manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Oliver IGD
  6. •
  7. Control Panel
  8. •
  9. Oliver IGD TOCSIN 700+ Guide

Oliver IGD TOCSIN 700+ Guide

Other Oliver IGD Control Panel manuals

Oliver IGD Tocsin 920 Series Installation guide

Oliver IGD

Oliver IGD Tocsin 920 Series Installation guide

Oliver IGD TOCSIN 700 Guide

Oliver IGD

Oliver IGD TOCSIN 700 Guide

Popular Control Panel manuals by other brands

GENEVO PRiMA 6 installation manual

GENEVO

GENEVO PRiMA 6 installation manual

NAPCO X 255 - Programming instructions

NAPCO

NAPCO X 255 - Programming instructions

Next Systems UNIR1 230 instruction manual

Next Systems

Next Systems UNIR1 230 instruction manual

HORNER HE-XPW1E0 user manual

HORNER

HORNER HE-XPW1E0 user manual

DSC CLASSIC PC1555 instruction manual

DSC

DSC CLASSIC PC1555 instruction manual

Bosch Solution 2000 installation guide

Bosch

Bosch Solution 2000 installation guide

VRinsight MS Panel user manual

VRinsight

VRinsight MS Panel user manual

Zeiss SYCOP 3 Quick reference guide

Zeiss

Zeiss SYCOP 3 Quick reference guide

HULTSTEINS ECOFRIDGE DISPLAY user manual

HULTSTEINS

HULTSTEINS ECOFRIDGE DISPLAY user manual

Elkron C420 Programming manual

Elkron

Elkron C420 Programming manual

GST GST200-2 Installation and operation manual

GST

GST GST200-2 Installation and operation manual

Efka Variocontrol V810 instruction manual

Efka

Efka Variocontrol V810 instruction manual

RDZ PC-HRX user manual

RDZ

RDZ PC-HRX user manual

STG-BEIKIRCH MZ3 operation instruction

STG-BEIKIRCH

STG-BEIKIRCH MZ3 operation instruction

AMX AutoPatch CP-15 instruction manual

AMX

AMX AutoPatch CP-15 instruction manual

Cebora 208-10 instruction manual

Cebora

Cebora 208-10 instruction manual

Satel CA-6 KLED-S user manual

Satel

Satel CA-6 KLED-S user manual

Evolution IQ plus 800 installation manual

Evolution

Evolution IQ plus 800 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Tel:
Fax:
Email:
Web Site:
+44(0)161 483 1415
+44(0)161 484 2345
[email protected]
www.oliver-igd.co.uk
I G D
O L I V E R
4a Pepper Road
Stockport
SK7 5BW
England
Oliver IGD Limited V9.0
TOCSIN 700+
INSTALLATION
AND
USER INSTRUCTIONS
Table of Contents
Specification
Overview
Interface Wiring
Operating System
3
3
7
8
9
10
11
12
13
14
15
17
18
21
22
23
26
27
29
30
34
36
38
40
44
45
46
47
48
49
50
51
CE Declarations
Relay Outputs, Audio Visual Output, two and
three wire detectors
3 Wire 4-20mA Pellistors (analogue)
Digital Port
Toxic Analogue Detectors 2 wire
Infra Red 3 Wire Detectors
FREON Detectors
Fire and Smoke Detector Inputs
Addressable Detectors
Addressable Relay Outputs
19" Rack System Versions
Accepting and Resetting Alarms
Basic Menu Operation
User Menu System Overview
Zero and Calibration Commands
Alarm Setup
Channel Description Edit
Engineers Menu Overview
Detector Channel Setup
FIND detectors command
Additional Relay Outputs
Analogue Outputs
Addressable Sensor Test
Addressable Relay Test
Fire Input Test
Production Menu Overview
Alarm Operation
Mimic Panels
RS 485 Repeaters
Modbus Map
OLIVER I G D
This product must be earthed in accordance with local safety regulations.
The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
Standard voltage and frequency range is:-
AC Mains Powered 85 to 264 VAC 40 to 400 Hz
DC Low Voltage Powered 18 to 30V DC
Should the control panel be used in conjunction with portable generating equipment, care should be taken to ensure that
the electrical supply is within the tolerance band described above. The control panel may be stored at temperatures
0 0
