NOVO 485HE User manual

Canada
855 Park St.
Unit 1
Regina, SK S4N 6M1
490 Pinebush Rd.
Unit 1
Cambridge, ON N1T 0A5
56 Lightcap Rd.
Pottstown, PA 19464
U.S.A.
9760 Mayower Park Drive,
Suite 110
Carmel, IN 46032
4645 McDowell Rd. W
Suite 106
Phoenix, AZ 85035
Service Manual
485HE
Upow & Downow Softener Manual
1. Avoid pinched o-rings during installation by applying IAPMO certied lubricant to all seals (provided with install kit).
2. This system is not intended for treating water that is microbiologically unsafe or of unknown quality without
adequate disinfection before or after the system.

Table of Contents

Table of Contents
TROUBLE SHOOTING GUIDE 4
EFFICIENCY STATEMENT 5
AUTOMATIC RESIN CLEANER SOLUTION FEEDER
INSTALLATION INSTRUCTIONS (OPTIONAL) 6
PROBLEM WATER INJECTOR KIT 7
REPLACEMENT/SERVICE
TIMER REMOVAL 8
INSPECTION AND REPLACEMENT OF PISTON ASSEMBLY AND SEAL AND SPACER KIT 8
REPLACING THE BYPASS AND METER CABLE 9
REPLACE METER ASSEMBLY 10
REPLACE MOTOR 10
CLEAN INJECTOR ASSEMBLY 11
REPLACE DRAIN LINE FLOW CONTROL 11
REPLACE BRINE LINE FLOW CONTROL 11
REPLACING PCBS 12
DISPLAY REPLACEMENT 12
AFTER SERVICING 12
PARTS BREAKDOWN 13
PARTS
PARTS BOX & BRINE TANK ASSEMBLY 14
POWERHEAD 15
VALVE BODY 16
BYPASS 17
CABINET 18
LEVEL 2 PROGRAMMING (OPTIONAL SETTINGS) 19
MASTER PROGRAMMING 20

4
Problem Possible Solutions
LEVEL 1 -- SEE HOME OWNERS MANUAL
Recommended for the home owner
** IMPORTANT **
before attempting any trouble shooting be sure to test the water or have the water tested.
The tests should include the raw water, the hot treated water, and the cold treated water.
Delivers untreated water
Bypass is closed bypassing raw water past the unit - Return bypass valve to the open position to service
the home - See ‘Manual Water Bypass’
Bypass loop in the homes plumbing - Close outlet valve only on conditioner bypass, open nearest
conditioned water line. If no water ow then there is not a bypass in the plumbing. If there is water ow
then there is a hidden bypass in the plumbing (contact plumber).
No salt or low salt level - Fill salt to above the water level in the salt tank. Low salt will aect the
conditioners capacity. - See ‘Maintenance’
Not programmed correctly for current application -Verify programming. Correct hardness level and
amount of people in the home if necessary. - See‘Start Up and Programming’
Excessive water in the salt tank Refer to Maintenance, Cleaning the Injectors and Cleaning the Salt Tank
Not regenerating automatically, not metering water ow
Check diagnostics for last regeneration - See How Your Conditioner Works
Open nearest conditioned water outlet and check if gallons is counting down, if not metering -
Contact authorized service representative
Not using salt Injectors or injector screen plugged. Clean and or replace injectors and screen - See ‘Maintenance’
Salt Bridged in salt tank - See ‘Maintenance’
Not regenerating automatically - Alarms Caused by a power outage or brown out during regeneration – unplug power for 30 seconds then
re-connect. If alarm continues - Contact your authorized service representative, if necessary.
Unit regenerates but does not use salt
Clean and or replace injectors - See ‘Maintenance’
Drain line ow control is plugged – clean drain line ow control to ensure there are no kinks, or
restrictions in the drain line.
Using too much salt or more salt than expected Check programming – is the unit set properly for salt eciency, is the programming correct for
hardness and people - See ‘Start Up and Programming’
Alarms after regeneration
Caused by a power outage or brown out during regeneration – unplug power for 30 seconds then
reconnect if alarm continues - Contact your authorized service representative, if necessary.
Corroded or damaged rear circuit – replace circuit Contact your authorized service
representative, if necessary.
Discolored water
Result of city / town supply being contaminated – check with local authority to see if there has
been water main activity in your area. If there has been, manually regenerate the unit a couple of times
in a row to clear the color. If there hasn’t been, Contact your authorized service representative if
necessary.
Iron Bleed through – if there are small amounts of iron in your raw water supply eventually it will
build up in the resin and could result in bleed through.
– review settings to compensate for iron in the water - See ‘Start Up and Programming’
- Contact your dealer or local plumbing supply store to obtain an approved resin cleaner. Use resin
cleaner to clean the resin as directed. For permanent maintenance if required add in an automatic
feeder - See Automatic Resin Cleaner Solution Feeder
Excessive pressure loss Check unit specications - peak or continuous service ow rates maybe exceeding capacity causing
the unit to be restrictive due to size - See‘Unit Specications’ - Contact your dealer if necessary.
TROUBLE SHOOTING GUIDE

