Instruction Manual
EVA-ZMU-SCI Zone Module
Before Installation
Please read these instructions carefully and keep for future reference.
The information in this document is subject to change without notice.
For updates please refer to our website.
Note :Follow the requirements for the installation of the product in
accordance with the Specifications. Otherwise it may cause malfunction.
Note :Do not install the product in any location where oil, dust, iron
powder, chemicals, or hydrogen sulphide may occur or affect the product.
It may cause malfunction.
This package contains the following items:
Main unit ………………………………………………………………1
Outer cover EVA…………………………………………………………1
Instruction Manual ……………………………………………………1
Tapping screw …………………………………………………………2
Pan head screw …………………………………………………………2
EOL Resistor(RE-10k)………………………………………………………1
General Description
EVA-ZMU-SCI Zone Module with Short Circuit Isolator is intended for
use in addressable two wire systems, which can be connected with
2-wire conventional detectors. The module monitors and transmits the
status (normal, open, short, or alarm) of zone with the detectors to a
control panel. The initiating device circuit (IDC) can be wired on Class A
or Class B.
General Operation
Normal standby condition: The module receives polling from the control
panel at the regular interval. Polling LED (green) flashes.
Alarm condition: When an external input is activated, Input LED (red)
illuminates, and the module communicates to the control panel the
alarm status.
Trouble condition: If an overcurrent occurs because SLC (Signaling Line
Circuit) is shorted, SCI LED (yellow) illuminates, and the module
communicates to the control panel the short status. The module also
communicates to the control panel the open/short status of IDC,
depending on the Subtype Setting described below.
SCI (Short Circuit Isolator) Function
The module has a built-in short circuit isolator. SCI circuit prevents
entire loop failure in the event of a short between L+ and L- on the loop.
If a short is detected between L+ and L-, the yellow LED indicator is
illuminated. The line between Lin- and Lout- is disconnected
automatically to isolate the short circuit, and short circuit status is
communicated to the control panel. Upon removal of the short condition,
the module will automatically connect between Lin- and Lout- to restore
the entire loop to the normal operating status.
Polling LED (GREEN)
Input LED (RED)
SCI LED (YELLOW)
Address Setting Port
Figure 1
Figure 2
NITTAN COMPANY, LIMITED
1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN
http://www.nittan.com
Make sure to turn the power off before commencing any wiring work.
Otherwise it may cause electric shock or damage to equipment.
CAUTION
!
Do not disassemble, repair, or modify the products. It may cause a fire or
electric shock.
CAUTION
!
Do not use the products outside the rated power supply voltage range
specified in the Specifications. It may cause a fire or damage to
equipment.
CAUTION
!
DW1401990 Rev.K2
Dec 18, 2019
2
Compatibility Requirement
To ensure proper operation, the module shall be connected to UL listed
control panel NFU-7000 series.
Before Installing
Disconnect power to the control panel before installing the module. If
the module is installed in an existing operational system, inform the
operators and local authorities that the system will be temporarily out
of service.
Mounting
Mount the module directly to 4’’ square electrical box (UL Listed).
Secure the module to the electrical box, as shown in Figure 3.
Main unit
Outer cover EVA
Electrical box
Tapping screw
Pan head screw
Figure 3
Setting
・Address Setting
Use EVA-AD2 Programmer for setting the address of the module prior
to installation. EVA-ZMU-SCI has an address given at random from
factory. Connect the Programmer with the address setting port to
change the address to any of 1-254 (dec), with reference to the
instruction manual of EVA-AD2 Programmer. The address can be set
regardless of whether power supply from the control panel is turned on
or off. During setting address, the module does not respond to the
control panel.
Set the address of module according to Job data.
・Subtype Setting
Set the subtype depending on the wiring configuration as below. The
subtype is to be set through the Configurator for the control panel.
Sub
type
Input
Method
Open
-circuit
Detection
Short
-circuit
Detection
Class
Interrupt
1
Normally
Open
Yes
No
Class B
Disabled
2
Enabled
3
Class A
Disabled
4
Enabled
5
Normally
Open
Yes
Yes
Class B
Disabled
6
Enabled
7
Class A
Disabled
8
Enabled
When interrupt is enabled, it allows a high priority communication to
the control panel. The consumption current increases with this setting.
Note : Applicable subtype setting differs depending on control panels.
Subtype 1 to 8 can be used with the control panel complying with UL864
9th edition.
Subtype 5 to 8 can be used with the control panel complying with UL864
10th edition.
Please contact Nittan customer service for any required details.
Compatible Two wire detector for use with EVA-ZMU-SCI with Zone
Identifier A:
Detector
Model
Compatibility
ID
Detector
Type
Base
Model
Base
ID
Max.
No. of
Detectors
EVCA-P
A
Photoelectric
EVA
-UB4
EVA
-UB4-6
A
20
Operating voltage range 12 to 18VDC
DW1401990 Rev.K2
Dec 18, 2019
3
Wiring
All wiring must conform to applicable local codes, ordinances, and
regulations.
Install module wiring in accordance with the appropriate wiring
diagrams.
Note: All wiring is power-limited and supervised.
Class B (Short circuit detection is not available)
