Nico Technology Ltd.
24F,No.37,SanMin Rd, 2.Sec, PanChiao City, Taipei County, Taiwan
Phone +886-2-2954-5338
Fax +886-2-2954-5308
Technical Support Tom_Yeh@nico-tech.com
Web site http://www.nico-tech.com

1201L-1K RTD Controller User’s Manual
2 Rev.1.1
This Manual
This manual provides any required information for installation, configuration
and operation of the Nico Technology Ltd.1201L-1K RTD Controller.
It exclusively treats the handling of this device. It neither describes the
LonWorks technology by Echelon nor the LonMark profile implemented in
detail. More specific information concerning these subjects can be found in the
documentation of Echelon (www.echelon.com) and the LonMark
Interoperability Association (www.lonmark.org).
The first part of this manual provides a survey about the device and its
installation in chapters 1 to 3. The 2nd part describes the implemented
application for lighting control and its configuration possibilities. Chapter 4
contains a description of the firmware interface while chapter 5 describes the
implemented LonMark Objects in detail providing an outlook of the individual
objects, their tasks and their relevant configuration parameters.
Chapter 6 explains the basics required to connect the objects to each other.
This manual is relevant for all variants of the Nico Technology Ltd.1201L-1K
RTD Controller where applications for building automation control are
implemented.
This documentation is subject to modification at any time without prior advice. Nico does not take over any
responsibility for mistakes or inaccuracies in this documentation and eventually occurring consequences.
In any case Nico as well as its representatives and staff are not reliable for eventual defaults, damages caused
indirectly or during use, occurring due to the use or non-usability of the software or the accompanying documentation.
Nico is a registered trademark of Nico Technology Ltd.
Echelon, LON, LonMark, LonWorks and Neuron are registered trademarks of Echelon Corporation. Other name may
be registered trade marks of the respective companies.

1201L-1K RTD Controller User’s Manual
3 Rev.1.1
Contents
Contents .........................................................................................................................3
2 Product Information...............................................................................................4
2.1 Functional Elements...................................................................................4
3 Installation..............................................................................................................5
3.1 Warnings ....................................................................................................5
3.2 Mounting....................................................................................................6
3.3 Connections................................................................................................6
3.4 Software Installation..................................................................................7
4 Device Description.................................................................................................8
4.1 Hardware Survey .......................................................................................8
4.2 Operation and Display Elements ...............................................................8
4.3 Connection Pin Assignment.......................................................................8
4.4 Wiring Diagram .......................................................................................11
4.5 EMC.........................................................................................................12
4.6 Technical Specifications ..........................................................................13
4.7 Dimensions ..............................................................................................14
5 Application Software for Building Automation Control .....................................15
5.1 System Scope...........................................................................................15
5.2 Interoperable Interface.............................................................................15
6 System Objects.....................................................................................................16
6.1 Node Object.............................................................................................16
6.2 Temp Sensor (OLS) Object......................................................................17

1201L-1K RTD Controller User’s Manual
4 Rev.1.1
2 Product Information
2.1 Functional Elements
Figure 1.1 1201L-1K RTD Controller
No Description
1 Power Indicator
2 Service Pin LED indicator
3 Transmission LED indicator
4 Receive LED indicator
5 Reset button
6 Service Pin button
7 Pt1000 Sensor Probe
8 12~24VDC Input Power
9 LonWorks FTT-10 Channel

1201L-1K RTD Controller User’s Manual
5 Rev.1.1
3 Installation
This chapter first describes the installation of the device; the installation of the
configuration software is described in section 3.4.
3.1 Warnings
Attention
The device must be installed in compliance with the relevant DIN/VDE
regulations or the relevant national standards. The connection to the
supply voltage must be performed in accordance with VDE 0100 and VDE
0160 or the relevant national standard Installation should perform by
qualified and technical experienced personnel only.
CAUTION
At the connections of the input channel (Fig. 1.1, terminal 7) and the power
supply (terminals 8) 12~24VDC main voltage with load guard band is
accessible. The installation of the unit therefore has to be effected in a
switch cabinet or behind a respective cover.

1201L-1K RTD Controller User’s Manual
6 Rev.1.1
3.2 Mounting
3.3 Connections
The1201L-1K RTD Controller has to be connected to a 12~ 24VDC power
supply and to the LonWorks network.According to the respective
application peripheral equipment has to be connected to outputs.

