Omega DPF700 User manual

DPF700
Dual Relay Option Board
for the DPF700 Meter
www.omega.com
e-mail: [email protected]
User’s Guide
Shop on line at

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New
Approach Directi es. OMEGA will add the CE mark to e ery appropriate de ice upon certification.
The information contained in this document is belie ed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reser es the right to alter
specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This de ice is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this de ice as the guide contains important
information relating to safety and EMC.
This de ice is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this de ice as the guide contains
important information relating to safety and EMC.
!
Servicing North America:
USA: One Omega Dri e, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700
Canada: 976 Bergar
La al (Quebec) H7L 5A1
TEL: (514) 856-6928 FAX: (514) 856-6886
For immediate technical or application assistance:
USA and Canada: Sales Ser ice: 1-800-826-6342 / 1-800-TC-OMEGA®
Customer Ser ice: 1-800-622-2378 / 1-800-622-BEST®
Engineering Ser ice: 1-800-872-9436 / 1-800-USA-WHEN®
Mexico and TEL: (001)800-TC-OMEGA® FAX: (001) 203-359-7807
Latin America: En Español: (001) 203-359-7803
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstel een, The Netherlands
TEL: +31 20 3472121 FAX: +31 20 6434643
Toll Free in Benelux: 0800 0993344
Czech Republic: Frystatska 184, 733 01 Kar iná
TEL: +420 59 6311899 FAX: +420 59 6311114
France: 11, rue Jacques Cartier, 78280 Guyancourt
TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
German /Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0 FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
United Kingdom: One Omega Dri e
ISO 9002 Certified Ri er Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
OMEGAnet® On-Line Service
www.omega.com
Internet e-mail
®
®

i
PREFA E
MANUAL OBJE TIVES
This manual shows you how to install and use the Dual-Relay option board with the DPF700
meter.
In this manual we pro ide procedures for:
* Setting up the Dual-Relay option board
* Installing the Dual-Relay option board
Use this manual with you DPF700 manual (M1676)
NOTES and AUTIONS
Information that is especially important to note is identified by these labels:
• NOTE
• WARNING
• AUTION
• IMPORTANT
NOTE: pro ides you with information that is important to successfully setup
and use the Programmable Digital Meter.
AUTION or WARNING: tells you about the risk of electric shock.
AUTION, WARNING or IMPORTANT: tells you of circumstances or
practices that can effect the meter's functionality and must refer to
accompanying documents
Note ☞

ii
TABLE OF ONTENTS
1.1 UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2.1 INSTALLING THE DUAL-RELAY OPTION BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.2 SETTING UP THE DUAL-RELAY OPTION BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.3 ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3.1 RELAY OUTPUT OPTION BOARD SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . .6
FIGURES
2.1 DUAL RELAY OPTION BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.2 SETPOINT EXAMPLE ILLUSTRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.3 ELECTRICAL WIRING FOR RELAY CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.4 DUAL RELAY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
TABLES
2.1 SETPOINT EXAMPLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

1.1 UNPA KING
Remo e the Packing List and erify that all equipment has been recei ed. If there are any
questions about the shipment, use the phone number for the Customer Ser ice Department
nearest you.
Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take
particular note of any e idence of rough handling in transit. Immediately report any damage to
the shipping agent.
The carrier will not honor any claims unless all shipping material is saved for their
examination. After examining and removing contents, save packing material and carton
in the event reshipment is necessary.
1.2 SAFETY ONSIDERATIONS
Refer to your main owners guide manual for complete safety considerations.
This option card is intended for use in a DPF700 panel mount de ice that is protected in
accordance with Class I of EN 61010 (115/230 AC power connections). Installation of this
instrument should be done by Qualified personnel.
• Do not exceed oltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosi e atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate entilation to ensure instrument does not
exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to minimize
electrical shock hazards.
1
1
Note ☞
Note ☞

