Nittan EVA-DIP-SCI User manual

DW1401989 Rev.K2
Dec 18, 2019
1
Instruction Manual
EVA-DIP-SCI Dual Input Module
Before Installation
Please read these instructions carefully and keep for future reference.
The information in this document is subject to change without notice. For
updates please refer to our website.
Note :Follow the requirements for the installation of the product in
accordance with the Specifications. Otherwise it may cause malfunction.
Note :Do not install the product in any location where oil, dust, iron
powder, chemicals, or hydrogen sulphide may occur or affect the product. It
may cause malfunction.
This package contains the following items:
Main unit ……………………………………………………………………1
Outer cover EVA ……………………………………………………………1
Instruction Manual …………………………………………………………1
Tapping screw ………………………………………………………………2
Pan head screw ……………………………………………………………2
EOL register (RE-10k) ………………………………………………… 2
General Description
EVA-DIP-SCI Dual Input Module with Short Circuit Isolator is intended
for use in addressable two wire systems. The module monitors and
transmits the status (normal, open, short, or active) of devices equipped
with NC/NO dry contacts to a control panel. The initiating device circuit
(IDC) can be wired on Class A or Class B.
Note: Any conventional detector cannot be connected with the module.
General Operation
Normal standby condition: The module receives polling from the control
panel at the regular interval. Polling LED (green) flashes.
Active condition: When an external input is activated, Input LED (red)
illuminates, and the module communicates to the control panel the active
status.
Trouble condition: If an overcurrent occurs because SLC (Signaling Line
Circuit) is shorted, SCI LED (yellow) illuminates, and the module
communicates to the control panel the short status. The module also
communicates to the control panel the open/short status of IDC, depending
on the Subtype Setting described below.
SCI (Short Circuit Isolator) Function
The module has a built-in short circuit isolator. SCI circuit prevents entire
loop failure in the event of a short between L+ and L- on the loop. If a short
is detected between L+ and L-, the yellow LED indicator is illuminated.
The line between Lin- and Lout- is disconnected automatically to isolate
the short circuit, and short circuit status is communicated to the control
panel. Upon removal of the short condition, the module will automatically
connect between Lin- and Lout- to restore the entire loop to the normal
standby status.
Figure 1
Figure 2
NITTAN COMPANY, LIMITED
1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN
http://www.nittan.com
Polling LED (GREEN)
Input LED (RED)
SCI LED (YELLOW)
Address Setting Port
mm(in)
Make sure to turn the power off before commencing any wiring work.
Otherwise it may cause electric shock or damage to equipment.
CAUTION
!
Do not use the products outside the rated power supply voltage range
specified in the Specifications. It may cause a fire or damage to
equipment.
CAUTION
!
Do not disassemble, repair, or modify the products. It may cause a fire
or electric shock.
CAUTION
!

DW1401989 Rev.K2
Dec 18, 2019
2
Compatibility Requirement
To ensure proper operation, the module shall be connected to UL listed
control panel NFU-7000 series.
Before Installing
Disconnect power to the control panel before installing the module. If the
module is installed in an existing operational system, inform the operators
and local authorities that the system will be temporarily out of service.
Mounting
Mount the module directly to 4’’ square electrical box (UL Listed).
Secure the module to the electrical box, as shown in Figure 3.
Main unit
Outer cover EVA
Electrical box
Tapping screw
Pan head screw
Figure 3
Setting
・Address Setting
Use EVA-AD2 Programmer for setting the address of the module prior to
installation. EVA-DIP-SCI has an address given at random from factory.
Connect the Programmer with the address setting port to change the
address to any of 1-254 (dec), with reference to the instruction manual of
EVA-AD2 Programmer. The address can be set regardless of whether
power supply from the control panel is turned on or off. During setting
address, the module does not respond to the control panel.
Set the address of module according to Job data.
・Subtype Setting
Set the subtype depending on the wiring configuration as below. The
subtype is to be set through the Configurator for the control panel.
Sub
Type
Input
Method
Open
-circuit
Detection
Short
-circuit
Detection
Class
Interrupt
1
Normally
Open
Yes
No
Class B
Disabled
2
Enabled
3
Class A
Disabled
4
Enabled
5
Normally
Close
No
Yes
Class B
Disabled
6
Enabled
7
Normally
Open
Yes
Yes
Class B
Disabled
8
Enabled
9
Class A
Disabled
10
Enabled
When interrupt is enabled, it allows a high priority communication to the
control panel. The consumption current increases with this setting.
Note : Applicable subtype setting differs depending on control panels.
Subtype 1 to 10 can be used with the control panel complying with UL864
9th edition.
Subtype 7 to 10 can be used with the control panel complying with UL864
10th edition.
Please contact Nittan customer service for any required details.
Wiring
All wiring must conform to applicable local codes, ordinances, and
regulations.
Install module wiring in accordance with the appropriate wiring diagrams.
Use cable AWG12-22 for wiring. Do not connect different gauge cables
at one terminal in order to prevent loosening. Use a fork terminal for
crimping two cables.
CAUTION
!
Do not connect cables in reverse polarity. Failure to connect the polarity
correctly could result in damage to the module and/or other equipment.
CAUTION
!
Note: All wiring is power-limited and supervised.