4 5
Problem Possible Solutions
LEVEL 2 –
recommended for qualied service
technician only
Not drawing brine solution
Injectors or injector screen plugged. Clean and or replace injectors and screen - See Replacement/
Service Section
Drain line ow control plugged or drain line restricted - See Replacement/Service Section
Safety oat assembly seating prematurely – clean or replace safety oat and clean brine tank - See
Parts Section
Loose connections between control valve and safety oat allowing unit to draw air - See
Replacement/Service Section
No water in salt tank
Loose connections between control valve and safety oat allowing unit to draw air -
See Replacement/Service Section
Rell time not set correctly for unit size; water not coming above the grid plate.
Rell control button plugged causing no rell – clean and or replace rell control button.
Problem Possible Solutions
** Not regenerating automatically Alarms **
Jammed piston - replace piston and seal assembly - See Replacement/Service Section
Defective or damaged circuit - replace circuit See Replacement/Service Section
Loose or corroded connections between the 2 circuits – reconnect securely or replace - See
Replacement/Service Section
Conditioner initiates regeneration but alarms after
a few seconds
Drive motor defective replace motor - See Replacement/Service Section
Defective transformer replace transformer.
Internal valve leak - Running to the drain constantly Replace piston and seal assemblies - See Replacement/Service Section
Not drawing brine no problem with injectors or drain
**Meter not counting down **
Check diagnostics for last regeneration .
Check that meter cable is plugged into the meter assembly - See Replacement/Service Section
Check that meter cable is reading the meter by moving a fridge magnet (or similar magnet) across it
rapidly for a few seconds you should be able to see the gallons change.
Be sure there is no debris caught in the the turbine
If the meter cable is good, and no debris caught then replace the meter assembly - See
Replacement/Service Section
Leaking past distributor tube Contact Technical services for additional trouble shooting information: 877-288-9888
Alarms after regeneration or after manual regeneration
Damaged or missing sensor magnet on brine gear – replace as required, or send in for repair to
nearest oce.
Corroded or damaged rear circuit – replace as required.
Excessive pressure loss
Check unit specications - peak or continuous service ow rates may be exceeding capacity caus-
ing the unit to be restrictive due to size - See product specic information on warranty sheets
suplied with the unit. Contact Customer Service for clarication if this is suspected – 877-288-9888.
Upper distributor cone plugged with foreign material – remove valve, remove upper distributor
cone and clean then replace and put valve back on unit.
Chlorine degradation of resin – excessive amounts of chlorine or chloramine can damage soften-
ing resin and break it down causing excessive pressure loss – replace media bed and add in chlorine
removal system to protect softener.
TROUBLE SHOOTING GUIDE

6
5/8" hole in brine
well cap
Res-up feeder
1/4” Holes
Res-Up Feeder Bottle (Chemical sold Separately)
The 12 cc feeder (Part # 33010) is for conditioners up to 64,000 grains (2 ft3 of
resin).
The 30 cc feeder (Part # 33018) is for larger conditioners over 64,000 grains.
Pro-Res Care Chemicals
Item #45147 Pro-ResCare - Gallon
Item #45148 Pro-ResCare - Quart
Resin Cleaner
An approved resin cleaner MUST be used on a regular basis if your water supply contains iron.The amount of resin cleaner and
frequency of use is determined by the quantity of iron in your water (consult your local representative or follow the directions on
the resin cleaner package).
Res-Up Feeders attach to your brine tank and automatically dispense the Res-Up cleaner into the brine solution where it cleans the
resin during the regeneration cycle.
The feeder hooks onto the tube inside your brine tank and you just pour some chemical in it and your water conditioner should last
signicanly longer. A res-up feeder is essential if your raw water contains measurable amounts of iron.
1. Install the grid and brine well inside
the tank.
3. Mark the location of the holder and
drill.
2. Measure 2 inches from the top of the
tank beside the oblong molding.
Install Res-Up Feeder
4. IInstall the holder and the Res Care
Solution
5. Take o the small hole cover on the
Brine Well lid.
6. Take o the cover of the Res Care
bottle . Insert the wick, making sure it
touches the bottom of the bottle.
Insert the other end of the tube
completely into the hole in the brine
well cap. Automatic feeding will start
in a few hours.
AUTOMATIC RESIN CLEANER SOLUTION FEEDER
INSTALLATION INSTRUCTIONS (OPTIONAL)