1201L-1K RTD Controller User’s Manual
7 Rev.1.1
Attention
Before connecting peripheral equipment the power supply device has to be
switched off.
The connection is effected by means of the included plug-screw terminals.
Clamping range of the plug-screw terminals:
- DC power and network connections (terminals 8): 2.5 mm
The pin assignment of the connections is described in chapter 3.1, also
containing wiring details.
Voltage
The 12~24 Volt Direct Current connections are through connected in order to
achieve easy wiring.
LonWorks Network
The connection to the LonWorks network is made by means of twisted-pair
cables. The connection “shield” has to be connected to ground in order to
achieve a reliable dissipation of over-voltage on the LON circuits.
Analog Inputs
The actors to be controlled are connected to the RTD Pt1000 inputs. In each
case the connection is effected terminal 1).
Attention
The 1201L-1K RTD Controller input power supply must within 12~ 24VDC
power supply only.
3.4 Software Installation
The configuration software of the 1201L-1K RTD Controller has to be
installed by starting the program Setup.exe on the data carrier provided. It
suns under Windows 9x/2000 and NT.
Download url: http://www.nico-tech.com/download

1201L-1K RTD Controller User’s Manual
8 Rev.1.1
4 Device Description
The 1201L-1K RTD Controller for LonWorks network in building automation. Its
peripheral scope has been specially designed for the use as temperature or
humidity sensor device spreading control of applications such as valve control
or lighting control thru Lux sensor.
For the use in building automation control the1201L-1K RTD Controller
realizes 1 independent input channel.
The LonMark object available per channel flexible use of the 1201L-1K RTD
Controller; The configuration of the building automation application is effected
via any LonWorks network management tool.
Of course, the1201L-1K RTD Controller is also freeing programmable in
Neuron C. As a flash module is used the application can be load via the
LonWorks network, making the 1201L-1K RTD Controller, e.g. for detail info
4.1 Hardware Survey
The1201L-1K RTD Controller disposes of eight output circuit for each. The
output circuit can be accept individually input RTD Pt1000 single.
4.2 Operation and Display Elements
The1201L-1K RTD Controller is fitted with a service button accessible via
a small gap on the front panel (see Figure. 1.1, 6).Activation of the buttons
generates a service-pin message transmitted via the LonWorks network.
The processor status as well as the service-pin status are displayed by the
service LED (figure. 1.1,2), which is on while the service button is activated.
By use the network management function Wink the service LED flashes.
Furthermore the1201L-1K RTD Controller is fitted with a reset LED (figure.
1.1, 1) same as Power indicator, displaying the availability of device occur
reset. The LED is connection to an I/O pin of the Neuron chip processor.
4.3 Connection Pin Assignment
The following tables show the connector pin assignment of the individual
connectors. Connections the 1marking cf. Figure. 1.1 On previously page.
In each clamp block pin 1 is situated on the left. For further wiring

1201L-1K RTD Controller User’s Manual
9 Rev.1.1
information see figure 3.2.
LonWorks Network Connection
The double-core bus line can be connection either to LON Aor to LON B.
No polarity has to be considered by connecting the LonWorks network.
Figure 3.1 Connector pin assignment LonWorks network

1201L-1K RTD Controller User’s Manual
10 Rev.1.1
Input circuit
Figure 3.2 Connector pin assignment input circuit.
Power Supply
The1201L-1K RTD Controller has to be connected via connector 2, 3, 5, 7
to 24VDC main voltage. Also see figure. 1.1.
Figure 3.3 Connector pin for Power Supply near LonWorks channels side

1201L-1K RTD Controller User’s Manual
11 Rev.1.1
4.4 Wiring Diagram
Figure 3.5 Connecting to 1208L
Figure 3.6 Connecting to other one of 1201L-1K or LonWorks device

1201L-1K RTD Controller User’s Manual
12 Rev.1.1
4.5 EMC
The 1208LAnalog Input Module is a CE certified device according to the
regulation 89/336/EEC for electron magnetic compatibility, modified by
92/31/EEC”. Concerning the emission it fulfills classification B (living area)
according to EN 55022A/B, EN 55011 A/B and EN 50081-1/2 and,
concerning the interference sensibility, classification A (industrial area)
according to EN 50082-2.