DW1401989 Rev.K2
Dec 18, 2019
3
Class B (Short circuit detection is not available)
EOL (10k ohm) is connected between A+ (B+ )and A- (B-)in
EVA-DIP-SCI.
Dry contact switches(input switches)are OFF.
Figure 4
Class A (Short circuit detection is not available)
It is a status that dry contact switches connected between A+(B+)and A-
(B-)in EVA-DIP-SCI are OFF.
Figure 5
Class B (Short circuit detection is available)
EOL (10k ohm) is connected between A+ (B+ )and A- (B-)in
EVA-DIP-SCI.
Dry contact switches are OFF.
*Two external inputs can be connected to one input line.
*Resistor of 2.2k ohms(RE-2.2k)is an option and not included in this
product.
B-
B+
A+
A-
Lin+
Lin-
Lout+
Lout-
EOL
10kΩ
Typical wiring for N/O contacts only
2.2kΩ2.2kΩ
2.2kΩ2.2kΩ
EOL
10kΩ
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Figure 6
Class A (Short circuit detection is available)
It is a status that dry contact switches connected between A+(B+)and A-
(B-)in EVA-DIP-SCI are OFF.
*Two external inputs can be connected to the input line.
*Resistor of 2.2k ohms(RE-2.2k)is an option and not included in this
product.
B-
B+
A+
A-
Lin+
Lin-
Lout+
Lout-
Typical wiring for N/O contacts only
2.2kΩ2.2kΩ
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Figure 7
Normally Close Class B
A dry contact switch and EOL (10k ohm) are connected in series between
A+(B+)and A-(B-)in EVA-DIP-SCI.
Dry contact switches are ON.
*Only one external input can be connected to one input line.
B-
B+
A+
A-
Lin+
Lin-
Lout+
Lout-
Typical wiring for N/C contacts only
EOL
10kΩ
EOL
10kΩ
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Figure 8
EOL
10kΩ
Typical wiring for N/O contacts only
EOL
10kΩ
B-
B+
A+
A-
Lin+
Lin-
Lout+
Lout-
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
B-
B+
A+
A-
Lin+
Lin-
Lout+
Lout-
Typical wiring for N/O contacts only
Loop
- +
TO NEXT
DEVICE
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE

