMENTS:EnterValue
boxisdisplayed.
ACTION:None
COMMENTS:M560 is
programmedto200/5A
ACTION : Enter Value
COMMENTS:Enter400
(400 Amps). Click on OK
16
M560AT~1.PM5 01/08/101, 12:5216

17
2.15PulsedOutput(Pulsedoutputis an option.If theunit
does not have this option please proceed to section 2.16)
The M560 measures and displays W.h Import & Export,
VAr.h Import & Export, VA.h, A.h. Any of these parameters
can be assigned to the output relay to give pulses
corresponding to which ever parameter is selected.
2.15.1 Selecting Parameter to be assigned to relay for
pulsedoutput.
ACTION: ClickOn Relay
ModeButton.
COMMENTS : Relay Mode
boxisdisplayed.
ACTION:None
COMMENTS : Relay is
assignedW.hImport.(Watt
HourImport)
ACTION:Select Parameter
to be assigned to relay
output.
COMMENTS:Usingtheup
and down cursor you can
scroll through the
parametersavailable.Inthis
exampleA.h(AmpereHours
) has been selected, click on
OKButton.
M560AT~1.PM5 01/08/101, 12:5217

18
2.15.2 Selecting Relay output pulse width.
The pulse width can be set between 0msec (off) and
200msec, in steps of 20msec.
ACTION : Click On Pulse
WidthButton.
COMMENTS:PulseWidth
Selection box is displayed.
ACTION:Enter value
between 20msec and
200msec.
COMMENTS:Pulsewidths
are in steps of 20msec. If
60msec enter 60 and click on
OK.
2.15.3 Selecting Relay Divisor
This allows the user to set the relay to pulse every 1, 10 ,
100 or 1000 counts. i.e. If the divisor is set to 1 every time
M560 registers and stores 1 count relay the pulses once. If
set to 100, the relay only pulses once after M560 has
registered and stored 100 counts. The M560 always
registers and stores the number of counts regardless of what
the relay divisor is set to. i.e. If the kilowatt consumption
was 500 kW per hour and relay divisor was set to 100 you
wouldget5pulsesanhour.
ACTION: ClickOn Relay
Divisor Button.
COMMENTS : Divisor
selection box is displayed.
M560AT~1.PM5 01/08/101, 12:5218
Table of contents