Nordmann Engineering SPA Display User manual

INSTALLATION AND OPERATION MANUAL
Nordmann SPA Display
2591871-A EN 1903

Thank you for choosing Nordmann
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Site:
Model:
Serial number:
Proprietary Notice
This document and the information disclosed herein are proprietary data of Nordmann Engineering AG. Neither
this document, nor the information contained herein shall be reproduced, used, or disclosed to others without the
written authorisation of Nordmann Engineering AG, except to the extent required for installation or maintenance
of recipient's equipment.
Liability Notice
Nordmann Engineering AG does not accept any liability due to incorrect installation or operation of the equipment
or due to the use of parts/components/equipment that are not authorised by Nordmann Engineering AG.
Copyright Notice
© Nordmann Engineering AG, All rights reserved.
Technical modications reserved.

3
Contents
1 Introduction 4
1.1 To the very beginning 4
1.2 Notes on the installation and operation manual 4
2 For your safety 6
3 Product Overview 8
4 Installation 9
4.1 Unpacking and checking the scope of delivery 9
4.2 Storing the unit 9
4.3 Notes on positioning the Nordmann SPA Displays 10
4.4 Mounting the Nordmann SPA Display 10
4.4.1 In-wall mounting 11
4.4.2 On-wall mounting 17
4.5 Connecting the Nordmann SPA Display to the Nordmann Omega or to the
Condair Delta SPA Control Box 23
5 CongurationandoperationoftheNordmannSPADisplay 27
5.1 CongurationoftheNordmannSPA Display 27
5.2 Operation of the Nordmann SPA Display 27
6 Troubleshooting 28
6.1 Fault indications / warning and fault list 28
6.2 Malfunctions during operation of the Nordmann SPA Display 28
7 Takingoutofservice/Disposal 29
7.1 Taking out of service 29
7.2 Disposal/Recycling 29
8 Technicaldata 30
9 Spareparts 31

4
1.1 Totheverybeginning
We thank you for having purchased the Nordmann SPA Display with touch-sensitive display.
The Nordmann SPA Display incorporates the latest technical advances and meets all recognized safety
standards. Nevertheless, improper use of the Nordmann SPA Display may result in danger to the user
or third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the Nordmann SPA Display, please observe and
comply with all information and safety instructions contained in the present installation and operation
manual.
If you have questions after reading this manual, please contact your Nordmann representative. They
will be glad to assist you.
1.2 Notesontheinstallationandoperationmanual
Limitation
The subject of this installation and operation manual is the external Nordmann SPA Display.
This installation and operation manual is restricted to the installation, commissioning, operation,
and trouble shooting of the Nordmann SPA Display and is meant for well trained personnel being
sufciently qualied for their respective work.
This installation and operation manual is supplemented by the installation manual and the operation
manual for the steam generator Nordmann Omega or the Condair Delta SPA Control Box, respectively.
Where necessary, appropriate cross-references are made to this publication in this installation and
operation manual.
Symbols used in this manual
CAUTION!
The catchword "CAUTION" designates notes in this installation and operation manual that, if neglected,
may cause damage and/or malfunction of the unit or other material assets.
WARNING!
The catchword "WARNING" used in conjunction with the general caution symbol designates safety
and danger notes in this installation and operation manual that, if neglected, may cause to injury to
persons.
DANGER!
The catchword "DANGER" used in conjunction with the general caution symbol designates safety and
danger notes in this installation and operation manual that, if neglected, may lead to severe injury
or even death of persons.
1 Introduction

5
Safekeeping
Please safeguard this installation and operation manual in a safe place, where it can be immediately
accessed. If the Nordmann Omega or the Condair Delta SPA Control Box with which the Nordmann SPA
Display is used changes hands, the documentation should be passed on to the new operator.
If the documentation gets mislaid, please contact your Nordmann representative.
Language versions
This installation and operation manual is available in various languages. Please contact your Nordmann
representative for information.

