manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell VGF User manual

Honeywell VGF User manual

Other Honeywell Control Unit manuals

Honeywell BCU 460 Manual

Honeywell

Honeywell BCU 460 Manual

Honeywell NOTIFIER FW-MM User manual

Honeywell

Honeywell NOTIFIER FW-MM User manual

Honeywell Y8610U Operation manual

Honeywell

Honeywell Y8610U Operation manual

Honeywell ESSER IQ8MCP User manual

Honeywell

Honeywell ESSER IQ8MCP User manual

Honeywell VR8305 User manual

Honeywell

Honeywell VR8305 User manual

Honeywell VS8510 User manual

Honeywell

Honeywell VS8510 User manual

Honeywell Fire-lite FFT User manual

Honeywell

Honeywell Fire-lite FFT User manual

Honeywell CentraLine CLIOL822A Operation manual

Honeywell

Honeywell CentraLine CLIOL822A Operation manual

Honeywell BA298I-F User manual

Honeywell

Honeywell BA298I-F User manual

Honeywell BA298F User manual

Honeywell

Honeywell BA298F User manual

Honeywell PFA 700 Manual

Honeywell

Honeywell PFA 700 Manual

Honeywell Kromschroder BCM 400 B1 Series User manual

Honeywell

Honeywell Kromschroder BCM 400 B1 Series User manual

Honeywell RV284 User manual

Honeywell

Honeywell RV284 User manual

Honeywell D05T User manual

Honeywell

Honeywell D05T User manual

Honeywell XW100 User manual

Honeywell

Honeywell XW100 User manual

Honeywell S7800A1167 User manual

Honeywell

Honeywell S7800A1167 User manual

Honeywell Galaxy 2 Series User manual

Honeywell

Honeywell Galaxy 2 Series User manual

Honeywell NOTIFIER 020-772 User manual

Honeywell

Honeywell NOTIFIER 020-772 User manual

Honeywell NK295C User manual

Honeywell

Honeywell NK295C User manual

Honeywell LTE-L57A User manual

Honeywell

Honeywell LTE-L57A User manual

Honeywell VR8205 User manual

Honeywell

Honeywell VR8205 User manual

Honeywell DirectLine DL421 User manual

Honeywell

Honeywell DirectLine DL421 User manual

Honeywell SK-Mon-10 User manual

Honeywell

Honeywell SK-Mon-10 User manual

Honeywell S4560A User manual

Honeywell

Honeywell S4560A User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

® U.S. Registered Trademark
Copyright © 2004 Honeywell International Inc. • All Rights Reserved
INSTALLATION INSTRUCTIONS
62-0213
VGF
Flanged Globe Valves
APPLICATION
VGF Flanged Globe Valves are used for on-off or
modulating control of steam, hot water, or chilled water-
glycol solutions up to 50% concentration in heating,
ventilating and air conditioning (HVAC) systems. They
can be operated by ML6984/7984, ML6420/6425,
ML7420/7425, M6421/7421 Electric Linear Actuators,
MP953 Pneumatic Actuators, Modutrol® Motors with
Q5001 valve linkage, or MN/MS series Direct Coupled
Actuators with Q5020 valve linkage.
Three-way bodies are available in mixing or diverting
style with equal percentage and linear flow characteristic.
Pressure-balanced models feature very high, low
leakage close-off ratings. Flanges conform to ANSI
standard B16.1, Classes 125 and 250, with face-to-face
dimensions per ANSI/ISA 75.03
Fig. 1. Proper hoisting of VGF Valves.
Safety
The valves are to be installed by skilled personnel and in
strict accordance with the installation instructions and
local regulations. (See Fig. 1 for proper hoisting method.)
Honeywell assumes no responsibility for damages or
injuries resulting from non-compliance with installation
instructions or standard good practice when mounting,
operating, or maintaining the valves, even if not explicitly
mentioned in the installation instructions. (See Fig. 2 for
basic pipe orientation.) Observe all safety practices when
working with steam systems.
Proper Use
These valves are only for use in cold, warm, hot water
systems and for steam applications. They are designed
for a medium temperature range of from 35 to 355°F, at a
maximum pressure of 125 or 250 psig, depending on
their ANSI body class. They are to be operated with the
appropriate Honeywell actuators only. Please refer to the
VGF family product data sheet, form 63-2618 for detail.
Water should be properly filtered, treated and
conditioned according to local conditions. The installation
of a strainer is strongly recommended.
Fig. 2. Basic pipe orientation.
VGF FLANGED GLOBE VALVES
62-0213 2
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Severe Burn Hazard.