Detectors and EOL (10k ohm) are connected between A+ and A- in
EVA-ZMU-SCI.
A+
A-
Lin+
Lin-
Lout+
Lout-
EOL
10kΩ
16
3
16
3
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Figure 4
Class A (Short circuit detection is not available)
Detectors are connected between A+(B+)and A- (B-)in EVA-ZMU-SCI.
B-
B+
A+
A-
Lin+
Lin-
Lout+
Lout-
16
3
16
3
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Figure 5
Class B (Short circuit detection is available)
Detectors and EOL (10k ohm) are connected between A+ and A- in
EVA-ZMU-SCI.
Refer to Figure 4.
Class A (Short circuit detection is available)
Detectors are connected between A+(B+)and A- (B-)in EVA-ZMU-SCI.
Refer to Figure 5.
Maintenance
Routine inspection: Ensure the module is secure and undamaged.
Operation Test
The purpose of the Operational Test is to confirm the product’s correct
operation.
1) When carrying out site testing of the product, the control panel
shall be set to “one-man-walk test mode” prior to the test.
2) Take any necessary precautions to limit the sounding of the alarm
sounders/bells and any fire service summoning device.
3) Operate a detector connected to IDC of the module, and confirm
that the module is in alarm condition and the input LED (red)
illuminates. Confirm that an alarm signal is transmitted to the
control panel.
Note: If the test cannot be carried out by operating the detector, test the
area between terminal A+ and A-(or B+ and B-)with appr. 2.4kΩ
resistor to check the module.
4) After the detector has given the alarm condition, reset the detector
from the control panel. It may be necessary to allow a short time to
elapse before the detector is reset.
Note: For detector testing and cleaning information, refer to the
instruction manual of detector.
5) In any subtype setting, open between terminal A+ and A-(or B+
and B-), and confirm that the control panel detects the open circuit.
If subtype is set as 5-8, short between A+ and A-(or B+ and B-),
and confirm that the control panel detects the short circuit.
6) Short between terminal Lin+ (Lout+) and Lin- (Lout-), and the SCI
LED (yellow) is illuminated. The short circuit isolator isolates the
devices connected after the short-circuited area, which makes these
devices have no response. Upon removal of the short condition, the
area is automatically connected to go back to the normal operating
status, and the SCI LED (yellow) turns off.
Do not connect cables in reverse polarity. Failure to connect the polarity
correctly could result in damage to the module and/or other equipment.
CAUTION
!
Use cable AWG12-22 for wiring. Do not connect different gauge cables
at one terminal in order to prevent loosening. Use a fork terminal for
crimping two cables.
CAUTION
!
DW1401990 Rev.K2
Dec 18, 2019
4
FOR WARRANTY SERVICE, RETURN TO:
OVERSEAS BUSINESS DIVISION, NITTAN COMPANY, LIMITED
1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN
http://www.nittan.com
Specifications
SLC Applied Voltage
Rated Range 20 to 38VDC
SLC Current Consumption
Standby 2.6mA
Alarm 35.9mA (max)
SLC Line Impedance
Up to 50 ohms
Number of IDC Circuits
1 x Class A or 1 x Class B
IDC Circuit Rating
12 to 18VDC, 560 ohms,
32mA(max)
IDC Line impedance
Up to 50 ohms
EOL Device
RE-10k (10k ohms, 1/4W) ,
Class B only
SCI on Resistance
0.2 ohms (max)
SCI Fault Detection Threshold
10V (min)
SCI Isolation Current
22mA (max)
Visual Indicator (Status LED)
Polling LED(GREEN)
Input LED(RED)
SCI LED(YELLOW)
Ambient Installation
Temperature
0℃to 49℃(32°F to 120°F)
Storage Temperature
-20℃to 60℃(-4°F to 140°F)
Max Relative Humidity
Up to 93%RH,non-condensing
Environment
Indoor dry use only
Maximum quantity per loop
127 units
Terminal
Screw AWG12 to 22
Address Setting
EVA-AD2 Address Programmer
Dimensions
124mm H x 124mm W x 34.5mm D
(4.882’’ H x 4.882’’ W x 1.358’’ D)
(Mount to a 4’’ square by 2⅛’’ deep
box)
Weight
Approximately154g (5.5oz)
Conformity
UL864
Warranties
1.1 Nittan warrants to the customers that:
(a) all products supplied hereunder will be of merchantable quality
and will comply with any specification agreed between Nittan and
customer.
(b) it is not aware of any rights of any third party in the market which
would or might render the sale of the products, or the use of any of
the trade marks on or in products, or the use of any of the trade
marks on or in relation to the products, unlawful.
1.2 In the event of any breach of the Nittan's warranty in Clause 1.1(a)
whether by reason of defective materials, production faults or
otherwise, Nittan's liability shall be limited to:
(a) replacement of the products in question; or
(b) at the Nittan’s option, repayment of the price where this had been
paid. And the warranty period is three (3) years from the shipment
from Nittan’s factory.
1.3 Notwithstanding anything to the contrary in this warranty terms,
Nittan shall not be liable to the customer by reason of any
representation or implied warranty, condition or other term or any
duty at common law, or under the express terms of this warranty
terms, for any consequential loss or damage whether for loss of
profit or otherwise and whether occasioned by the negligence of
Nittan or its employees or agents or otherwise, arising out of or in
connection with any act or omission of Nittan relating to Nittan or
supply of the products, their use by any customer.
1.4 Customer shall indemnify Nittan against all loss, damages,
liabilities, costs and expenses which Nittan may suffer or incur as a
result of or in connection with any breach by customer of this
warranties terms or any laws or regulations of any jurisdiction or
any rules of any governing authorities.