6
General
Every person working with the Nordmann SPA Display must have read and understood the present
installation and operation manual before carrying out any work.
Knowing and understanding the contents of the Installation and operation manual is a basic requirement
for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the
unit safely and correctly.
All ideograms, signs and markings applied to the Nordmann SPA Display must be observed and kept
in readable state.
Qualication of personnel
All actions described in the present Installation and operation manual (installation, operation, etc.) must
be carried out only by well trained and sufciently qualied personnel authorised by the owner.
For safety and warranty reasons any action beyond the scope of this manuals must be carried out only
by qualied technical personnel authorised by your Nordmann representative.
It is assumed that all persons working with the Nordmann SPA Display are familiar and comply with the
appropriate regulations on work safety and the prevention of accidents.
This unit may not be used by persons (including children) with reduced physical, sensory or mental
abilities or persons with lacking experience and/or knowledge, unless they are supervised by a person
responsible for their safety or they received instructions on how to operate the unit.
Children must be supervised to make sure that they do not play with unit.
Intended use
The Nordmann SPA Display is intended exclusively for the control of the steam generator Nord-
mann Omega and the Condair Delta SPA Control Box within the specied operating conditions
(see chapter8). Any other type of application without the express written consent of the manufacturer is
considered as not conforming with the intended purpose and may lead to the system becoming dangerous.
Operation of the equipment in the intended manner requires that all the information in these instruc-
tions are observed (in particular the safety instructions).
2 For your safety

7
Behavior in case of danger
If it is suspected that safe operation is no longer possible, then the Nordmann Omega or the Condair
Delta SPA Control Box, respectively should immediately be set out of operation, disconnected from
the mains and secured against accidental power-up (see Nordmann Omega or Condair Delta SPA
Control Box operation manual). This can be the case under the following circumstances:
– if the Nordmann SPA Display is damaged
– if the Nordmann SPA Display is no longer operating correctly
– if the connecting cable is damaged
All persons working with the Nordmann SPA Display must report any alterations to the unit that may
affect safety to the owner without delay.
Prohibited modications to the unit
No modications must be undertaken on the Nordmann SPA Display without the express written
consent of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts
available from your Nordmann representative.

8
Nordmann SPA Display
in-wall mounted
Nordmann SPA Display
on-wall mounted
5
8
7
2a
1
4
5
78
1
4
2b
Fig. 1: Front view Fig. 2: Front view
6
3
2a
7
3
6
2b
7
8
Fig. 3: Back view Fig. 4: Back view
3 Product Overview
1 Touch-sensitive display
2a In-wall mounted housing
2b On-wall mounted housing
3 Connecting terminals (CAN BUS)
4 Decorative cover
5Magnets for the attachment of the decora-
tive cover
6 Magnetic centring frame with sealing
7 Cable entries
8 Shielding clamps

9
4 Installation
4.1 Unpackingandcheckingthescopeofdelivery
Unpacking the unit
Open the packing and check the delivery for completeness. Please contact your Nordmann represen-
tative in case something is lacking, they will be glad to send you the missing part without delay. The
standard delivery includes:
– Nordmann SPA Display in-wall mounted
– Nordmann SPA Display control PCB
– In-wall mounted housing with pre-mounted display mounting supports, fastening claws and
3 magnets
– Plastic bag containing mounting material
– Nordmann SPA Display on-wall mounted
– Nordmann SPA Display control PCB
– On-wall mounted housing
– Plastic bag containing mounting material
– Decoration cover with pre-mounted centring frame and sealing (if ordered)
Please check the equipment for damage. Please report any damage to your Nordmann representative
and to the carriers, as required.
Packaging
The original packaging of the Nordmann SPA Display was designed for optimum safety during transpor-
tation. Please preserve the original packing material in case you once have to return the unit for some
reason.
In case you wish to dispose of the packaging, observe the local regulations on waste disposal. Never
dispose of the packaging to the environment.
4.2 Storingtheunit
If the Nordmann SPA Display must be stored, store it in a protected area (best in the original packaging)
meeting the following requirements:
– room temperature: 1 ... 40 °C
– room humidity: 10 ... 80 %rh (non condensing)