1201L-1K RTD Controller User’s Manual
13 Rev.1.1
4.6 Technical Specifications
Model 1201L-1K RTD Controller
CPU Echelon Neuron 3120,10MHz
Memory 4Kbytes flash EPROM,4Kbytes RAM, 12Kbytes ROM
LonWorks Transceiver FTT-10A/FT-X1
Power supply 12~ 24VDC (12VDC is recommend)
Power consumption 500mA(Per channel maximum)
38mA(Standby)
Connection Plug-screw clamp 2.5mm
Operation 0 ~ +70
Temperature Storage -25 ~ +85
Sensor Type Pt 1000resistance measuring
Sensor Connection 3-wire connection (factory preset) or 2-wire
Sensor Temperature range -220 °C ... +239 °C (PT)
Resolution 0.04°C
Measuring error ±1.5°C of full scale value
Conversion time 500ms (per channel)
Admitted relative humidity 5 ~ 93%, non condensing
Dimensions 90 x 71 x 57.7 mm,
DIN 43880, incl. clamps
Mounting DIN rail(EN 50022, 35 x 15)
Display & Operation Service-pin and Reset LED indicator and button
I/O Channels 1 RTD (resistive temperature device) input for Pt1000
Table 3.1 Technical Specification

1201L-1K RTD Controller User’s Manual
14 Rev.1.1
4.7 Dimensions
Figure 3.5 Device dimensions without plug-screw clamps

1201L-1K RTD Controller User’s Manual
15 Rev.1.1
5 Application Software for Building Automation Control
On the1201L-1K RTD Controller an application for building automation control
is implemented, making output functionality as well as analog control functions
available.
Therefore the relevant LonMark profiles stated in Table 4.1 are implemented.
The use of network variables (NV) compiles with the LonMark standard.
SCPT’s are used for parameterization by applying the read/write-memory
method.
Title Present
Version Identification
LonMark Application Layer Interoperability
Guidelines V3.1 078-0120-01D
The SNVT Master List and Programmer’s
Guide V 8.0
The SCPT Master List V 8.0
LonMark Functional Profile Open Loop Sensor
Object V 1.1 0001_11
Table 4.1 Referring document about LonMark profiles
5.1 System Scope
The1201L-1K RTD Controller is equipped with single channel for RTD
input.
The RTD input of the1201L-1K RTD Controller allows the connection of
Pt1000 type sensor. ASensor object, according to LonMark Standard can
be assigned to these output and configured.
.
The 1201L-1K RTD Controller is equipped with single resister input to
connect e.g. Temperature sensor, Humidity sensor, Lux sensor.
5.2 Interoperable Interface
The LonMark profile 0001_11 Open Loop Sensor is realized in
the1201L-1K RTD Controller. The network interface remains standardized,
clear and especially it is interoperable. That means, the1201L-1K RTD
Controller can be used in connection with network components by other
manufactures. The following table contains a survey of the network
variables defining the 1201L-1K RTD Controller. network interface and

1201L-1K RTD Controller User’s Manual
16 Rev.1.1
their assignment.
NV Name Type Allocated Object
nvo_temp SNVT_temp_p TempSensor (Close Loop Sensor)
Table 4.4 Allocation of NVs and LonMark objects
Under the order code 1201L-1K RTD Controller a data carrier containing
the interface describing file Nico_RTD-1201L-1K.XIF and the application
Nico_RTD-1201L-1K.APB is provided free of charge at simultaneous
purchase of a 1201L-1K RTD Controller. The XIF-file is necessary for
integration with LonMaker for Windows or any other LonWorks network
management tool.
6 System Objects
This chapter describes the LonMark objects implemented in the1201L-1K
RTD Controller. For each it states the network variable used, special
configuration properties, general object properties, response during
modification of the configuration and after a reset, and, if available, further
object properties.
6.1 Node Object
The functionality of the node object is defined in theApplication Layer
Guidelines of LonMark Interoperability Association (www.lonmark.org).
Network Variables
NV Name NV Type Comment
nviRequest SNVT_obj_request Status request
nvoStatus SNVT_obj_status Status response
nvoAlarm SNVT_alarm Alarm generating
nvoFileDirectory SNVT_address Address of file for parameterization

1201L-1K RTD Controller User’s Manual
17 Rev.1.1
6.2 Temp Sensor (OLS) Object
Network Variables
NV Name NV Type Comment
nvo_temp SNVT_temp_p Temperature value
Valid range:-50~70
Configuration Properties
CP Name Comment
SCPTmaxSendTime Send Heartbeat
SCPTminSendTime Send Throttle
SCPTnvType For specify the network variable maximum
length. (nvo_temp support changeable network
variable type to SNVT_temp_p or SNVT_temp_f)
[Note] this feature was reserved for future use.
SCPTsndDelta Generic send on Delta