2
2
2.1 INSTALLING THE DUAL-RELAY OPTION BOARD
To install the dual-relay option board, follow these steps (refer to the Figure 2-1):
!AUTION: The meter has no power-on switch, so it will be in operation
as soon as you apply power.
!IMPORTANT: Disconnect the power from the unit before installing this
option board.
1. Hold the board in a horizontal position, with the TB3 connector facing towards the
rear of the meter.
2. Line up the 3 connectors located on the back side of the board with pin groups J3, J4
and J5 on the mother card.
3. Push connectors down to secure on relay board.
Figure 2-1. Dual-Relay Option Board
NC1 N01 CM1 NC2 NO2 CM2
123456
TB3/RELAY
RELAY BD MAIN BD
123
TB1
123456
123456
TB2
S1
OPEN
CLOSED
12345678910
21
21
21
J4
J3
J5
TB3
S5
AB

3
2.2 SETTING UP THE DUAL-RELAY OPTION BOARD
You may enter a setpoint from -99999 to 999999 with a decimal point in any of the following
positions: 9.9.9.9.9.9. After applying the scale factor and offset, the displayed measurement is
compared to the setpoint alues.
LO ALARM
Displayed alue is less than Setpoint LO
HI ALARM
Displayed alue is more than Setpoint HI
HYSTERESIS
Relay 2 is energized when display alue is more than Setpoint HI. Relay 2 is not
energized when display alue is less than Setpoint LO
Setpoint Example:
Setpoint H is 500.0 and Setpoint LO is 100.0.
Reading changes from 0 to 600 and back to 0.
Figure 10-2 on the following page illustrates Table 2-1.
Table 2-1. Setpoint Example
Alarm Status
Reading LO (Relay 1) HI (Relay 2) HYS
0 On Off Off
99.9 Off Off Off
300 Off Off Off
500.0 Off Off Off
500.1 Off On On
600 Off On On
500.1 Off Off On
100 - 500 Off Off On
99.9 On Off Off
0 On Off Off
2

2
2.2 SETTING UP THE DUAL-RELAY BOARD ( ontinued)
Figure 2-2. Setpoint Example Illustration
To con ert Setpoint LO to a second high setpoint, set software switch 3 of the configuration
menu to 1 (ConFIG = XX1XXX). LO ALARM becomes acti e when the reading is greater (more
positi e) than that setpoint.
To con ert both setpoints to latched setpoints, set software switch 2 of the configuration menu to
1 (ConFIG =X1XXXX). When relays are energized, they stay energized until a Reset (either
front-panel or back connector reset).
STANDARD RELAY OPTION
RELAY OPERATION WITH HYSTERESIS
RELAY 1 (LO)
RELAY 2 (HI)
RELAY 2 (HI)
RELAY 1 (LO)
RELAY 2 (HI)
RELAY 1 (LO)
RELAY 2 (HI)
RELAY 1 (LO)
(RELAY ON OR ENERGIZED)
(RELAY ENERGIZED)
99.9
SET POINT 99.90
SET POINT 99.90
ON
ON
OFF
OFF
OFF
OFF
OFF OFF
OFF OFF
ON
ON
ON
OFF OFF
OFF OFF
ON
ON
OFF
OFF OFF
ON
ON
500.1
500.1
ON
4

5
2.3 ELE TRI AL ONNE TION AND SPE IFI ATION
Each relay has a form C contact. Refer to Figure 2-1 and Figure 2-3 to locate contacts and S5
switch.
* Install S5-A to control Relay 2 with hysteresis action.
* Install S5-B to control Relay 2 with setpoint HI.
* TB3-1 is a normally closed contact of relay 1.
* TB3-2 is a normally open contact of relay 1.
* TB3-3 is a common contact of relay 1.
* TB3-4 is a normally closed contact of relay 2.
* TB3-5 is a normally open contact of relay 2.
* TB3-6 is a common contact of relay 2.
Figure 2-3. Electrical Wiring for Relay onnections
Figure 2-4. Dual-Relay onnections
10-1. Dual-Relay Option Board
2
J1
J2
TB1
123
123456
1
6
TB2
TB3
EXTERNAL
LOAD
N
L
FUSE
RELAY 1 RELAY 2
NC1
NO1
CM1
NC2
NO2
CM2
TB3—1
TB3—2
TB3—3
NC1
NO1
CM1
TB3—4
TB3—5
TB3—6
NC2
NO2
CM2
RELAY1
RELAY2
K1
K2 A
BS5
P5
SETPOINT LOW OUTPUT
HYSTERESIS OUTPUT
SETPOINT HIGH OUTPUT