10
4.3 NotesonpositioningtheNordmannSPADisplays
Please observe the following notes for the correct positioning of the Nordmann SPA Display(s):
– The Nordmann SPA Display(s) must not be installed in hazardous locations and in rooms where
water splashes may occur.
– Do not mount the Nordmann SPA Display(s) inside the steam bath cabin, sauna, bio sauna, etc..
– If possible mount the Nordmann SPA Display(s) at eye level.
– Do not mount the Nordmann SPA Display(s) in exposed places.
– Do not mount the Nordmann SPA Display(s) on vibrating components.
– Place the Nordmann SPA Display(s) in such a way, that the total length of 50 m of the CAN BUS
cables with which the Nordmann Omega or the Condair Delta SPA Control Box and the Nordmann
SPA Display(s) are interconnected is not exceeded.
4.4 MountingtheNordmannSPADisplay
CAUTION!
The electronic components of the Nordmann SPA Display are very sensitive to electrostatic discharge.
For all installation work on equipment appropriate measures must be taken to protect these components
against damage caused by electrostatic discharge (ESD protection).
Note: the Nordmann Omega or the Condair Delta SPA Control Box, respectively and the Nordmann SPA
Display(s) (up to a max. of 8 SPA Displays) are interconnected via a so-called CAN BUS. Use only a
shielded four-wire cable with a cross section of 0.34 mm2per wire to establish the CAN BUS con-
nections. The total length of the CAN BUS must not exceed 50 m.

11
4.4.1 In-wallmounting
1. At the desired location, mark mounting opening according to the size of the in-wall mounted housing
with the help of a spirit level, then ream out the mounting opening.
Important: the mounting opening must be reamed out exactly since the decoration cover (broken
line in Fig. 5) overlaps the mounting opening on the right side only 4 mm, on the left side only 9 mm
and on the top and bottom side only 8.5 mm.
8.5 mm
141 mm
124 mm
87 mm
9 mm 4 mm
T
100 mm
8.5 mm
141 mm
124 mm
87 mm
9 mm 4 mm
T
100 mm
Cavity wall
Tmin: 15 mm
Massive wall
Tmin: 35 mm
Fig. 5: Making the mounting opening for the in-wall mounted housing
2. Knock out the desired cable entry of the in-wall mounted housing and insert the CAN BUS cable
(shielded four-wire cable, 0.34 mm2per wire) into the in-wall mounted housing. Then, lead the cable
through the wall opening to the steam generator or to the Condair Delta SPA Control Box.
Fig. 6: Inserting the CAN BUS cable

12
3. Insert the in-wall mounted housing into the wall opening, align it with the help of a spirit level, then x
it with the four fastening claws attached to the in-wall mounted housing (only necessary with cavity
walls).
Note: in massive walls the in-wall mounted housing must be xed either with the screws and dowels
supplied or by using PU mounting adhesive or mortar.
Fig. 7: Mounting the in-wall mounted housing to the wall opening
4. Free the shielding of the CAN BUS cable(s) by removing the insulation from the appropriate clamp-
ing position to the end of the cable. Remove the exposed shielding to about 2 cm, then x the end
of the remaining shielding with a piece of shrink tubing as shown in Fig. 8 and secure the exposed
shielding with the shielding clamp(s) to the housing.
Stripped-down shielding
shrinkable tubing
Cable wires
Fig. 8: Fix the CAN BUS cable(s) with exposed shielding to the housing with the shielding clamp(s)

13
5. Connect the supplied CAN BUS connecting plug to the CAN BUS cable from the Nordmann Omega,
Condair Delta SPA Control Box or from another Nordmann SPA Display as shown below. For this
purpose, strip the individual cable wires of the CAN BUS cable 6 mm, crimp the suitable wire end
ferrules and insert the cable wires as far as possible into the correct connection opening of the sup-
plied CAN BUS connecting plug. Then connect the CAN BUS connecting plug to the adapter cable
(ex factory connected to terminal "X3").
X3
JP1
1 4
L
H
24V
GND
L
H
24V
GND
L
H
24V
GND
X2
1 4
Attach cable end
ferrules and crimp
strip
6 mm
Conneting plug
Adapter cable
GND
24V
H
L
Fig. 9: Connecting one CAN BUS cable to the Nordmann SPA Display

14
A CAN BUS cable to another Nordmann SPA display is connected either directly or via another
adapter cable (available as an accessory) to the unused terminal "X2" (see notes in chapter 4.5).
Important: If two CAN BUS cables are connected to the Nordmann SPA Display board, jumper "JP1"
(terminator) on the Nordmann SPA Display must be removed.
X3
JP1
1 4
L
H
24V
GND
L
H
24V
GND
L
H
24V
GND
X2
1 4
L
H
24V
GND
Attach cable end
ferrules and crimp
strip
6 mm
Remove jumper "JP1" if two
CAN BUS cables are con-
nected.
Fig. 10: Connecting two CAN BUS cables to the Nordmann SPA Display