6 7
6(77,1*6 83 '2:1
0$18$/
5(*(1
PRESS SETTINGS KEY
3 SEC TO UNLOCK
1. The display will read “PRESS SETTINGS
KEY 3 SEC TO UNLOCK”.
2. After 3 seconds, the display will beep
confirming unlock.
6(77,1*6 83 '2:1
0$18$/
5(*(1
CODE: 100
3. Press & hold DOWN .
4. Enter code 100 using UP . Press
MANUAL REGEN three times to accept
code.
6(77,1*6 83 '2:1
0$18$/
5(*(1
IRON & MN
2100 GRAINS
5. Press MANUAL REGEN to advance past
IRON & MN LBS to IRON & MN GRAINS.
6. Press DOWN to change 2500 to
2100. Press MANUAL REGEN until past
PROGRAMMING COMPLETE.
6(77,1*6 83 '2:1
0$18$/
5(*(1
WATER SOURCE
MUNICIPAL
8. For problem water set to
WELL/OTHER
6(77,1*6 83 '2:1
0$18$/
5(*(1
WATER SOURCE
WELL/OTHER
9. Now press UP or DOWN
to change WATER SOURCE value For
problem water set to WELL/OTHER
6(77,1*6 83 '2:1
0$18$/
5(*(1
SALT SETTING
IRON & MN
7. Now press UP or DOWN
to change SALT SETTING value For
problem water set to IRON & MN
Injectors
Injector Conguration Upow
Red Plug
Size Ft3Color
75 #1 WHITE
100 #1 WHITE
150 #1 WHITE
200 #2 BLUE
250 #2 BLUE
300 #3 YELLOW
IMPORTANT
The injector cage must be lined
up and inserted properly to
avoid crushing when the
injector cap is re-installed.
Markings on the cage and
valve body must line up.
PROBLEM WATER INJECTOR KIT
IMPORTANT!: If the water source this water softener is being applied on is not municipal water and contains up to 1.5 mg/l/ppm of ferrous (Clear Water) iron and/or up to
.75 mg/l/ppm of manganese, the enclosed Problem Water Injector Kit #60010382 needs to be installed into the control valve following these instructions. You will need
to make 3 programing changes. In the main user settings: 1. Salt Setting set to Iron/MN. 2. Water Source set to Well/Other. 3. Iron & MN capacity requires additional
adjustments see instructions below. FAILURE TO DO THIS WILL RESULT IN UNSATISFACTORY OPERATION OF THIS EQUIPMENT AND VOID ANY IMPLIED
PERFORMANCE WARRANTY.
CAUTION!
DO NOT over tighten
injectors. Snug tight only.
85HE Valve
Replace injectors with correct number and color corresponding
to your equipment size.
*NOTE: Remember to properly lubricate ALL O Rings with
Silicone Lubricant - supplied.
Programming Change Required
Change the iron/MN capacity settings in the second level
programming from 2,500 grains per pound of salt to 2,100
grains per pound of salt.
IMPORTANT
This change is necessary to
compensate for the injector
conversion

8
1. Follow steps 1 to 3 ofTimer Removal above.
2. Remove three screws from the plate on the
valve body.
3. Remove the plate from the valve body and pull the
Piston Assembly from the valve. The brine valve
assembly can also be removed in this stage.
4. Remove the seal spacer assembly, grease it
with silicone lubricant (# 92360).
5. Re-install in this order: seal and spacer assembly,
piston assemby, brine valve assembly, and then the
timer assembly.
Remove 3 X
Screws Plate
Seal #13242-02
Spacer #14241
Brine Valve
Assembly
#60032
Piston Assembly:
- Upflow - #60010129
- Downflow - #60010171
1. 2.
2. 3. 4.
3.
TIMER REMOVAL
INSPECTION AND REPLACEMENT OF PISTON ASSEMBLY AND
SEAL AND SPACER KIT
CAUTION!
DO NOT use petroleum
based grease products.
1. Remove screw & washer from piston rod link
2. Remove 2 bolts securing powerhead to body
3. Remove powerhead from body
THE FOLLOWING ‘REPLACEMENT / SERVICE SECTION’, PAGES 8 TO 12 CONTAIN CONTENT
THAT SHOULD ONLY BE USED BY A QUALIFIED SERVICE TECHNICIAN:
REPLACEMENT/SERVICE