between 0 C and 55 C. If stored at low temperatures and then brought into a warmer environment, condensation may
form on some components. In such a situation , this condensation should be allowed to evaporate prior to use of the
equipment. If stored at high temperature, care should be taken to ensure that humidity condensation does not enter
critical electrical components, for example the power supply. The Control Panel is designed to operate within
o o
specification for ambient temperature between 0 C and 55 C, relative humidity up to 95% ( non-condensing ).
!Warning !
Do not use a Control Panel for protection applications that has not been calibrated. If calibration seals are missing from
the control panel or have been tampered with or broken, then the control panel must be re-calibrated and sealed by a
trained engineer.
See declaration CE-700-03
Page 3 of 52
Power Source 85 to 264 VAC ( 18 to 30 VDC Option)
Power Consumption 60 Watts (basic) 150 Watts (700+)
Display 2 x 16 backlight LCD
Operating Temperature 0°c to 55°c
Operating Humidity Up to 95% non-condensing
Resolution 0.00% or ppm Range Dependant
Update Rate 1 Second
Size (mm) 255 (H) x 265 (W) x 100 (D)
Protection Standard IP54. With seal kit option fitted IP55
Inputs Up to 4 or up to 8 x 4-20mA loops
Additional 8 analogue 4-20mA loopsInputs (Optional)
2 x RS485 data highways for up to 64 detectors (700+)
3 x configurable SPCO relays (7 Amp non conductive load)
1 x fault SPCO relays (7 Amp non conductive load)
1 x solid state audio/sounder 24VDC
Outputs (Standard)
1 x solid state visual/flasher 24VDC
Outputs (Optional) Up To 32 x configurable SPCO relays 7 Amp non inductive load
Up To 16 x Analogue Outputs (4 per additional card)
Up To 32 x Addressable Relay Outputs
Optional Equipment Battery backup module 7AH 255 (H) x 265 (W) x 100 (D)
CE Declaration BS EN61000-6-4 EMC Compatibility 'Emissions'
Weight 4.6 KG
BS EN 61000-6-2:2001 EMC Compatibility 'Immunity'
BS EN 61010-1: 2001 Safety requirements, electrical equipment
Who should read this manual.
This manual is intended for use by trained installers of gas detection systems who are technically competent and
have all necessary tools to undertake installation and maintenance on this type of equipment.
Failure to install and maintain the equipment properly can render the detector ineffective.
You should not undertake any of the procedures in this manual if you do not have access to the correct equipment,
have not undertaken training on this or similar equipment or are not technically qualified to install this equipment.
Calibration gases and test equipment is available from IGD.
EC Declaration of Conformity
OLIVER I G D
CO
H2S
CO2
SO2
NO NO2
CH4
Issuers name and address:
Oliver IGD Limited of
4a Pepper Rd
Stockport, SK7 5BW
United Kingdom
Declares that the product listed as:
TOCSIN 700
Multi-Channel Hazardous Gas Detector Control Panel
IP54 Version.
Part Numbers 5109601 5109602 5109601DC
5110001 5110001DC 5110801
5110801DC
Are in conformity with the provisions of the following European Directive(s) when installed, operated, serviced
and maintained in accordance with the installation and operating instructions contained in the product
documentation.
And that the standards and/or technical specifications referenced below have been applied or considered.
2004/108/EC EMC Directive
2006/95/EC Low Voltage Equipment Directive (note not applicable to 24V DC Powered Versions)
EN 61779-1:2000
EN 50271:2001
BS EN 60529
Technical File Reference
Electrical apparatus for the detection and measurement of flammable gases,
general requirements and test methods.