15
6. Connect the CAN BUS cable according to the specications in chapter 4.5 to the Nordmann Omega
or the Condair Delta SPA Control Box, then perform the function tests of the Nordmann Omega SPA
Display.
7. After function tests have been passed carefully place the Nordmann SPA Display onto the in-wall
mounted housing. Make sure the supply cable is not getting pinched. Then, x the Nordmann SPA
Display to corresponding supports of the in-wall mounted housing using the four screws supplied.
Magnete
Fig. 11: Mounting the Nordmann SPA Display

16
8. If necessary loosen the screws of the display supports and adjust the display.
Fig. 12: Adjusting the display
9. Finally attach the decoration cover (the decoration cover is held by the magnets in the in-wall mounted
housing), and seal the gap between the decoration cover and the wall splash-proof with silicone.
Fig. 13: Attaching and sealing the decoration cover

17
4.4.2 On-wallmounting
1. Using the aluminum on-wall mounted housing as template mark the two xing holes at the desired
location, with the help of a spirit level. Then proceed as follows:
– for the mounting on a stonework wall:
• Drill 2 holes ø6 mm, depth 35 mm.
– for the mounting on a wooden wall:
• Drill 2 holes ø3 mm, depth 35 mm
Note: If the mounting location does not permit bolt mounting (e.g. on a glass wall) the aluminum on-
wall mounted housing can also be glued over its entire surface to the underground.
If the CAN BUS cable is routed in-wall to the mounting point, an cavity of 40 mm x 80 mm (centered
on the drill holes) with a minimum depth of 30 mm must be provided for the shielding clamps.
In-wall cable routing On-wall cable routing
75 mm
Fig. 14: Drilling mounting holes and making cavity for in-wall cable routing

18
2. Free the shielding of the CAN BUS cable(s) (shielded four-wire cable, 0.34 mm2per wire) by removing
the insulation from the appropriate clamping position to the end of the cable. Remove the exposed
shielding to about 2 cm, then x the end of the remaining shielding with a piece of shrink tubing as
shown in Fig. 15 and secure the exposed shielding with the shielding clamp(s) to the housing.
In-wall cable routing On-wall cable routing
Stripped-down shielding
shrinkable tubing
Cable wires
Fig. 15: Fixing the exposed shielding of the CAN BUS cable(s) to the housing with the shielding
clamp(s)

19
3. Mount the on-wall mounted housing to the wall:
– for the mounting on a stonework wall:
• Insert the supplied dowels.
• Fix on-wall mounted housing to the wall using the screws supplied, align housing with the
help of a spirit level and fasten den screws.
– for the mounting on a wooden wall:
• Fix on-wall mounted housing to the wall using the countersunk screws supplied, align hous-
ing with the help of a spirit level and fasten den screws.
Fig. 16: Mounting the on-wall mounted housing (Figure shows attachment to masonry)

20
4. Connect the supplied CAN BUS connecting plug to the CAN BUS cable from the Nordmann Omega,
Condair Delta SPA Control Box or from another Nordmann SPA Display as shown below. For this
purpose, strip the individual cable wires of the CAN BUS cable 6 mm, crimp the suitable wire end
ferrules and insert the cable wires as far as possible into the correct connection opening of the sup-
plied CAN BUS connecting plug. Then connect the CAN BUS connecting plug to the adapter cable
(ex factory connected to terminal "X3").
X3
JP1
1 4
L
H
24V
GND
L
H
24V
GND
L
H
24V
GND
X2
1 4
Attach cable end
ferrules and crimp
strip
6 mm
Conneting plug
Adapter cable
GND
24V
H
L
Fig. 17: Connecting one CAN BUS cable to the Nordmann SPA Display
Table of contents
Popular Control Panel manuals by other brands

Honeywell
Honeywell HVC0001 owner's guide

Sky Laboratories
Sky Laboratories SPG 84 installation manual

RS Flight Systems
RS Flight Systems SCU Front Panel V2 Installation & operation manual

GST
GST GST301 Installation and operation manual

Mitsubishi Electric
Mitsubishi Electric PAC-YT34STA Instruction book

UltraLux
UltraLux SSW1Z instructions