8 9
Step 1 Step 2*
Unplug the
power from the
wall socket.
Remove 2 screws and
clips from bypass.
Disconnect the
meter cable from
the bypass.
Grey Meter Cable
60010267
Step 3
Remove Cover.
Step 4 Step 5
Step 6 Step 7
Disconnect
the cables
from the
front PCB
display.
Disconnect
the cables
from the rear
PCB display.
Remove
strain relief
with pliers.
Replace the
old cable
with the
new Cable.
60095101 Bypass comes with Meter
and Grey Meter Cable
*NOTE
Water to the household
needs to be turned off
and pressure relieved
before Step 2
Cut the tie
that fastens
the wires
Remove
the meter
cable
attached
on Main
PCB.
If valve is manufactured before March 20th, 2018, and customer wishes to replace or service impeller on bypass. Customer can order item #60010238.
If customer wishes to replace to new design, then follow the steps below.
Valve Model Region Meter Ratio
OLD NEW
85HE Series U.S Gallon 8.000 5.680
REPLACING THE BYPASS AND METER CABLE

10
1. 2. 3.
Motor
Screws Motor #92393
3.
Meter Cable
1. Disconnect the meter cable from the meter.
2. Disconnect the valve from bypass by removing clips
3. Remove the coupling adapter from the bypass
1. 2.
MOTOR REPLACMENT
1. Remove the powerhead cover and disconnect the LCD cable from the circuit board
2. Remove the motor screws
3. Pull the motor out from powerhead
METER ASSEMBLY REPLACMENT

10 11
Clip
Brine Line Elbow
Clip
Drain Line Elbow
Drain washer
3. 4.
DRAIN LINE FLOW CONTROL REPLACMENT
BRINE LINE FLOW CONTROL REPLACMENT
1. Pull the drain line clip and remove the drain line elbow
and washer
2. Clean/replace drain line washer
NOTE
Be sure to shut off any
bypass line.
1. 2.
CLEAN INJECTOR ASSEMBLY
1. Remove four screws of the injector cap.
2. Pull the Injector Cap Out
3. Remove the injector assembly, oring and screen,
4. Clean the injectors then replace screen (if necessary)
and re-install end cap assembly and screws
Groove
Plug Injectors
Prominence
PLEASE NOTE: Make sure the two prominences
on the injector are aligned to the grooves
on the valve body.

12
Remove PCBs by removing the
screws shown in the picture
Remove Display
by removing the
screws shown in
the picture
PCB REPLACMENT
AFTER SERVICING
1.Reconnect drain line
2. Return bypass or inlet valve to normal in service position. Water pressure will automatically build in the
conditioner.
3. Check for leaks at all sealed areas. Check drain seal with the control in the backwash position.
4. Plug electrical cord into outlet
5. Set ‘Time of Day ‘and cycle the control valve manually to ensure proper function. Make sure control valve is
returned to the ‘In Service’ position.
DISPLAY REPLACEMENT
NOTE
Be sure to shut off any
bypass line.

12 13
Control Valve - 10010060
Bypass - 60095101
6(77,1*683 '2:1
0$18$/
5(*(1
Upper Cone
-18280
Distributor
Model Mineral Tank
Size
Tank # Distributor# Valve # Media Bed # Brine Tank
Softener Upow (Single Tank)
75 8 x 44 25020051 50010019
10010060
95600 30020006
100 9 x 48 25020052 50010006 95601 30020006
150 10 x 54 25020053 50010005 95606 30020006
200 12 x 52 25010058 50010005 95609 30020010
250 13 x 54 25010064 50010010 95610 30020010
300 14 x 65 25030001 and 50040039 50010010 95604 30020032
75C 9 x 35 25010028 50010020 95600 N/A
100C 10 x 35 25010043 50010020 95601 N/A
PARTS BREAKDOWN

