
General points for the installation engineer
Transport and storage
F2015 should be transported and stored vertically.
Inspection of the installation
Current regulations require the heating installation to be in-
spected before it is commissioned. The inspection must be
carried out by a suitably qualified person and should be
documented. The above applies to closed heating systems.
If the heat pump is replaced, the installation must be inspec-
ted again.
Assembly
F2015 is placed outdoors on a firm base, preferably a con-
crete foundation. F2015 should not be positioned next to
sensitive walls, for example, next to a bedroom. Also ensure
that the placement does not inconvenience the neighbours.
Care must be exercised so that the heat pump is not
scratched during installation.
Large amounts of condensation water as well as melt water
from defrosting can be produced. Provide good drainage at
the installation area and make sure water cannot run out
onto paths or the like during periods that ice can form. Ideally
condensation water is led off to a drain or similar. It is also
possible to install the accessory KVT 10, which is a collecting
trough for leading off condensation.
The distance between F2015 and the house wall must be at
least 350 mm. Clearance in front of F2015 should be at least
one metre. F2015 must not be placed so that recircula-
tion of outdoor air can occur. This causes lower output
and impaired efficiency.
Control
F2015 is equipped with an internal electronic controller that
handles all functions necessary for heat pump operations.
Accordingly, defrosting, stop at max/min temperature, con-
nection of the compressor heater as well as enabling the
heater for the drip pan, monitoring of motor protection and
pressure switches are controlled.
The number of starts and the operating time can also be
read.
The integrated controller is set during installation and can
be used during a service.
Under normal operation conditions the home owner does
not need to have access to the controller.
F2015 has an integrated electronic return line sensor that
limits the return temperature.
F2015 can also be switched on/off via signals from other
control equipment or a thermostat. If F2015 is controlled
from the accessory SMO 10 the control is described in the
instructions supplied.
SMO 10 communicates with F2015 which means that set-
tings and measurement values from F2015 can be adjusted
and read off in SMO 10 .
350 mm
400 mm
3 m
Fritt utrymme bakom
Fritt utrymme framför
Fritt utrymme
Min. avstånd
vid användning
av flera F 2025
)UHH VSDFH
)UHH VSDFH EHKLQG
)UHH VSDFH LQ IURQW
0LQ GLVWDQFH ZKHQ XVLQJ VHYHUDO )
5F2015
For the Installer
General points for the installation engineer