DW1401989 Rev.K2
Dec 18, 2019
4
Maintenance
Routine inspection: Ensure the module is secure and undamaged.
Operation Test
The purpose of the Operational Test is to confirm the product’s correct
operation.
1) When carrying out site testing of the product, the control panel shall
be set to “one-man-walk test mode” prior to the test.
2) Take any necessary precautions to limit the sounding of the alarm
sounders/bells and any fire service summoning device.
3) Turn on the external inputs connected to the module, and confirm
that the module is in active condition and the input LED (red)
illuminates. Confirm that an active signal is transmitted to the
control panel.
Note: If the test cannot be carried out through the external inputs, test the
area between terminal A+ and A-(or B+ and B-)to check the module. (In
accordance with the subtype setting, set the status either 0Ωshort (for
subtype 1-4), 2.2kΩshort (for subtype 7-9), or open (for subtype 5-6).)
4) After the external inputs have brought the module into the active
condition, reset the external inputs. Confirm that the module goes
back to the initial status after the external inputs are reset.
5) If subtype is set as 1-4, or 7-10, open between terminal A+ and A-(or
B+ and B-)and confirm that the control panel detects the open
circuit. If subtype is set as 5-10, short between terminal A+ and A-(or
B+ and B-)and confirm that the control panel detects the short
circuit.
6) Short between terminal Lin+ (Lout+) and Lin- (Lout-), and the SCI
LED (yellow) illuminates. The short circuit isolator isolates the
devices connected after the short-circuited area, which makes these
devices have no response. Upon removal of the short condition, the
area is automatically connected to go back to the normal standby
status, and the SCI LED (yellow) turns off.
FOR WARRANTY SERVICE, RETURN TO:
OVERSEAS BUSINESS DIVISION, NITTAN COMPANY, LIMITED
1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN
http://www.nittan.com
Specifications
SLC Applied Voltage
Rated range 20 to 38VDC
SLC Current Consumption
Standby 3.0mA
Activated 16.9mA(max)
SLC Line Impedance
Up to 50 ohms
Number of IDC Circuits
1 x Class A or 2 x Class B
IDC Circuit Rating
15VDC, 2.2k ohms, 6.8mA (max)
IDC Line Impedance
Up to 50 ohms
EOL Device
RE-10k (10k ohms, 1/4W), Class B
only
2.2k ohms EOL required for each dry
contact switch in subtype setting
7,8,9,and 10
SCI on Resistance
0.2 ohms (max)
SCI Fault Detection Threshold
10V (min)
SCI Isolation Current
22mA (max)
Visual Indicator (Status LED)
Polling LED (GREEN)
Input LED (RED)
SCI LED (YELLOW)
Ambient Installation
Temperature
0℃to 49℃(32°F to 120°F)
Storage Temperature
-20℃to 60℃(-4°F to 140°F)
Max Relative Humidity
Up to 93%RH, non-condensing
Environment
Indoor dry use only
Max. number of units per loop
127 units
Terminal
Screw AWG12 to 22
Address Setting
EVA-AD2 Address Programmer
Dimensions
124mm H x 124mm W x 34.5mm D
(4.882’’ H x 4.882’’ W x 1.358’’ D)
(Mount to a 4’’ square by 2⅛’’ deep
box)
Weight
Approximately 153g (5.4oz)
Conformity
UL864

DW1401989 Rev.K2
Dec 18, 2019
5
Warranties
1.1 Nittan warrants to the customers that:
(a) all products supplied hereunder will be of merchantable quality and
will comply with any specification agreed between Nittan and
customer.
(b) it is not aware of any rights of any third party in the market which
would or might render the sale of the products, or the use of any of the
trade marks on or in products, or the use of any of the trade marks on
or in relation to the products, unlawful.
1.2 In the event of any breach of the Nittan's warranty in Clause 1.1(a)
whether by reason of defective materials, production faults or
otherwise, Nittan's liability shall be limited to:
(a) replacement of the products in question; or
(b) at the Nittan’s option, repayment of the price where this had been paid.
And the warranty period is three (3) years from the shipment from
Nittan’s factory.
1.3 Notwithstanding anything to the contrary in this warranty terms,
Nittan shall not be liable to the customer by reason of any
representation or implied warranty, condition or other term or any
duty at common law, or under the express terms of this warranty
terms, for any consequential loss or damage whether for loss of profit
or otherwise and whether occasioned by the negligence of Nittan or its
employees or agents or otherwise, arising out of or in connection with
any act or omission of Nittan relating to Nittan or supply of the
products, their use by any customer.
1.4 Customer shall indemnify Nittan against all loss, damages, liabilities,
costs and expenses which Nittan may suffer or incur as a result of or in
connection with any breach by customer of this warranties terms or
any laws or regulations of any jurisdiction or any rules of any
governing authorities.
Other Nittan Control Unit manuals