Other Nittan Control Unit manuals

Nittan EV-SCM Manual

Nittan

Nittan EV-SCM Manual

Nittan EVA-SCM-SCI User manual

Nittan

Nittan EVA-SCM-SCI User manual

Nittan EVA-DIP-SCI User manual

Nittan

Nittan EVA-DIP-SCI User manual

Popular Control Unit manuals by other brands

Madas XVR-1-3-6 manual

Madas

Madas XVR-1-3-6 manual

Sinclair SCMI-03S user manual

Sinclair

Sinclair SCMI-03S user manual

Honeywell VGF installation instructions

Honeywell

Honeywell VGF installation instructions

Niobrara QUCM 3964 Installation and programming manual

Niobrara

Niobrara QUCM 3964 Installation and programming manual

M-system R30TS4 instruction manual

M-system

M-system R30TS4 instruction manual

Texas Instruments LM5123EVM-BST user guide

Texas Instruments

Texas Instruments LM5123EVM-BST user guide

Sit 650 DELTA Use and Installation Instructions

Sit

Sit 650 DELTA Use and Installation Instructions

SEW-Eurodrive Movidrive MDX61B manual

SEW-Eurodrive

SEW-Eurodrive Movidrive MDX61B manual

Taconova NOVAMIX COMPACT quick start guide

Taconova

Taconova NOVAMIX COMPACT quick start guide

Honeywell Esser IQ8TAL Installation instruction

Honeywell

Honeywell Esser IQ8TAL Installation instruction

ABB A3 Series instruction sheet

ABB

ABB A3 Series instruction sheet

Siemens CU240S DP-F operating instructions

Siemens

Siemens CU240S DP-F operating instructions

Burkert 0290 operating instructions

Burkert

Burkert 0290 operating instructions

Dart DP10 instruction manual

Dart

Dart DP10 instruction manual

Seneca Z-4DI-2AI-2DO installation guide

Seneca

Seneca Z-4DI-2AI-2DO installation guide

Warren rupp Sandpiper HD20F Service & operating manual

Warren rupp

Warren rupp Sandpiper HD20F Service & operating manual

Ross Vision 4800DR-325-02 installation guide

Ross

Ross Vision 4800DR-325-02 installation guide

SMA 1C4-313-001-001 Replacement manual

SMA

SMA 1C4-313-001-001 Replacement manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.