Parameter: 23. The response after exceeding dened power values
Description: This parameter denes the way that 3rd association group devices are controlled. Depends on the actual mea-
sured power (as parameters 21 and 22 settings).
Available settings: 1 - turn the associated devices ON, once the power drops below DOWN value (parameter 21)
2 - turn the associated devices OFF, once the power drops below DOWN value (parameter 21)
3 - turn the associated devices ON, once the power rises above UP value (parameter 22)
4 - turn the associated devices OFF, once the power rises above UP value (parameter 22)
5 - combination of 1 and 4.
Turn the associated devices ON, once the power drops below DOWN value (parameter 21).
Turn the associated devices OFF, once the power rises above UP value (parameter 22).
6 - combination of 2 and 3.
Turn the associated devices OFF, once the power drops below DOWN value (parameter 21).
Turn the associated devices ON, once the power rises above UP value (parameter 22).
Default setting: 6 Parameter size: 1 [byte]
Parameter: 24. SWITCH ON value - „On/Off” association groups
Description: The value of BASIC SET command frame sent to the devices associated in „On/Off” association groups (2, 3).
„On/Off (Button)” association group - in accordance with parameter 20.
„On/Off (Power)” association group - in accordance with parameter 23.
Available settings: 0-99 or 255
Default setting: 255 Parameter size: 2 [bytes]
Parameter: 30. Active alarms
Description: Dene Z-Wave network alarms to which Plug-Control will respond.
Available settings: 1 - general alarm
2 - smoke alarm
4 - CO alarm
8 - CO2 alarm
16 - high temperature alarm
32 - ood alarm
Default setting: 63 (all) Parameter size: 1 [byte]
Parameter: 31. Response to alarm frames
Description: This parameter denes how Plug-Control will respond to alarms (device’s status change).
In case of values 1 or 2 Plug-Control is operating normally and LED ring signals an alarm through time dened in
parameter 32 or until the alarm is cancelled.
In case of values 5 to 50 Plug-Control does not report status change, power changes, ignores BASIC SET com-
mand frames. After time dened in parameter 32 or after the alarm cancellation, connected device is set to the
previous state.
Available settings: 0 - no reaction,
1 - turn connected device on
2 - turn connected device off
5-50 (0.5-5.0s, step 0.1s) - cyclically change device state with set period
Default setting: 0 Parameter size: 1 [byte]
Parameter: 32. Alarm state duration
Description: This parameter species the duration of alarm state. If a device sending an alarm frame through the Z-Wave net-
work sets alarm duration as well, this settings are ignored.
Available settings: 1-32400 (in seconds)
Default setting: 600 (10min) Parameter size: 2 [bytes]
Parameter: 40. Power load for violet colour
Description: This parameter determines maximum active power value, which when exceeded, causes the LED ring ash violet.
Function is active only when parameter 41 is set to 1 or 2.
Available settings: 1000-30000 (100.0-3000.0W, step 0.1W)
Default setting: 25000 (2500W) Parameter size: 2 [bytes]