1. APPLICATION
The NIPRESS D-400 series pressure transmitters measuring pressure and converting it into voltage and
current output can be used in 2- and 3-wire systems. The wide choice of the models makes it suitable for the
most pressure measurement tasks whether relative or absolute pressure, static or dynamic measurement is
required even at high temperatures. The series is available with two different accuracy classes.
Design of the transmitter, its overload capability and wide range of temperature and the possibility to install
the unit in any position allows their application in the most different industrial circumstances. It is especially
suitable for pressure measurement of contaminated mediums and at the bottom (level). Standard pressure
transmitting fluid is silicone oil but on request unit with liquid acceptable in the food industry is also available.
Transmitters can be delivered with plug in display UNICONT PLK-501 enabling on site reading.
2. TECHNICAL DATA
TYPE D–4–
Range -1
–
400 ba
r
(according to the order code)
Overload capability
A
ccording to the order code
Accuracy ±0.5%
Optionally (0.4 bar  PN 40 bar): ±0.25%
Medium temperature
Filling fluid silicone oil: -40 °C … +125 °C
High temperature version max. +300 °C
Filling fluid food grade oil: -10 °C … +125 °C
High temperature version max. +250 °C
Usage in vacuum max. +150 °C
Ambient temperature -40 °C … +85 °C
-5 °C … +70 °C (cable outlet without ventilation tube)
Sensing method Piezoresistive
Materials of
wetted parts
Senso
r
1.4435 stainless steel (diaphragm)
Sensor sealing FKM (Viton, max. +200 °C),
optional FFKM (recommended for medium temp. > +200 °C max. 100 bar),
Dairy pipe, Tri-Clamp connection: without seals
Process connection Stainless steel: 1.4435 (316 L)
Housing Stainless steel: 1.4404 (316 L)
Output 4 – 20 mA; 0 – 10 V
Power supply 4 – 20 mA output: 8 – 32 V DC
0 – 10 V DC voltage output: 14 – 30 V DC
Load resistance 4 – 20 mA 2-wire current output Rmax = [( US– 8 V ) / 0.02 A] 
0 – 10 V DC voltage output: R > 10 k
Process connection
A
ccording to the order code
Electric connection ISO 4400 connection, M12 x 1 (4-pin), and integral cable version
Ingress protection IP65 (ISO4400) / IP67 (M12 x 1) / IP68 (integral cable version)
Electric protection SELV Class III
Mass ~ 0.2 kg
2.1 ACCESSORIES
User’s Manual,
Warranty Card,
EU Declaration of Conformity
ADDITIONAL DATA FOR EX APPROVED MODELS (ONLY FOR 4–20 mA /2-WIRE)
TYPE D
–
4
–
6 Ex D
–
4–D Ex
Ex marking Pending
Power supply Usupply=10V … 28 VDC
Intrinsically safe data Use only with Ex ia certified power supply!
Uimax = 28 V DC, Iimax = 93 mA, Pimax = 660 mW, Ci 0 nF, Li 0 mH
The supply connections have an inner capacity of max. 27nF to the housing.
Permissible temperatures for environment Zone 1, 2: -20 °C …+70 °C
Zone 0: 0.8 ba
r
PATM 1.1 ba
r
: -20 °C …+60 °C
2.2 ORDER CODE (NOT ALL COMBINATIONS POSSIBLE!)
NIPRESS D
–
4
–
MEASUREMENT /
TEMPERATURE CODE PROCESS CONNECTION CODE CODE RANGE (OVERLOAD CAPABILITY)BAR (1) CODE OUTPUT /EXCODE
Relative / up to +125 °C R ½" BSP (4) B 0 - 1
–
0 (5)
(12) 0
–
10 (40)
A
4
–
20 mA 2-wire 2
A
bsolute / up to +70 °C(2) E ½" BSP
(5) C 1 0
–
0.1 (0.5) 0
–
16 (80) B 0
–
10 V 3-wire 3
Relative / up to +150 °C
high temperature(3) H ¾" BSP
(2) D R 0
–
0.16 (1) 0
–
25 (80) C 4-20 mA 2-wire /Ex ia 6
1” BSP E 2 0
–
0.2
5
(1) 0
–
40 (105) D 4-20 mA 2-wire SIL2 C
Relative / up to +300 °C
high temperature(3) J 1 ½" BSP F 3 0
–
0.4 (2) 0
–
60 (100) E 4-20 mA 2-wire SIL2 /Ex ia D
¾" Triclamp
(10) T 4 0
–
0.6 (5) 0
–
100 (200) F
1" Triclamp
(7) L 5 0
–
1.0 (5) 0
–
160 (400) G
1 ½" Triclamp (8) M 6 0
–
1.6 (10) 0
–
250 (400) H ACCURACY CODE
2" Triclamp (8) N 7 0
–
2.
5
(10) 0
–
400 (600) J 0.25%
(13) 1
Dairy pipe DN25(6) (11) O 8 0
–
4.0 (20) 0.5% 2
Dairy pipe DN40(6) (11) P 9 0
–
6.0 (40)
Dairy pipe DN50(9) (11) R
VARIVENT DN40/50
(14) V
(1) Special range on request
(2) p  0.6 bar
(3) Up to max. 160 bar
(4) p  1 bar
(5) F
r
om -1 bar to 40 bar, up to +12
5
°C, without media separato
r
(6) From 0.25 bar to 40 bar
(7) From 0.25 bar to 16 bar
(8)p  16 bar
(9) From 0.25 bar to 25 bar
(10) From 4 bar to
8
ba
r
(11) In accordance to DIN 11851
(12) Up to max. +150 °C
(13) 0.4 bar  p  40 bar
(14) p  2
5
ba
r
Dodávate:
MICROWELL spol. s r. o.,
SNP 2018/42, 927 00 Šaa
Tel.: (+421) 31/ 770 7585, 770 7587
E-mail: [email protected]
http://www.microwell.sk
IBExU: pending  drc4612a0600h_08 - 2/3
2.3 DIMENSIONS
D

