Omega DP20 User manual

To view the DP20 spec sheet and manuals visit us at hps://www.omega.com/pptst/DP20.html
3. Addional documentaon
1. Front view
1. Open the instrument (see secon 7).
2. Select the jumpers for the desired signal range (see secon 8).
3. Close the instrument (see secon 7).
4. Connect the signal and the power (see secon 6).
5.
Congure the instrument
from the ‘
Conguraon menu’ (see secon 9).
6. If you need addional informaon, see secon 3.
5. Installaon and start-up
6. Connecons
7. How to open the instrument
DP20
Model
-
Opon 1
-A1 (1 relay)
-M1 (analog output)
-S1 (Modbus RTU)
-(empty)
-
Opon 2
-A2 (1 relay)
-(empty)
4. How to order
2. Dimensions and panel cut-out (mm)
8. Internal structure and jumpers for range selecon
MQS5802_0618
Key ‘LE’ Key ‘SQ’
1. Exit the menu
Key ‘UP’
1. Enter into ‘Fast access’
2. Next value
Units
Alarm 1 and 2
Fuse
Opon M1 (4/20 mA)Opon A1 (relay)
Protecon fuse value :
250 mA me-lag for power voltage > 50 Vac/dc
400 mA me-lag for power voltage < 50 Vac/dc
ABC
Common
Vexc.
4/20 mA
ABC
NC
Com.
NO
Opon S1 (Modbus RTU)
ABC
Common
B
A
Opon 2 Opon 1
12345 890
-Vdc / Neutral
+Vdc / Phase
Not Connected
ABC
Opon A2 (relay)
NC
Com.
NO
G IH
G IH
~Vac, ±Vdc, resistance, mA, pot
thermocouple+, Pt+, Ni+, PTC+, NTC+
~600 Vac, ~200 Vac
±600 Vdc, ±200 Vdc
~5 Aac, ±5 Adc
neutral, 0 V, common
Vexc, Pt100 3 wires, pot+
external control
NTC probes ‘R25’
(congurable)*
Jumpers
‘S’
Jumper
‘T’
Range
of measure
Accuracy
(% of reading)
Beta
(congurable)
10K F K 4-5 -60ºC to
150ºC
<1.5 % of
reading
3500
*‘Beta’ congurable (2000 to 5500). R25 congurable. Resistance measure from 100R to 1MR.
AC ranges Scalable Jumpers
‘S’
Jumper
‘T’
Accuracy
(% FS)
~ 600 Vac
from 9999
to -1999
G I
4-5
<0.30 %
(up to 150 Hz)
~ 200 Vac I
~ 20 Vac A I
~ 2 Vac B I
~ 200 mVac C I
~ 60 mVac E I
~ 5 Aac I <0.50 %
(up to 150 Hz)
~ 20 mAac D I
DC ranges Scalable Jumpers
‘S’
Jumper
‘T’
Accuracy
(% FS)
±600 Vdc
from 9999
to -1999
G
4-5
<0.20 %
±200 Vdc ---
±20 Vdc A
±2 Vdc B
±200 mVdc C
±60 mVdc E <0.25 %
±5 Adc - - -
±20 mAdc D<0.15 %
PTC probes
Family
Jumpers
‘S’
Jumper
‘T’
Range in ºC
(in ºF)
Total error
KTY-121 F
4-5 -55 / 150 ºC
(-67 / 302 ºF) <1 º
KTY-210 F H K
KTY-220 F H K
Pt and Ni
probes
Jumpers
‘S’
Jumper
‘T’
Range in ºC
(in ºF)
Total
error
Current at
sensor
Pt100
(3 wires) F H J 5-6 -200 / 700 ºC
(-328 / 1292 ºF)
<1º
< 900 uA
Pt100
(2 wires) F H
4-5
-200 / 700 ºC
(-328 / 1292 ºF) < 900 uA
Pt500 F -150 / 630 ºC
(-238 / 1166 ºF) < 90 uA
Pt1000 F -190 / 630 ºC
(-310 / 1166 ºF) < 90 uA
Ni100 F H -60 / 180 ºC
(-76 / 356 ºF) < 900 uA
Ni200 F H -60 / 120 ºC
(-76 / 248 ºF) < 900 uA
Ni1000 F -60 / 180 ºC
(-76 / 356 ºF) < 90 uA
Thermocouples
Jumpers
‘S’
Jumper
‘T’
Range in ºC
(in ºF)
Total error
(
cold juncon included
)
tc. K
E
4-5
-100 / 1350 ºC
(-148 / 2462 ºF)
<3 º