Electrical apparatus for the detection and measurement of combustible gases,
toxic gases or Oxygen: requirements and tests for apparatus using software and
or digital technologies. Excluding requirements for SIL
Requirements for the classification of degrees of protection provided by
enclosures for electrical equipment.
T700-TF9
Product Markings
Issued on: 16 May 2011 At Oliver IGD Limited, Stockport, SK7 5BW , United Kingdom
Notified Body For ATEX and/or QAN:
Sira Test & Certification Ltd
Hazardous Area Centre,
Rake Lane
Eccleston, Chester, CH4 9JN.
United Kingdom
Oliver IGD Limited operate an independently assessed
ISO9001:2008 Quality Assurance System and ATEX QAN.
Quality Assurance Certificate Number
023827
Quality Assurance Notification Number
SIRA 02ATEX M174
Signature:
Name Andrew J Collier M.I.Mech I.E I.Eng M.I.O.D
Position: Managing Director
Date: 16 May 2010
Declaration Ref: T700IP54CE-2
Declaration of Conformity in accordance with EN ISO/IEC 17050-1:2004
Page 1 of 1
TOCSIN 700+
Serial Numbers: S/17588-1-1 & S/17588-1-2
Page 4 of 52
EC Declaration of Conformity
OLIVER I G D
CO
H2S
CO2
SO2
NO NO2
CH4
Issuers name and address:
Oliver IGD Limited of
4a Pepper Rd
Stockport, SK7 5BW
United Kingdom
Declares that the product listed as:
TOCSIN 700
Multi-Channel Hazardous Gas Detector Control Panel
IP66 Version.
Part Number 5110005 IP66
Are in conformity with the provisions of the following European Directive(s) when installed, operated, serviced
and maintained in accordance with the installation and operating instructions contained in the product
documentation.
And that the standards and/or technical specifications referenced below have been applied or considered.
2004/108/EC EMC Directive
2006/95/EC Low Voltage Equipment Directive (note not applicable to 24V DC Powered Versions)
EN 61779-1:2000
EN 50271:2001
BS EN 60529
Technical File Reference
Electrical apparatus for the detection and measurement of flammable gases,
general requirements and test methods.
Electrical apparatus for the detection and measurement of combustible gases,
toxic gases or Oxygen: requirements and tests for apparatus using software and
or digital technologies. Excluding requirements for SIL
Requirements for the classification of degrees of protection provided by
enclosures for electrical equipment.
T700-TF9
Product Markings
Issued on: 12 Jan 2009 At Oliver IGD Limited, Stockport, SK7 5BW , United Kingdom
Notified Body For ATEX and/or QAN:
Sira Test & Certification Ltd
Hazardous Area Centre,
Rake Lane
Eccleston, Chester, CH4 9JN.
United Kingdom
Oliver IGD Limited operate an independently assessed
ISO9001:2008 Quality Assurance System and ATEX QAN.
Quality Assurance Certificate Number
023827
Quality Assurance Notification Number
SIRA 02ATEX M174
Signature:
Name Andrew J Collier M.I.Mech I.E I.Eng M.I.O.D
Position: Managing Director
Date: 12 Jan 2009
Declaration Ref: T700IP66CE-2
Declaration of Conformity in accordance with EN ISO/IEC 17050-1:2004
Page 1 of 1
TOCSIN 700 or TOCSIN 700+
S/-serial number
Page 5 of 52
EC Declaration of Conformity
OLIVER I G D
CO
H2S
CO2
SO2
NO NO2
CH4
Issuers name and address:
Oliver IGD Limited of
4a Pepper Rd
Stockport, SK7 5BW
United Kingdom
Declares that the product listed as:
TOCSIN 700
Multi-Channel Hazardous Gas Detector Control Panel
IP55 Version with seal kit fitted.
Part Numbers 5109601 5109602 5109601DC
5110001 5110001DC 5110801
5110801DC
Are in conformity with the provisions of the following European Directive(s) when installed, operated, serviced
and maintained in accordance with the installation and operating instructions contained in the product