C–4

–

1/2 "BSP FLUSH MEMBRANE
D

E–4

–

1” BSP FLUSH MEMBRANE
DH

–4

–

DJ

–4

–

WITH COOLING ELEMENT
D

V–4

–

VARIVENT DN40/50
TRANSMITTER WITH
PLK-501-2
~33
Ø34,5
Ø26,5
33
SW 27
~60
15
18
1/2" BSP
SW 44
22
19
1" BS P
Ø50
~60
~3
3
33
Ø34,5
Ø26,5
Ø26,5
~32
4848
33
33
Ø34,5
Ø26,5
17
Ø64
Ø71
Ø84
~33
3350
DD–4 –
3/4" BSP FLUSH MEMBRANE
DF–4 –
1 1/2" BSP FLUSH MEMBRANE
3. INSTALLATION
Due to its small size and weight NIPRESS D-400 can be directly installed on
tanks, pipes, machines, etc. without mounting device.
To provide chance for replacement of the instrument during operation the use
of closing armature is recommended. A simple ball valve will be suitable for
lower pressures and for higher pressures (above 6 bar) a three-way blow-off
needle-valve can be suggested.
For measuring hydrostatic pressure for level the unit should be thread in a
stub at the tank wall possibly near to the bottom.
Using longer impulse tube its proper sloping for the necessary deaerating and
emptying has to be ensured.
Measuring low pressures in systems with substantial height difference
between the transmitter and place of measurement the hydrostatic pressure
of the medium in the impulse pipe should be taken into consideration. In the
case of outside installation, the unit is supposed to be protected against rain
or splash water.
3.1 INSTALLATION REGULATION
Depending on the medium measured, the medium may cause hazard to the
installer, therefore you should be wearing suitable protective clothing, gloves,
and goggles.
For mounting and dismantling SW27 or SW44 open-end wrench should be
used. Take care for the vulnerable flush face diaphragm.
The cylindrical housing of the transmitter should not be gripped
and tightened with pipe wrench!
The plug-in electric connector can be unplugged after releasing and removing
its fastening screw. The connection insert can be pushed out by a screw
driver from the direction of the screw.
Pushing electric cable through the cable gland it can be connected to the
relevant points of the connector. Make sure that the cable gland and sealing
plate of the connector will be tight.
For the sake of noise suppression, the transmitter should be grounded. If the
grounding of the appliance with the pressure transmitter is appropriate no
further action will be needed. If not, the grounding should be performed.
Installation steps:
The specified tightening torques must not be exceeded!
Tightening torques:
1/4” BSP: max. 5 Nm; 1/2” BSP max. 10 Nm; 3/4” BSP: max. 15 Nm; 1” BSP:
max. 20 Nm; 1 1/2" BSP: max. 25 Nm.
Mounting steps for connections according to DIN 3852:
Do not use any additional sealing material such as teflon tape! Check the o-
ring is undamaged, it has a flawless and clean surface and seated in the
designated groove. Screw the device into the corresponding thread by hand,
and tighten the parts with a suitable torque wrench.
Mounting steps for dairy pipe connections (DIN11851):
Check the o-ring is undamaged, it has a flawless and clean surface and
seated in the designated groove.
Centre the dairy pipe connection in the counterpart. Screw the cup nut onto
the mounting part, then tighten it using a suitable wrench.
Mounting steps for Clamp and Varivent
£
connections:
Choose a suitable seal for the measured medium and pressure. Place the
seal onto the corresponding mounting part. Centre the clamp connection or
Varivent£connection above the counterpart with seal, then fasten the device
with a suitable fastening element (e. g. half-ring or retractable ring clamp)
according to the supplier’s instructions.
3.2 CONDITIONS OF SAFE OPERATION
Before device turn on, make sure the installation is complete, and there are
no visible defects. The device may only be used within the limitations
specified in the technical specifications.
The device connector must be installed in such a way that the IP20 level of
protection is always remain.
Ex ia certified transmitters can only be operated in qualified, certified and
approved galvanically isolated intrinsically safe Ex ia circuits complying with
the technical data and the device’s explosion protection marking.
The metal housing of the device must be connected to the EP network.
DAIRY PIPE DIN 11851 TRI-CLAMP
10
ØA
ØB
51
33
33
Ø34
Ø26,5
5
ØA
ØB
50
33
33
Ø34
Ø26,5
TYPE DO–
4–
DP–
4–
DR–
4–
DT–
4–
DL–
4–
DM–
4–
DN–
4–
DIMENSIONS DN 25 DN 40 DN 50 3/4" 1" 1 1/2" 2"
A[mm] 23 32 45 14 23 32 45
B[mm] 44 56 68.5 25 50.5 50.5 64
PN[bar]  0.25
 40
 0.25
 40
 0.25
 25
 4
 8
 0.25
 16  16  16
IBExU: pending  drc4612a0600h_08 - 3/3
4. WIRING
2-WIRE CURRENT OUTPUT
3-WIRE VOLTAGE OUTPUT
CONNECTION OF INTEGRAL CABLE
CONNECTION OF ISO 4400
12
3

–
+ Out
+
CONNECTION OF M12 X 1 / 4 pin
1:2:
3: Out

4:
4.1 EXAMPLES OF ARRANGEMENTS
WIRING OF 2-WIRE PRESSURE TRANSMITTERS
P
I
Current controlled
switch
PKK-312
~230V
Pressure transmitter
PLK-501
display
P
I
Panel instrument
PMM-300
PMM-500
~230V
Pressure transmitter
Power supply
PPK-331
P
I
Current loop indicator
PDF-401
~230V
Pressure transmitter
WIRING OF 3-WIRE PRESSURE TRANSMITTERS
Power supply
PPK-331
P
U
Panel instrument
PMG-411
+
Out
~230V
~230V
Pressure
transmitter
WIRING OF 2-WIRE Ex ia PRESSURE TRANSMITTERS
5. TROUBLESHOOTING
Fault Possible causes Fault detection / remedy
No output signal:
Connected incorrectly. Check the connections!
Conductor/wire breakage. Check all wires with cable tester!
Defective measuring
device (signal input).
Check the amperemeter (and its
fuse) and the analog input of the
signal processing unit!
Analog output
signal too low:
Load resistance too high. Check the value of the load
resistance!
Supply voltage too low. Check the power supply and
power /current on the transducer /
transmitter!
Slight shift of the
output signal:
Diaphragm of senor is
severely contaminated.
Cleaning with non-aggressive
cleaning solutions, soft brush or
sponge.
Diaphragm of sensor is
calcified or crusted.
It is recommended to clean
carefully and remove dirt.
Large shift of the
output signal:
Diaphragm of sensor is
damaged (caused by
overpressure or
mechanically).
Check the diaphragm of the
sensor, if it is damaged then send
the device back to the
manufacturer!
6. MAINTENANCE AND REPAIR
The instrument does not require regular maintenance. If necessary possible
dirt deposited should be cleaned off. All repairs will be carried out at the
Manufacturer’s premises.
7. STORAGE CONDITIONS
Storage temperature: -40 °C ... +100 °C
drc4612a0600h_08
July 2019.
NIVELCO reserves the right to change technical data without notice.