Contact with hot liquid can lead to severe
injury or cause death.
Release system pressure and isolate or drain the
valve pipe section so the medium (steam, water
or glycol solution) does not leak out of the valve
body during installation (see Fig. 3).
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply to the actuator to
prevent electrical shock and equipment
damage, or remove and cap the air line to the
actuator.
IMPORTANT
• Before installing the valve, raise and lower the
valve stem to make sure that the valve stem
operates freely. Impaired stem operation can
indicate that the stem was bent by rough
handling. This condition can require replacing
the valve.
• Protect the stem from damage due to bending
or scratching.
Fig. 3. Piping must prevent leakage.
Location
Select a location where the valve and actuator are
accessible. Allow sufficient space for servicing the valve
and actuator. See Fig. 6 for valve body dimensions.
Mounting the Valve
See Fig. 5 for typical installation.
1. Hoist valve by its body only. Do not lift by stem,
bonnet, flanges, or flange holes. (See Fig. 1.)
2. Install the valve so the flow follows the direction of
the arrow indicated on the valve body.
3. Install the valve so the actuator is above the valve
body. The valve can be installed in any position
between vertical and horizontal. Do not install the
valve with the stem below horizontal or upside
down.
4. When controlling steam, use appropriate high
temperature kit 43196000 and rotate valve body so
that actuator is not positioned directly above the
piping.
5. Use companion flanges with the same number of
bolt holes and dimensions as the valve to be
installed. The optional service flange may be
installed in the lower port. See Table 1 for part
numbers. Use standard cast-iron flanges for the
two end ports.
6. Use a gasket material recommended for the
medium to be handled.
7. Use mounting bolts long enough so the nuts can
use the full length of the nut threads. (See Fig. 4.)
Use bolts 1/8 in. smaller than the diameter of the
bolt hole to allow clearance for installing. (See
Fig. 5.)
Table 1. Service Flange Part Numbers.
Fig. 4. Basic proper bolt length.
Valve Size
in in. (mm) ANSI 125 ANSI 250
2 1/2 (65) 208628 208633
3 (80) 208629 208634
4 (100) 208630 208635
5 (125) 208631 208636
6 (150) 208632 208637
133 in-lb
(15 Nm)
VGF FLANGED GLOBE VALVES
3 62-0213
Mounting Actuator
For information on mounting, refer to the Product Data
literature for the actuator. Actuator installation clearances
are provided. It is important to have the correct actuator
available for the installation. See Table 2 for basic
clearance information.
Table 2. Installation Clearances
(from Valve Bonnet, B).
Fig. 5. Flanged valve body installation.
Fig. 6. Dimensions for valve installation.
Table 3. Valve Sizes and Dimensions.
aThree-way valves only.
NOTE: See VGF family Product Data sheet
(form 63-2618) for complete specifications.
CHECKOUT
For instructions for operating the valve actuator, see the
Product Data sheet for the specific actuator. Operate the
control system and check the valve operation to
determine that the valve stem positions the valve
smoothly through full stroke without binding.
Actuator
Minimum
Vertical Clearance
in in. (mm)
ML6420, ML7420 12-11/16 (322)
ML6421A, ML7421A 14-1/4 (360)
ML6421B, ML7421B 16-7/8 (430)
ML6425A,B; ML7425A,B 14-5/16 (364)
MN/MS Series + Q5020 12 (305)
ML6984, ML7984
Modutrol IV + Q5001 14-1/2 (369)
MP953C (8 inch dia) 11-7/8 (302)
MP953C (13 inch dia) 17-11/16 (449)
MP953E (8 inch dia) 16-1/2 (420)
MP953E (13 inch dia) 25-13/16 (655)
COMPANION
FLANGE
GASKET
GASKET
GASKET
BE SURE FACE OF COMPANION FLANGE IS FLUSH
WITH FACE OF VALVE-BODY FLANGE AND ALIGNED
SQUARELY BEFORE TIGHTENING MOUNTING NUTS.
OPTIONAL SERVICE FLANGE
COMPANION FLANGE
PIPE M7977
Size
Dimensions, in. (mm)
See Fig. 6
in. DN A Da
ANSI Class 125
2-1/2 65 10-7/8 (276) 3-3/4 (95)
3 80 11-3/4 (298) 4-3/8 (111)
4 100 13-7/8 (352) 5-1/8 (130)
5 125 15-3/4 (400) 5-3/4 (146)
6 150 17-3/4 (451) 6-5/8 (168)
ANSI Class 250
2-1/2 65 11-1/2 (292) 3-3/4 (95)
3 80 12-1/2 (318) 4-3/8 (111)
4 100 14-1/2 (368) 5-1/8 (130)
5 125 16-5/8 (422) 5-3/4 (146)
6 150 18-5/8 (473) 6-5/8 (168)
M22409
D
A
C
B
1DOTTED LINE REPRESENTS ANSI 125
VALVE BONNET.
1
E
Stroke Y
62-0213 B.B. 9-04 www.honeywell.com