Myson MPE 222 User manual

MYSON POWER EXTRA
SPRING RETURN ZONE VALVE
MPE 222 / MPE 2 3/4 “- 2 PORT 22mm VALVE
Thank you for choosing a MYSON heating control.
The MPE 222 is designed to control water circulation in primary hot water
or central heating circuits. The motor is powered to open the valve with a
spring return to the closed position.
The valve is not directionally sensitive and may be fitted with flow through
either Port A or Port B.
For convenience the neon indicator light illuminates, indicating when the
valve is open.
When the manual lever is moved to the right, the valve is open. This is used
when filling, venting or draining the system. The spring return valve rests
in the closed position.
TECHNICAL SPECIFICATION
Motor Supply Voltage 230 V AC
Frequency 50 Hz
Power Consumption 6 W
Motor Insulation Rating Class ‘F’
Maximum Working Pressure 10 Bar
Maximum Water Temperature 95o C
Maximum Ambient Temperature 52oC
KV value 6.7
Switch Rating 3(0.5) A
High Temperature Silicon Cable 1100mm
Valve Body Brass with spring loaded
Mica filled PTFE shoes
Actuator Power to Open
SpringtoClose
MPEDOC002 Issue: 9
INSTALLATION INSTRUCTIONS
Step 1. Select Valve Position:
Choose a suitable position for the valve in
the circuit to be controlled, which allows
sufficient access for wiring and
maintenance.
The position chosen must not isolate the
boiler from the open vent or the cold feed
pipe work.
The valve may be fitted in a horizontal,
vertical or inclined orientation and may be
fitted on either the flow or return circuit.
The actuator must not be fitted below the
valve body.
Step 2. Fit Valve Body to Pipe work:
BOILER
PUMP
RADIATORS
TANK
TWO PORT
VALVES
AUTO
BYPASS
VALVE
Fit the valve body using the 22mm
compression nuts provided. Ensure
that the valve body is only gripped
on the hexagonal faces at the valve
ports. Take care not to over
tighten.
Step 3. Fit Actuator to Valve Body:
Position the actuator on the valve body by
locating the spindle in the cam slot.
Rotate actuator until the locating lug (shown)
lines up with locating lug-hole on the mounting
plate (shown).
provided.
Fix the actuator to the body by lightly
tightening the screws
Set the override lever to MAN. Fill, test and
thoroughly flush the system.
Locating Manual
Step 4. Electrical Connections:
The actuator is fitted with 1100mm of 4-core cable for connection of the system
equipment. The installation will be simplified by the use of an electrical junction
box into which all the system equipment can connect.
The actual wiring connections will depend on the system equipment used,
following the wiring principle outlined below. The MPE 222 is double insulated
and requires no earth connection.
ation
f at least 3mm.
lly open any equipment connected
ng return to the closed
and auxiliary equipment should cease to operate.
tes:
a. with thermal insulation, or in
b. that the valve is kept within the specified ambient
The valve actuator is not designed for continuously powered operation.
IMPORTANT:
The wiring must
comply with
current I.E.E.
regulations. Ensure
mains supply to all
controls is fused at
no more than 3A.
Mains isolating
switch must have
contact separ AUX. SWITCH
3A. 230V
ORANGE
GREY
BROWN
BLUE
STAT.
NLOFF
ON
System Controls To Be FUSED 3A MAX
COM
N/C
N/O
MOTOR
MICRO-
SWITCH
BA 22MM
o
Step 5. Commissioning:
When the installation is complete, filled and vented, check that the valve operates
correctly. Switch on the system controls, i.e. programmer and thermostats: The
valve should move to the open position. When fu
to the valve’s auxiliary switch should operate.
Switch off the heating controls: The valve should spri
position
No Ensure that the actuator is not covered
contact with pipe work or other materials.
When the valve is fitted in confined space, ample ventilation must be
provided to ensure
temperature range.
c.
MPE 222 Spares Part No.
ctuator with 421101
rews
m 2 Port 421102
ve body.
HANGE WIRING GUIDE
2-PORT ZONE 22mm
Description
A
Fixing sc
22m
Val
PRODUCT INTERC
A
22MM
B
Honeywell V4043H
Danfoss DMV2C
Tower MV2
ACL 6799H308
Landis & Gyr ZA-V222
Grey
Orange
Brown
Blue
Green/Yellow
Permanent Live
Switched Live
Motor Open
Neutral
Earth
Brown
Orange
Blue
Grey
Landis & Gyr SK2
Randall HP2
Potterton PMV2
Sunvic SZ1326
Motor Open
Switched Live
Permanent Live
Earth
Neutral
Orange
Blue
Grey
Brown
Grey
Blue
Brown
Orange
AB 22MM
ACL 679H308
AB 22MM
Grey
Red
Yellow
Blue Neutral
Permanent Live
Motor Open
Switched Live
Blue 22MM
BA
Orange
Brown
Grey
White
Green/Yellow
Switchmaster 1183
N/A
N/A
MYSON CONTROLS, MYSON LTD., EASTERN AVENUE, TEAM VALLEY,
GATESHEAD, TYNE & WEAR, NE11 OPG
SALES OFFICE No.: 0845-402-3434
IN ACCORDANCE WITH OUR POLICY OF CONTINUAL PRODUCT IMPROVEMENT, WE RESERVE THE RIGHT TO AMEND THE SPECIFICATION OF
THESE PRODUCTS WITHOUT PRIOR NOTIFICATION