Other NIVELCO Measuring Instrument manuals

NIVELCO NIVOTRACK MT 2 Series User manual

NIVELCO

NIVELCO NIVOTRACK MT 2 Series User manual

NIVELCO NIVOROTA EL 7 Series User manual

NIVELCO

NIVELCO NIVOROTA EL 7 Series User manual

NIVELCO UNICONT PDF 01-2 Series Assembly instructions

NIVELCO

NIVELCO UNICONT PDF 01-2 Series Assembly instructions

NIVELCO THERMOCONT TFP Series User manual

NIVELCO

NIVELCO THERMOCONT TFP Series User manual

NIVELCO UNICONT PDF Assembly instructions

NIVELCO

NIVELCO UNICONT PDF Assembly instructions

NIVELCO MicroTREK HT Owner's manual

NIVELCO

NIVELCO MicroTREK HT Owner's manual

NIVELCO NIVOFLIP MAK-100 Series User manual

NIVELCO

NIVELCO NIVOFLIP MAK-100 Series User manual

NIVELCO NIVOCONT User manual

NIVELCO

NIVELCO NIVOCONT User manual

NIVELCO NIVOSONAR SLM-308 User manual

NIVELCO

NIVELCO NIVOSONAR SLM-308 User manual

NIVELCO THERMOCONT TXP-1 Series User manual

NIVELCO

NIVELCO THERMOCONT TXP-1 Series User manual

NIVELCO PiloTREK W-100 Owner's manual

NIVELCO

NIVELCO PiloTREK W-100 Owner's manual

Popular Measuring Instrument manuals by other brands

Shodex Asahipak GF-HQ Series Operation manual

Shodex

Shodex Asahipak GF-HQ Series Operation manual

MaxTo M3 manual

MaxTo

MaxTo M3 manual

Avery Weigh-Tronix 2060 Quick user guide

Avery Weigh-Tronix

Avery Weigh-Tronix 2060 Quick user guide

Stanford Research Systems SR785 Brochure & specs

Stanford Research Systems

Stanford Research Systems SR785 Brochure & specs

Leuze AMS 304i Original operating instructions

Leuze

Leuze AMS 304i Original operating instructions

Pulsar FLOWPULSE instruction manual

Pulsar

Pulsar FLOWPULSE instruction manual

Campbell SR20-T2 product manual

Campbell

Campbell SR20-T2 product manual

Sierra Top-Trak 820 Series instruction manual

Sierra

Sierra Top-Trak 820 Series instruction manual

Pfeiffer Vacuum QMG 422 operating instructions

Pfeiffer Vacuum

Pfeiffer Vacuum QMG 422 operating instructions

Emerson Rosemount 2230 quick start guide

Emerson

Emerson Rosemount 2230 quick start guide

Pfeiffer Vacuum HPT 200 operating instructions

Pfeiffer Vacuum

Pfeiffer Vacuum HPT 200 operating instructions

Argus AA300 user manual

Argus

Argus AA300 user manual

MR MSENSE DGA 9 Installation and operating instructions

MR

MR MSENSE DGA 9 Installation and operating instructions

Bosch DLE 40 Professional Original instructions

Bosch

Bosch DLE 40 Professional Original instructions

National Instruments FD-11613 manual

National Instruments

National Instruments FD-11613 manual

YOKOGAWA PX8000 user manual

YOKOGAWA

YOKOGAWA PX8000 user manual

Weller WXsmart WCU instruction manual

Weller

Weller WXsmart WCU instruction manual

XS Instruments Temp70 PT100 vio instruction manual

XS Instruments

XS Instruments Temp70 PT100 vio instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.