14
PARTS BREAKDOWN
Brine Tank
(Round or
Square)
Brine Tank
Tubing
**Brine Well/
Safety Float
Brine Tank Lid
*Grid (Round or Square)
Grid Legs (3 for
Round and 4 for
Square)
Brine Tank Assembly (Round Brine Tank Shown))
*GRID
55010013 - For BTR 100
55010036 - For BTR145
55010037 - For BTR 200
**FLOAT ASSY
55010023 - BTR100
55010054 - BTR145
55010033 - BTR200
60010181 - Tube Stiffener 3/8” PLASTIC
TUBE INSERT
,03257$17
3/($6((1685(7+($77$&+('
78%(67,))(1(5,6,16(57('
,1727+(%5,1(/,1(%()25(
7,*+7(1,1*
7+(187
18280
Upper Basket
Parts Box
60090003
2X 1” Straight
Adapter
60010006
Bypass Tool
60010026
O Rings Attached
60090010
2 X 3/4”
Elbow
Adapter)
60010052
Transformer
92360
Grease
Packet

14 15
Power head parts list
No. Part # Description Qty
23 60010331 Power Cable Clip 1
22 60010330 Meter Cable Clip 1
21 60010124 Power Cable 1
20 60010240 Display-PCB cable 1
19 60010115 Meter Cable 1
18 80080164 485HE Face Label 1
17 60095662 Bnt485 Display Plate(White) 1
16 60010309 Bnt485 Housing(White) 1
15 60010180 Bnt85HE Display (Before Aug.15, 2019) 1
60021979 Bnt85HE Display (After Aug.15, 2019)
14 92393 Bnt85 Motor 1
13 60095658 Motor Pin 1
12 60010673 Screw-ST2.9×10 8
11
60010179 Main Pcb, (DF) (Before Aug. 15, 2019)
1
60021982 Main Pcb, (DF) (After Aug. 15, 2019)
60010178 Main Pcb, (UF) (Before Aug. 15, 2019)
60021981 Main Pcb, (UF) (After Aug. 15, 2019)
10 60010574 Screw-ST3.5x13 10
960010573 Bnt85HE Mounting Plate 1
860010575 Screw-4.2×12 1
460095102 Gear, Brine, 85HE(UF) 1
60095103 Gear, Brine, 85HE(DF)
392391 Main Gear, 85HE 1
2 92389 Bnt85 Drive Gear 1
1 60095077 Bnt485 Base(White) 1
60010371 Complete Powerhead,485UF
60010372 Complete Powerhead,485DF
Drive Gear
Main Gear
Indent Brine Gear
Notch
Main Gear Brine Gear
Correct alignment for Up Flow Gears
Drive Gear Main Gear Brine Gear
Main Gear
NotchBrine Gear
Indent
Correct alignment for Down Flow Gears
Upflow Gear Alignment
Downflow Gear Alignment
PARTS BREAKDOWN