3
6
3.1 RELAY OUTPUT OPTION BOARD SPE IFI ATIONS
2 Form "C" on/off relays.
Configurable for latched and unlatched by software.
Max Current: 5 Amps, resisti e load.
Max Voltage: 250 Vac or 28 Vdction D
NOTES
aults

WARRANTY/DIS LAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal
one (1) year product warranty to co er handling and shipping time. This ensures that OMEGA’s customers recei e
maximum co erage on each product.
If the unit should malfunction, it must be returned to the factory for e aluation. OMEGA’s Customer Ser ice
Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon
examination by OMEGA, if the unit is found to be defecti e it will be repaired or replaced at no charge. OMEGA’s
WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to
mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification.
This WARRANTY is VOID if the unit shows e idence of ha ing been tampered with or shows e idence of being
damaged as a result of excessi e corrosion; or current, heat, moisture or ibration; improper specification;
misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not
warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither
assumes responsibilit for an omissions or errors nor assumes liabilit for an damages that result from
the use of its products in accordance with information provided b OMEGA, either verbal or written.
OMEGA warrants onl that the parts manufactured b it will be as specified and free of defects. OMEGA
MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR
IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION
OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liabilit of OMEGA with
respect to this order, whether based on contract, warrant , negligence, indemnification, strict liabilit or
otherwise, shall not exceed the purchase price of the component upon which liabilit is based. In no event
shall OMEGA be liable for consequential, incidental or special damages
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or acti ity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or acti ity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth
in our basic WARRANTY/DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold
OMEGA harmless from any liability or damage whatsoe er arising out of the use of the Product(s) in such a
manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Ser ice Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to pre ent
breakage in transit.
FOR WARRANTY RETURNS, please ha e the
following information a ailable BEFORE
contacting OMEGA:
1. P.O. number under which the product was
PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relati e to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for
current repair charges. Ha e the following information
a ailable BEFORE contacting OMEGA:
1. P.O. number to co er the COST
of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems
relati e to the product.
USA
MADE
IN
OMEGA’s policy is to make running changes, not model changes, whene er an impro ement is possible. This affords our customers
the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2003 OMEGA ENGINEERING, INC. All rights reser ed. This document may not be copied, photocopied, reproduced,
translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior written consent of
OMEGA ENGINEERING, INC.
PATENT NOTICE: The “Meter Case Bezel Design” is a trademark of NEWPORT Electronics, Inc., registered in the U.S. USED
UNDER LICENSE. This product is co ered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577 /
CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 /
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. OTHER INTERNATIONAL PATENTS PENDING.

M1799/1203 11689ML-99 Re . C
Where Do I Find Everything I Need for
Process Measurement and ontrol?
OMEGA…Of ourse!
Shop on line at www.omega.com
TEMPERATURE
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FOR E
Transducers & train Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
FLOW/LEVEL
Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/Paddlewheel ystems
Totalizers & Batch Controllers
pH/ ONDU TIVITY
pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, imulators & Pumps
Industrial pH & Conductivity Equipment
DATA A QUISITION
Data Acquisition & Engineering oftware
Communications-Based Acquisition ystems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging ystems
Recorders, Printers & Plotters
HEATERS
Heating Cable
Cartridge & trip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL
MONITORING AND ONTROL
Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, oil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved Oxygen Instruments
Other manuals for DPF700
2
Table of contents
Other Omega Measuring Instrument manuals

Omega
Omega FPR310 Series User manual

Omega
Omega DP26-RTD Instruction manual

Omega
Omega PRESSURE GAUGES DPG3000 User manual

Omega
Omega DPG108 User manual

Omega
Omega SP-010 User manual

Omega
Omega DP18 series User manual

Omega
Omega USB-4750 User manual

Omega
Omega DP25B-S User manual

Omega
Omega C760 User manual

Omega
Omega HHLM3 User manual

Omega
Omega CL1000 Series User manual

Omega
Omega DP18-P9 User manual

Omega
Omega HHM598F User manual

Omega
Omega i-SERIES User manual

Omega
Omega DPG104 User manual

Omega
Omega FTB380 Series User manual

Omega
Omega FHG Series User manual

Omega
Omega DP18-AC1 User manual

Omega
Omega HHWT-11 User manual

Omega
Omega PHB21 User manual