2.Safety Instructions2.Safety Instructions
2.2 General Safety Instructions
!WARNING:
Solis-2.5K-2G is a transformerless inverter. Hence before its operation, it is very
important to ensure that the DC input source and the AC output source are
electrically isolated. Failure to do so will cause serious damage to the inverter.
( CAUTION: AC and DC voltage sources are terminated inside the inverter.
The AC circuit and the DC circuit must be isolated from each other before
servicing. Each circuit must be individually disconnected before servicing.)
!WARNING:
All electrical installations must be done in accordance with the local and
National Electrical Code AS/NZS3000.
!WARNING:
To reduce the risk of fire, branch circuit overcurrent protective devices are
required for circuits connected to Solis-2.5K-2G. The rating of overcurrent
device should not exceed 15 amperes.
CAUTION:
Risk of electric shock. Do not remove cover. There are no user serviceable
parts inside. Refer servicing to qualified and accredited service technician.
CAUTION:
The PV array (Solar panels) supplies a DC voltage when it is exposed to light.
CAUTION:
Risk of electric shock from energy stored in capacitors of Solis-2.5K-2G. Do not
remove cover until 5 minutes after disconnecting all sources of supply. Service
technician only. Warranty may be void if unauthorized removal of cover.
CAUTION:
Solis-2.5K-2G has a heat sink on its top surface, which helps in cooling down the
internal components. The heat sink can reach temperatures up to 70℃ (158 F).
To avoid risk of burns, do not touch the heat sink when the inverter is
operating. To install an inverter on a wooden, painted, or any other combustible
surface, a cement sheet is required to be used as a fire retardant material
between the wall and the inverter mounting.
Inverter must be installed OUT OF REACH OF CHILDREN.
2.3 Intended Use
The inverter has been constructed according to the applicable safety and technical
guidelines. Use the inverter in installations that meet the following sepcifications
ONLY:
1.Permanent installation is required.
2.The inverter must be connected to a separate, grounded AC group, to which no other
electrical equipment is connected.
3.The electrical installation must meet all the applicable regulations and standards.
4.The inverter must be installed according to the instructions stated in this manual.
5.The inverter must be installed according to the correct technical specifications.
.5. .6.
7.The DC input voltage into the Solis-2.5K-2G must NOT exceed 600Vdc.
6.To startup the inverter, the Grid Supply Main Switch (AC) must be switched on before
the solar panel DC isolator is switched on. To stop the inverter, the Grid Supply Main
Switch (AC) must be switched off before solar panel DC isolator is switched off.