16 Item #s For All
Injector Assemblies
and Brine Line and
Drain Line Washers:
Part # Part Description
60010110 BLFC BUTTON #2 0.3GPM A32
60010082*BLFC BUTTON #2 0.7GPM A32
60010128 BLFC BUTTON 0.2GPM
60010601
60010602
INJECTOR SET #0000 BLACK THROAT
NOZZLE #0000 BLACK THROAT
60010603
60010604
INJECTOR SET #000 GREYTHROAT
NOZZLE #000 GREY THROAT
60010605
60010606
INJECTOR SET #00 VIOLET THROAT
NOZZLE #00 VIOLET THROAT
60010607
60010608
INJECTOR SET #0 REDTHROAT
NOZZLE #0 RED THROAT
60010609*
60010610*
INJECTOR SET #1 WHITE THROAT
NOZZLE #1 WHITE THROAT
60010611
60010612
INJECTOR SET #2 BLUETHROAT
NOZZLE #2 BLUETHROAT
A47
A28 and A30
* Default
Injector
Assemblies
600101276001012660010032 60010033 60010034 60010035
Part # Part Description
60010613
60010614
INJECTOR SET #3 YELLOW THROAT
NOZZLE #3 YELLOW THROAT
60010685
60010686
INJECTOR SET #4 GREENTHROAT
NOZZLE #4 GREEN THROAT
60010131 DLFC #1 1.5GPM
60010132 DLFC #2 2.0GPM
60010133 DLFC #3 2.4GPM
60010135 DLFC #5 3.5GPM
60010041 DLFC #6 4GPM
60010169 DLFC #7 5GPM
60010136 DLFC #A 5.0GPM
60010137 DLFC #B 7.0GPM
60010138 DLFC #C 11.0GPM
A28 and A30
A15
Injector
Assemblies
6001003160010686
Valve Body Parts List
No. Part # Description Qty
A01 60010075 Screw-M5x12(Hexagon) 3
A02 60010076 Screw-M5x16(Hexagon With Washer) 2
A03 60010645 End Plug Retainer 1
A04 60095056 BNT85HE Rod 1
A05 60010647 Piston Pin 1
A06
60010344
BNT85HE Quad Ring Plug Cover 1
A07 Quad Ring 2
A08 BNT85HE End Plug 1
A09 60095058 BNT85HE Piston Retainer 1
A10 60095075(UF)
60095059(DF)
BNT85HE Piston(Up ow and Downow) 1
A11 13242-02 Seal 5
A12 14241 Spacer 8
A13 60010229 Drain Fitting-B 1
A14 60095060 BNT85HE Spacer 1
A15 60010657? DLFC 3.0GPM? 1
A16 60010069 Secure Clip-s 2
A17 60095061 BNT85HE Valve Body 1
A18 60010596 Screw-M5x12(Hexagon With Washer) 5
A19 60095063 BNT85 End Cover 1
A20 60095614 O-Ring-¢30×2.65 1
A21 60010077 O-Ring-¢78.74×5.33 1
A22 60010080 O-Ring-¢25×3.55 1
A23 60010599 Valve Bottom Connector 1
A24 60010099 Screw-ST2.9X13(Large Washer) 2
A25 60010190 O-Ring-¢32×3 1
A26 60010189 O-Ring-¢18×3 1
A27 60010174 BNT85HE Injector Fixed Sleeve 1
A29 60010175 Injector Plug Body 1
A31 10227 Injector Screen 1
A32 60095076 Injector Plug 1
A33 60010193 BNT85HE Injector Cover Body 1
A34 60010195 O-Ring-¢40×2.65 1
A35 60010194 BNT85HE Injector Cover Cap 1
A36 60010196 Screw-M5×25(Hexagon with Washer) 4
A37
60032
Seal Mat 1
A38 O-Ring-¢12×2 3
A39 Injector Stem 1
A40 Injector Spacer 1
A41 O-Ring-¢12.5×1.8 1
A42 Injector Cap 1
A43 Injector Screen 1
A44 Spacer Washer 1
A45 Retaining Ring 1
A46 60010173 BNT85HE BLFC Fixed Sleeve 2
A47 BLFC(optional) 1
A48 60010188 O-Ring-¢8×1 1
A49 60010172 BNT85HE Brine Line Elbow 1
A50 60010186 O-Ring-¢12.5×1.5 2
A51 60010187 O-Ring-¢8×1.5 2
A52 60010191 Ball, Seal
Upow Piston
Assembly
60010129
Downow Piston
Assembly
60010171
Brine Valve
Injector Stem
Assembly
60032
Injectors
Injector Conguration Upow
Red Plug Injectors
Injector Conguration Downow
Plug
A11
A12 A13 A14 A15 A16
A17
A20
A24
A25
A26
A27
A28
A29
A30
A31
A32
A34
A35
A36
A33
A23 A22 A21
A19 A18
A49
A41
A48
A47
A46
A51
A50 A52
A16
A38
A01 A02 A03 A04 A05
A06 A07 A08
A09
A10*
A37
A39
A41
A42
A45
A38
A40
A07
A43
A44
Figure 1 Figure 2
See Figure 1/2
PARTS BREAKDOWN

PARTS BREAKDOWN
16 17
Bypass Parts List
No. Part #
(Water Group)
Part #
(Canature)
Description Qty
1 60010025 21709003N Secure Clip Inlet and Oulet 2
260010023 21319036N Elbow 3/4”NPT Inlet and Oulet 2
360010019 21319011N Straight 1”NPT Inlet and Oulet 2
460010026 26010143 O-ring on Inlet and Outlet 2
592846 05056155N Plug Clip 2
6 60095090 21709004B Shaft Clip 2
760010209 05056146 Bypass Plug 2
860010044 05056134 O-ring on Plug 2
960010006 70020007 Bypass Tool 1
10 05056212 063 Bypass Body 1
11 60010701 13000327 Screw on SS Clip 2
12 60010046 05056044B SS Clip 2
13 60010561 26010046 Big O-ring on Connector(Outlet) 1
14 60010101 05010083N Valve-Bypass Connector(Outlet) 1
15 60010079 05056025M Valve-Bypass Connector(Inlet) 1
16 60010562 05056129 Small O-ring on Connector(Outlet) 3
60095101
Part # Part Description
60010613
60010614
INJECTOR SET #3 YELLOW THROAT
NOZZLE #3 YELLOW THROAT
60010685
60010686
INJECTOR SET #4 GREENTHROAT
NOZZLE #4 GREEN THROAT
60010131 DLFC #1 1.5GPM
60010132 DLFC #2 2.0GPM
60010133 DLFC #3 2.4GPM
60010135 DLFC #5 3.5GPM
60010041 DLFC #6 4GPM
60010169 DLFC #7 5GPM
60010136 DLFC #A 5.0GPM
60010137 DLFC #B 7.0GPM
60010138 DLFC #C 11.0GPM