tc. J -100 / 1200 ºC
(-148 / 2192 ºF)
tc. E -100 / 1000 ºC
(-148 / 1832 ºF)
tc. N -100 / 1300 ºC
(-148 / 2372 ºF)
tc. L -100 / 900 ºC
(-148 / 1652 ºF)
tc. R
E J
0 / 1768 ºC
(32 / 3214 ºF)
tc. S 0 / 1768 ºC
(32 / 3214 ºF)
tc. T -100 / 400 ºC
(-148 / 752 ºF)
tc. C E0 / 2300 ºC
(32 / 4172 ºF)
<5 º
tc. B E J 700 / 1820 ºC
(1292 / 3308 ºF)
Resistance
ranges
Scalable Jumpers
‘S’
Jumper
‘T’
Accuracy
(% reading)
0 to 5 K from 9999
to -1999
F H K
4-5
<1.5 % of
reading
0 to50 K F K
Process
signals
Scalable Jumpers
‘S’
Jumper
‘T’
Accuracy
(% FS)
4/20 mA from 9999
to -1999
D1-2*<0.15 %
0/10 Vdc A <0.20 %
* Place jumper ‘T’ at posion 1-2 for +15 Vdc excitaon voltage at terminal 5. Oponally,
place jumper ‘T’ at posion 4-5 to work with ‘external contact’ at terminal 5.
Potenometers
nominal value
Scalable Jumpers
‘S’
Jumper
‘T’
Accuracy
(% FS)
500 R to 20 K from 9999
to -1999 A 2-3
<0.5 %
!
(acve output A-B)
(passive output B-C)
Risk of electric shock. Removing the front cover will grant access to internal
circuits which may be at dangerous voltage. Disconnect the input signal and
the power supply to prevent electric shock to the operator. Operaon must be
performed by qualied personnel only.
Use a at screwdriver to unlock clips ‘D’, C’, ‘B’
and ‘A’, in this order. Remove the front lter.
Gently let the internal boards slide out of the
instrument.
To reinsert the boards in the housing :
1. make sure that the boards are correctly con-
nected to the displays pins
2. slide the boards into the housing guides
3. place the front lter at corner X, and then
insert clips ‘A’, ‘B’, ‘C’ and ‘D’ in this order. XA
C
BD
Internal Jumpers
Opt.1
Opt.2
Opt.1
Display module Oponal modules
Housing
Front lter
Input signal terminal
Jumpers ‘S’
for signal range selecon
Displays
F
E
G
H
I
J
D
B
C
A
K
Jumpers not used can be
stored in the following three
‘no contact’ posions.
F
E
G
H
I
J
D
B
C
A
K
6
5
4
3
2
1
Jumper ‘T’
for terminal 5 funcon selecon
DP20 shown smaller
than actual size
Quick installaon guide DP20 (page 1/2) www.omega.com/ DP20.html
Detail of the female
terminal provided.
96 mm
48 mm
91 mm
(including terminal)
16
8
75
(0.63)
(0.31)
(2.95)
Panel
cut-out
92
(3.63)
44
(1.74)
(3.78)
(1.89)
(3.58)
TM
Frequency Scalable Jumpers ‘S’ Jumpers ‘T’ Accuracy
(% of reading)
15 Hz to 100 Hz from 9999
to -1999
select Vac or
Aac range
4-5 <0.15%
of reading

10. Regulaons
This instrument conforms to the actual CE regulaons. For a copy of the ‘CE declaraon
of conformity’ see secon 3. Applicable regulaons are :
Security regulaons EN-61010-1 (‘Fixed’ equipment, ‘Permanently connected’.
‘Double’ isolaon. ‘CAT-II’ category)
Electromagnec compability regulaons EN-61326-1
According to direcve 2012/19/EU, electronic equipment must be re-
cycled in a selecve and controlled way at the end of its useful life.
