9. Trouble Shooting9. Trouble Shooting
Alarm Message
OV-G-V01/02/03/04
OV-G-F01/02
UN-G-F01/02
G-IMP
NO-GRID
OV-DC01/02/03/04
OV-BU S
UN-BUS01/02
GRID-I N TF01/02
INI-FAULT
OV-TE M
Failure description
Over grid voltage
Under grid voltage
Over grid frequency
Under grid frequency
High grid impedance
No grid voltage
Over D C voltage
Over D C bus voltage
Under DC bus voltage
Grid interference
Initialization system fault
Over Temperature
Solution
1.Resistant of AC cable is too high.
Change bigger size grid cable
2.Adjust the protection limit if it’s
allowed by electrical company.
1.Check connections and grid switch.
2.Check the grid voltage inside inverter
terminal.
1.Reduce the module number in series
1.Restart inverter
2.Change power board
1.Check P V input connections
2.Check D C input voltage
(single phase >120V, three phase >350V)
3.Check if PV+/- is reversed
Inverter no power
on LCD
No power
LCD show initializing
all the time Can not start-up
1.Check if the connector on main
board or power board are fixed.
2.Check if the D SP connector to
power board are fixed.
1.Check inverter surrounding ventilation.
2.Check if there’s sunshine direct on
inverter in hot weather.
1.Use user define function to adjust the
protection limit if it’s allowed by
electrical company.
1.Check inverter inductor connection
2.Check driver connection
1.Restart inverter or contact installer.
UN-G-V01/02
DC-INT F D C input overcurrent
1.Restart inverter
2.Identify and remove the string to the fault MPPT
2.Change power board
IGFO L -F Grid current tracking fail
OV-G-I Over grid current
OV-DC A-I
IGBT-OV-I Over I G BT current
12Power-FA U LT 12V power supply fault
1.Restart inverter or contact installer.
IG-AD Grid current sampling fail
DSP-B-FAULT Comm. failure between main
and slave D SP
Table 9.1 Fault message and description
1.Remove all D C input, reconnect and
restart inverter one by one.
2.Identify which string cause the fault and
check the isolation of the string.
DCinj-FAULT High DC injection current
1.Check AC and DC connection
2.Check inverter inside cable connection.
1.Restart inverter or contact installer.
Alarm Message Failure description Solution
PV ISO-PRO
01/02 PV isolation protection
ILeak-PRO
01/02/03/04 Leakage current protection
RelayChk-FAIL Relay check fail
NOTE:
If the inverter displays any alarm message as listed in Table 9.1; please
turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5
minutes before restarting it (refer to Section 5.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Solis Three Phase Inverter;
2. The distributor/dealer of Solis Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings
, etc.);
6. Your contact details.
AFCI self-detection
(model with AFCI
module)
AFCI module self-detect fault 1.Restart inverter or connect technician.
Arcing protection
(model with AFCI
module)
Detect arc in DC circuit 1. Check inverter connection whether arc
exists and restart inverter.