18
Cabinet Parts List
No. Part # Description Qty
22 55010023 0435 Brine Valve Assembly 1
21 55010010 0435 Brine Well 1
20 55020002 4" Brine Well Cap 1
19 Plastic Screw M8×20 1
18 Hoop Clinch 1
17 60010362 4" Brine Well Clamp 1
16 85010132 Salt Lid(CS5) 1
15 High Cover(CS5) 1
14 80080015 Control Plate Label 1
13 80080021 Control Plate(CS5) 1
12 60010180 85HE Display Board 1
11 Transparent Back Cover 1
No. Part # Description Qty
10 Screw 2.9×6.5 10
9 302171 Drain Line Clamp 1
8 60095097-1 Canature BypassValve C/W Meter 1
7 10010061 Control Valve Assembly(CS5) 1
6 18280 Top Cone 1
5 50010020 D-Tube(35“) 1
425020019 935 Pressure Tank 0935(Without base) 1
25020020 1035 Pressure Tank 1035(Without base)
3Pressure Tank Protection 9" 2
Pressure Tank Protection 10”
225020019 TANK ASSY CS5H-1035 1
25020020 TANK ASSY CS5H-1035
150010011 9“ Tank Base 1
50010013 10“ Tank Base
A B
0844 49.98” 8”
0948 53.98” 9”
1054 59.98” 10”
1252 57.98” 12”
1354 59.98” 13”
1465 70.98” 14”
75C 100C
A 43.31” 43.31”
B 16.54” 16.54”
I
1
2
3
4
3
5
6
7
8
9
10 11 10 12 13 14
15
16
17
18
19
20
21
22
PARTS BREAKDOWN

18 19
6(77,1*6 83 '2:1
0$18$/
5(*(1 6(77,1*6 83 '2:1
0$18$/
5(*(1
PRESS MENU KEY
3 SEC TO UNLOCK
SYSTEM LANGUAGE
ENGLISH
The display will read Press
SETTINGS for 3 sec to
unlock”. After 3 seconds, the
display will beep confirming
unlock
Press and hold together
for three seconds to enter Level
Two Master Programming
NOTE
Under normal use there
is no need to change the
settings under level 2
programming. You can,
however, change the
default settings if
required.
CAUTION: DO NOT CHANGE LEVEL 2 SETTINGS WITHOUT CONSULTING A
CANATURE WATERGROUP TECHNICIAN (1-877-288-9888). Incorrectly
changing the settings can result in malfunction of the unit.
When the Level 2 Master Programming Mode is entered, all available option setting displays may be
viewed and set as needed. Depending on current option settings, some parameters cannot be viewed or set.
To change any setting under level 2 programming:
- Press the MANUAL REGEN key button and the value flashes
- Press the UP or DOWN keys to change the value
- Press the MANUAL REGEN again to accept value
- Press the DOWN key to advance to the next value
LEVEL 2 PROGRAMMING (OPTIONAL SETTINGS):