documentation.
And that the standards and/or technical specifications referenced below have been applied or considered.
2004/108/EC EMC Directive
2006/95/EC Low Voltage Equipment Directive (note not applicable to 24V DC Powered Versions)
EN 61779-1:2000
EN 50271:2001
BS EN 60529
Technical File Reference
Electrical apparatus for the detection and measurement of flammable gases,
general requirements and test methods.
Electrical apparatus for the detection and measurement of combustible gases,
toxic gases or Oxygen: requirements and tests for apparatus using software and
or digital technologies. Excluding requirements for SIL
Requirements for the classification of degrees of protection provided by
enclosures for electrical equipment.
T700-TF9
Product Markings
Issued on: 16 Feb 2009 At Oliver IGD Limited, Stockport, SK7 5BW , United Kingdom
Notified Body For ATEX and/or QAN:
Sira Test & Certification Ltd
Hazardous Area Centre,
Rake Lane
Eccleston, Chester, CH4 9JN.
United Kingdom
Oliver IGD Limited operate an independently assessed
ISO9001:2008 Quality Assurance System and ATEX QAN.
Quality Assurance Certificate Number
023827
Quality Assurance Notification Number
SIRA 02ATEX M174
Signature:
Name Andrew J Collier M.I.Mech I.E I.Eng M.I.O.D
Position: Managing Director
Date: 16 Feb 2009
Declaration Ref: T700IP55CE-2
Declaration of Conformity in accordance with EN ISO/IEC 17050-1:2004
Page 1 of 1
TOCSIN 700+
Serial Number
Page 6 of 52
OLIVER I G D
Tocsin 700 Panel Overview
2 x 16 LCD Display
24V DC Panel Power
Digital Inputs
Jog Wheel
3 off Configurable Relay Outputs
With Activation Indication Lamps
Sounder/Flasher
Outputs
Fault Relay Outputs
RS 485 Detector
Data Highway
Connector Port 1
‘C1’
(Addressable Versions)
RS 485 Detector
Data Highway
Connector Port 2
‘C2’
(Addressable Versions)
Expansion
Connector
8 off 4-20mA Loop Inputs
Mains/DC Input
(Check Supply Option Before Use) Grounding Points
L N E 110/230V AC 50/60Hz
RS232 Comm
Port
Page 7 of 52
OLIVER I G D
Tocsin 700 Interface wiring
Sounder Alarm
Max Current
150mA 24V DC
These 3 relays can be assigned,
named, zoned etc using the Tocsin
700 operating software.
Dedicated fault relay output, this output
is energised in normal operation
In all Cases:
Relay contact ratings.
7A @ 250V AC Non-Inductive
7A @ 30V DC Non-Inductive
Spike suppression must be fitted
Note that FAULT relays are normally
energised on power up.
Addressable control panel versions only.
See 'Addressable Sensors' Section
24V DC
24V DCAUDIO
OUTPUT
VISUAL
OUTPUT
SOUNDER O/P
WARNING LAMP O/P
Enclosure
Ground
Enclosure
Ground
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 1000M.
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 1000M.
Blue
Red
Black
Red
Blue
TOCSIN 102/A
TOXIC GAS
DETECTORS
TOCSIN 102IR
FLAMMABLE GAS/
CO2 DETECTORS
+24V DC
B
A
0V
Note Flasher on
with alarm level 1.
Buzzer on with
alarm level 2.
NO NC
COM
AL1
AL2
AL3
0V DC
4-20mA IN
+24V DC
GND
GND
Page 8 of 52
OLIVER I G D
OLIVER I G D
Tocsin 700 Interface wiring...continued
T106P Pellistor
Flammable Gas
Detectors
1.5mmSQ See Panel
for recommended cable
types.Max cable
run 1000M.
0V DC
4-20mA IN
+24V DC
GND
ZERO
FAULT
CAL
360
CHASS
24V DC
B
A
GND
mA
P Y W
Common
Active
Compensator
mA+360CONC0V mA-
Page 9 of 52
OLIVER I G D
OLIVER I G D
Tocsin 700 Interface wiring...Digital Port
Located at the top edge of the Tocsin
700 card is a 4 way connector used to
allow digital interface to the Tocsin 700
operating system as follows:
0V common
Password Inhibit
Reset Alarms
Inhibit Alarms
1 2 3 4
Page 10 of 52