NOVATEK-ELECTRO
REV-201М
REV-201M complies with requirements: IEC 60947-1:2004, ІDТ; ІEC 60947-6-2:1992, ІDT;
IEC 61000-4-2:2001, IDT; CISPR 11:2004, IDT
Pollutants in the amount, which is not to exceed the maximum permissible concentration are none
1.3.2 Front panel view and outer dimensions are shown on figure 1.
1.3.3 REV-201M operation algorithms.
-Energized (Turned ON) state of the REV-201M corresponds the closed position of the output terminals 1-2
(Channel 1) and 4-5 terminals (Channel 2). Thus the terminals 2-3 (Channel 1) and terminals 5-6 (Channel 2) are
open when the REV-201M turned ON.
-Deenergized (Turned OFF) state of the REV-201M is when terminals 1-2 (Channel 1) and terminals 4-5
(Channel 2) are open. And accordingly when the REV-201M is in OFF state –then terminals 2-3 (Channel 1)
and terminals 5-6 (Channel 2) are closed.
-Initialization time delay. After the power supply is given to the input terminals of the REV-201M with the initially
preset Zero time delay settings REV-201M turns ON not momentarily but within the time of approximately 250
milliseconds. This happens due to smooth voltage increase on the power supply source of REV-201M.
1.3.3.1 “Turn ON time delay”
Figure 2 –The working algorithm of relay “Turn ON time delay”
Timing countdown on each channel starts from the moment when the power supply source is applied to the
input terminals «L1-N»,(Channel 1); «L2-N», (Channel 2). Time delay setting is selected using the knobs of
potentiometers 3, 5, 10, 12 (figure 1). Each channel has two adjustable knobs: Т1and Т2. Time delay for the output
contacts triggering of is determined as the sum of the values adjusted by both knobs (T1 + T2) for each channel
separately.
When the power supply is present –GREEN LED starts glowing and timing countdown begins. After the expiry
of time delay interval –RED LED turns on and the output contacts change the position to the ON state.
1.3.3.2 “Impulse 1” operation mode
Figure 3 –The working algorithm of relay “Impulse 1”
Time counting on each of the channels starts from the moment the power is applied to the terminals «L1-N»,
(Channel 1); «L2-N», (Channel 2). Each channel has two adjustments T1 and T2.
When the power supply is given –on the channel GREEN LED starts glowing and countdown begins. Time
delay intervals are adjusted using the knobs 5and 10 (Figure 1.) in the diapason T2 for the Channel 1 and Channel
2 respectively –pause time.
After the turn ON time delay expiry REV-201M turns ON for the time determined by the knobs 3and 12 (Figure
1) in the diapason T1 –LED indicator change the color to RED.
When the Turn ON time interval comes to an end REV-201M turns OFF the load and REV-201M switches to the
idle mode. LED color indicator changes to GREEN. A relay working cycle is restarted after recurrent de-energizing
and reenergizing the voltage supply.