20
6(77,1*683 '2:1
0$18$/
5(*(1
Main Valve Settings
Meter Ratio METER RATIO AFTER MAR 20,2018 - 5.68
METER RATIO BEFORE MAR 20,2018 - 8.00
Service Delay 3.0
Backwash Delay 7.0
Brine Delay 4.0
Rinse Delay 5.0
Rell Delay 4.0
VALVE MODE
Softener UF
BACKWASH
4 Minutes
BRINE
90 Minutes
UNIT SIZE
1.00 CF RINSE
7 Minutes
PROGRAMMING
COMPLETE
Press SET/Regen Key Press SET/Regen Key
MASTER PROGRAMMING
Press Up and Down Buttons together for 5 seconds
Press MANUAL REGEN Button and and change value using Up and Down Buttons
Key Pad Setting
SETTINGS This function is to enter the basic set-up information required at the
time of installation.
MANUAL This function is to initiate an immediate or delayed manual
REGEN regeneration.
DOWN / Increase or decrease the value of the settings while in the
UP programming mode.
SOFTENER UPFLOW (UF)
This mode is for the operation of an up ow regenerating softener. The amount of salt
used each regeneration is proportional to the capacity remaining in the system. A preset
amount of brine (Default is 70%) is prepared after a normal regeneration. Just before a
regeneration is scheduled, fresh water is added to the brine tank to“top o”the already
prepared 70% of brine. The total amount of brine used to regenerate the system is
proportional to the capacity remaining.
I.e. If the system has 10% capacity remaining, then only 90% of the salt dosage is
needed to restore capacity to 100%. 70% of the brine is already prepared (and fully
saturated) so 20% is added so that the total of 90% is prepared.
When a standard regeneration is started, the valve will move rst to the rell position
to add water to the brine tank. The amount of water added is equal to the calculated
rell time for the salt dosage X BrineTank Rell%.The valve then will return to service
for the amount of Brine MakeTime.When this is com-plete the valve will move to the
Brine position.
The regeneration sequence is 1. BRINE MAKE (REFILL), 2. BRINE, 3. BACKWASH, 4 RINSE,
5. RE-FILL.
LANGUAGE
Current available language is English.
UNITS
Current unit of measure is gallons. Metric units may become available at a later date.
EFFICIENCY & CAPACITY SETTINGS
There are 3 settings to choose in Settings. High Eciency, Standard Capacity, and Iron &
Manganese.The values for these settings are set in the Factory Options and are used to
calculate the system capacity and rell time.
REFILL
This value should match the BLFC ow washer. It is used to calculate the rell time.
BRINE MAKE TIME
This value is the time allowed for the salt to dissolve in the water to create the brine
solution. The value is the amount of time ahead of the scheduled regeneration time that
the water will be added to“top o”the brine already prepared in the brine tank.
BRINE PRE-FILL%
This is the percentage of the water that will be added to the brine tank after a regener-
ation.The default is 70%. The remaining amount of water will be added just prior to the
regeneration and will be proportional to the amount of capacity left in the system.
DAILY RESERVE
This value is used to calculate the reserve capacity. Reserve Capacity = No. People x DAILY
RESERVE.
DAY OVERIDE
This setting can be used to add number of days to over ride the meter. As an example if the
setting is 5, the system will regenerate after 5 days even if there is still gallons capacity
remaining. OFF will cancel this feature.
RINSE OVERIDE
This setting can be used to skip the RINSE cycle. As an example if the setting is 10, the
system will skip 10 rinse. OFF will cancel this feature.
BW OVERIDE
This setting can be used to skip the back wash cycle. As an example if the setting is 10, the
system will skip 10 back wash cycles. The setting will only work if the WATER TYPE is set to
CITY for clean water applications.
FORCED REGEN
When set to ON, the system will start a forced regeneration when the remaining capacity
reaches 3%.The regeneration consists of 8 minutes of Brine and 12 minutes of Rinse.
The 20 minutes regeneration will restore up to 33% of the system capacity. At the next
regeneration time (2:00 AM), the system will automat-ically perform a standard regenera-
tion to restore ca-pacity to 100%.
VACATION MODE
When set to ON, the system will perform a 10 minute back wash and 10 minute rinse if
there is no water ow detected after 7 days.The regeneration will occur at the scheduled
REGEN TIME.
Other manuals for 485HE
1
Table of contents
Other NOVO Water Dispenser manuals
Popular Water Dispenser manuals by other brands

Clack
Clack WS1 Series Installation, operation & maintenance manual

Clack
Clack WS1 Series Installation, operation & maintenance manual

tomado
tomado Superior TWD7525B instruction manual

HEMWAY
HEMWAY W616 instructions

MERQUIP
MERQUIP NIAGARA SL 65 IB AC Installation, use and maintenance handbook

Pentair
Pentair FLECK 5600SXT Service manual

Cosmetal
Cosmetal Jclass 30 Installation, use and maintenance handbook

BWT
BWT WS355 Fitting and operating instructions

AFWFilters
AFWFilters 5600 Series installation instructions

Kenmore
Kenmore 625.384200 Use & care guide

Kenmore
Kenmore 625.348571 manual

WaterGroup
WaterGroup Econoflo ECS20 Installation and maintenance instruction manual