This manual suits for next models

1

Other Myson Heating System manuals

Myson WHISPA III 5000 User manual

Myson

Myson WHISPA III 5000 User manual

Myson FLOORTEC User manual

Myson

Myson FLOORTEC User manual

Myson 7-4 User manual

Myson

Myson 7-4 User manual

Myson MPE 322 User manual

Myson

Myson MPE 322 User manual

Myson UFH User manual

Myson

Myson UFH User manual

Myson KICKSPACE 500 DUO Installation instructions

Myson

Myson KICKSPACE 500 DUO Installation instructions

Myson Kickspace 500 User manual

Myson

Myson Kickspace 500 User manual

Myson 25-18 Instruction Manual

Myson

Myson 25-18 Instruction Manual

Myson FLOORTEC User manual

Myson

Myson FLOORTEC User manual

Myson WHISPA III 5000 User manual

Myson

Myson WHISPA III 5000 User manual

Myson FLOORTEC User manual

Myson

Myson FLOORTEC User manual

Myson 7-4 Instruction Manual

Myson

Myson 7-4 Instruction Manual

Myson SLIM-LINE RC Instruction Manual

Myson

Myson SLIM-LINE RC Instruction Manual

Popular Heating System manuals by other brands

flamco Duo Installation and operating instructions

flamco

flamco Duo Installation and operating instructions

Nibe UKV 20 Series User's and installer's manual

Nibe

Nibe UKV 20 Series User's and installer's manual

Amtrol SGH-S150G user manual

Amtrol

Amtrol SGH-S150G user manual

Chromalox POO400-7 installation instructions

Chromalox

Chromalox POO400-7 installation instructions

STIEBEL ELTRON SBP 700 E SOL Operating and installation instructions

STIEBEL ELTRON

STIEBEL ELTRON SBP 700 E SOL Operating and installation instructions

HDG Compact 25 operating manual

HDG

HDG Compact 25 operating manual

Agilent Technologies LTM II Series user guide

Agilent Technologies

Agilent Technologies LTM II Series user guide

JB INDUSTRIES F6-DP operating instructions

JB INDUSTRIES

JB INDUSTRIES F6-DP operating instructions

Magnum Heating W-CONTROL quick guide

Magnum Heating

Magnum Heating W-CONTROL quick guide

Conel CLEAR FILL operating instructions

Conel

Conel CLEAR FILL operating instructions

Novetec NGL-LJM-4 user manual

Novetec

Novetec NGL-LJM-4 user manual

Inta Hiper II V1 Installation and operating manual

Inta

Inta Hiper II V1 Installation and operating manual

Viessmann VITODENS operating instructions

Viessmann

Viessmann VITODENS operating instructions

Mitsubishi Electric Ecodan HUS210FTC4ST installation manual

Mitsubishi Electric

Mitsubishi Electric Ecodan HUS210FTC4ST installation manual

Thermo King Trailer Edition Heat King 450 Series installation manual

Thermo King

Thermo King Trailer Edition Heat King 450 Series installation manual

Airflow Uno hab Installation and operating instructions

Airflow

Airflow Uno hab Installation and operating instructions

Danfoss SET2E Installation & user's instructions

Danfoss

Danfoss SET2E Installation & user's instructions

ELEKTRA FreezeTec installation manual

ELEKTRA

ELEKTRA FreezeTec installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.