This instrument does not provide a general mains switch and will start operaon as
son as power is connected. The instrument does not provide protecon fuse, and the
fuse must be added during installaon.
Risk of electrical shock. Instrument terminals can be connected to
dangerous voltage.
Instrument protected with double isolaon. No earth connecon
required.
Instrument conforms to CE rules and regulaons.
Range, scaling and decimal point 0/600 Vac = 0/600
Alarm 1 as maximum
Setpoint 1000
Hysteresis 0 counts
Alarm 2 as maximum
Setpoint 1000
Hysteresis 0 counts
External control o
Fast access all o
Tools
Opon 1 o (retains last conguraon value)
Step 1
Average 0
Manual oset 0
Second scaling 0/600
‘Eco’ mode o
Temperature resoluon 1º
Degrees ºC
Alpha 385
cJc on
AC ‘deadband’ 20
Luminosity 3
Password o
Opon
Analog output 0/100.0=4/20 mA
Serial Modbus RTU 9600 bps, address 1, format 8n1
Jumpers ‘S’ range for 600 Vac
Jumper ‘T’ external contact ‘EK’ funcon
11. Factory conguraon
9. Conguraon menu
Press ‘SQ’ (<) for 1 second to access
the ‘Conguraon menu’.
Input AC signals
600 V
200 Vac
20 Vac
2 Vac
200 mVac
60 mVac
5 Aac
20 mAac
DC signals
±600 Vdc
±200 Vdc
±20 Vdc
±2 Vdc
±200 mVdc
±60 mVdc
±5 Adc
±20 mAdc
Process
4/20 mA
0/10 Vdc
Thermocouples
thermocouple
K
thermocouple
J
thermocouple
E
thermocouple
N
thermocouple
L
thermocouple
R
thermocouple
S
thermocouple
B
thermocouple
T
thermocouple
C
NTC probes
Resistances
0 to 5 K
0 to 50 K
Alarm 1
Setpoint
Hysteresis
Type
Alarm 2
Setpoint
Hysteresis
Type
Temp.
resoluon.
1º resoluon
0.1º resoluon
Scaling 2 Decimal
Display Low
Display High
‘Eco’ mode 5 to 255 sec.
Filter 0 a 100
Steps
Oset
Decimal 1
Decimal 2
Decimal 0
Scaling 2
Decimal 3
Opon 1
analog
relay
NoneTools
Modbus RTU
enters the
analog output
calibration
menu
Scaling Decimal
Display Low
Display High
Key UP
Maximum
Minimum
Setpoint 1
Setpoint 2
Minimum
Hold
Maximum
External
control
Disabled
Alpha
Alpha 385
Alpha 390
Front keypad menu operaon
Key SQ (<) - 1. Press to access the ‘Conguraon menu’.
2. Press to enter into the actual menu entry.
3. Press to accept a value.
Key UP (5) - 1. Press to access the ‘Fast access’ menu.
2. Press to move through available menu opons.
3. Press to increase the value of a numerical parameter.
Key LE (3) - 1. Without funcon.
2. Press to return to a previous level of the menu, discarding changes (to
validate changes, use SQ (<)).
3. Move through the digits of a numerical parameter.
To save the conguraon changes, press key LE (3) unl exing the menu (shown by
ashing decimal points). Instrument shows the signal range selected and starts opera-
on with the new conguraon.
PTC probes
KTY 121
KTY 210 and 220
Minimum
Brightness
Maximum
Standard
Password
Version
Factory reset
‘AC deadband’
‘Deadband’ on AC
ranges. Value 0 to 100.
Opon 1
conguraon
Analog Display Low
Display High
Modbus RTU Address
Speed
1 to 247
9600 bps
4800 bps
Format
Cold juncon Thermocouple cold juncon
compensaon ‘on’ or ‘o’
Degrees
Celsius
Fahrenheit
RTD probes
Pt100
(2 wires)
Pt500
Pt1000
Ni100
Ni200
Ni1000
Pt100
(3 wires)
Potenometer
If you need addional informaon, see secon 3 to download
the full User’s Manual.
12. User’s manual !
www.omega.com/ DP20.html
600U
600U
tArE
Tare funcon
Frequency
FrEq
Note: The AC powered units cannot be shipped to Canada.
Other manuals for DP20
1
Other Omega Touch Panel manuals