Omega DP41-S User manual

®
®
User’s Guide
Shop on line at
DP41-S
High Performance
Strain Gage Indicator

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the
right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
This device is marked with the international hazard symbol. It is important to read the Setup Guide before installing or commissioning this device as it
contains important information relating to safety and EMC.
United Kingdom: One Omega Drive
ISO 9001 Certified River Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
e-mail: [email protected]
France: TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
e-mail: [email protected]
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700
e-mail: [email protected]
Canada: 976 Bergar
Laval (Quebec) 7L 5A1
TEL: (514) 856-6928 FAX: (514) 856-6886
e-mail: [email protected]
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA®
Customer Service: 1-800-622-2378 / 1-800-622-BEST®
Engineering Service: 1-800-872-9436 / 1-800-USA-W EN®
exico and TEL: (001) 203-359-7803 FAX: (001) 203-359-7807
Latin America: e-mail: [email protected]
Servicing Europe:
Benelux: TEL: +31 20 3472121 FAX: +31 20 6434643
Toll Free in Benelux: 0800 0993344
e-mail: [email protected]
Czech Republic: Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899 FAX: +420 59 6311114
e-mail: [email protected]
O EGAnet® On-Line Service
www.omega.com
Internet e-mail
®
®
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0 FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
e-mail: [email protected]

SECTION 1 INTRODUCTION
1.1 Description.............................................................................1-1
1.2 Features.................................................................................1-1
1.3 Available Models....................................................................1-2
SECTION 2 UNPACKING .........................................................................2-1
SECTION 3 SAFETY CONSIDERATIONS
3.1 Safety Considerations............................................................3-1
SECTION 4 PARTS OF THE METER
4.1 Front of the Meter ..................................................................4-1
4.2 ear of the Meter...................................................................4-3
SECTION 5 SETUP
5.1 Conditions equiring Disassembly........................................5-1
5.2 Assembly/Disassembly Opening ...........................................5-1
5.2.1 Safety Precaution/Product ID Label ......................................5-4
5.2.2 Main Board Power Jumpers ..................................................5-5
5.2.3 Printed Circuit Board(s) Installation .......................................5-6
5.2.4 How to Access Jumpers ........................................................5-7
5.2.5 Panel-Mount Assembly ........................................................5-11
SECTION 6 JUMPER POSITIONS
6.1 Introduction............................................................................6-1
6.2 S1 Jumper Positions for eadrate and
Unipolar or Bipolar Input(s)....................................................6-1
6.3 S2 Jumper Positions for Input ange....................................6-1
6.4 Jumper setting(s) for Sensor Excitation.................................6-3
6.4.1 Jumper setting(s) for Sensor Excitation ac-powered unit ......6-3
6.4.2 Jumper setting(s) for Sensor Excitation dc-powered unit ......6-5
SECTION 7 SIGNAL AND POWER INPUT CONNECTIONS
7.1 Introduction............................................................................7-1
7.2 Signal Input Connections.......................................................7-1
7.3 Connecting Main Power.........................................................7-3
SECTION 8 METHODS FOR SCALING THE METER TO DISPLAY IN
ENGINEERING UNITS
8.1 Introduction............................................................................8-1
8.2 Strain Gage (Bridge) Input, programming the meter for a
desired Display ......................................................................8-1
8.3 Voltage Input (Non- atiometric), programming the meter
for a desired Display...........................................................8-15
8.4 Current Input, programming the meter for a desired Display ....8-28
i
Table of Contents

8.5 Potentiometer Input, programming the meter
for a desired Display............................................................8-40
SECTION 9 METER FUNCTION MENUS
9.1 Individual Lockout Information...............................................9-1
9.2 Meter Function Menus...........................................................9-7
9.2.1 Input.......................................................................................9-7
9.2.2 DG.CNF ( eading Configuration) .......................................9-7
9.2.3 DG SC ( eading Scale) and DG OF ( eading Offset).....9-9
9.2.4 IN CNF (Input Configuration) ...............................................9-11
9.2.5 IN.SC.OF (Input Scale and Offset) ......................................9-12
9.2.6 DEC PT (Decimal Point)......................................................9-14
9.2.7 CNT BY (Count By) .............................................................9-15
9.2.8 FIL.CNF (Filter Configuration) .............................................9-16
9.2.9 FIL TI (Filter Time Constant) ................................................9-17
9.2.10 SP CNF (Setpoints 1 & 2 Configuration) .............................9-18
9.2.11 AL CNF (Alarm Configuration).............................................9-19
9.2.12 AL FNC (Alarm Function) ....................................................9-21
9.2.13 AL DG (Alarm eadings) ..................................................9-22
9.2.14 SP DB (Setpoint Deadband)................................................9-23
9.2.15 AL DB (Alarm Deadband) ....................................................9-23
9.2.16 OUT.CNF (Output Configuration).........................................9-24
9.2.17 OT.SC.OF (Output Scale and Offset) ..................................9-25
9.2.18 BAUD (Baud ate) ..............................................................9-26
9.2.19 SE CNF (Serial Communication Configuration).................9-27
9.2.20 ADD ESS (Multipoint Communications Device Address)...9-28
9.2.21 DAT FT (Data Format) .........................................................9-28
9.2.22 BUS FT (Bus Format)..........................................................9-30
9.2.23 SE CNT (Serial Count).......................................................9-31
9.2.24 Analog Output Calibration Numbers....................................9-32
SECTION 1 SETPOINTS/ALARMS
10.1 Features overview ...............................................................10-1
10.2 Unlocking the Features........................................................10-3
10.3 Selecting “SP CNF” Setpoint Configuration Features..........10-3
10.4 Deviation Function for Alarms..............................................10-4
10.5 Selecting “AL CNF” Alarm Configuration Features ..............10-5
10.6 Selecting “AL FNC” Alarm Configuration Features ..............10-7
10.7 “AL DG”: Alarm eadings-Select Delay in Alarm Action ...10-8
10.8 “SP DB”: Select “SP 1”and “SP 2” Deadband (Hysteresis) .10-8
10.9 “AL DB”: Select Alarm 1 (“SP 3”)
and Alarm 2 (“SP 4”) Deadband ( Hysteresis) .....................10-8
10.10 “OUT.CNF”: Control Flashing of the Display........................10-9
10.11 Entering Setpoint Levels (in un Mode)..............................10-9
Table of Contents
ii

SECTION 11 PEAK AND VALLEY READINGS .......................................11-1
SECTION 12 ANALOG OUTPUT OPTION
12.1 Features Overview...............................................................12-1
12.2 Unlocking.............................................................................12-2
12.3 “OUT.CNF”: Configuring the Output.....................................12-2
12.4 “OT.SC.OF”: Setting Output Scale and Offset .....................12-2
12.5 Board Installation; Entering the trim Data............................12-3
12.6 Filter Configuration “FIL.CNF” Value to be transmitted .......12-5
12.7 Wiring/Connections..............................................................12-5
SECTION 13 BCD OPTION
13.1 Features Overview...............................................................13-1
13.2 BCD Card Jumper Table......................................................13-3
13.3 Interconnect Board ..............................................................13-3
13.4 50-Line Cable Compatibility.................................................13-4
13.5 Selecting the source of BCD Data: “OUT.CNF”...................13-4
13.6 Hold Control.........................................................................13-4
13.7 Data eady Timing Pulses ..................................................13-4
13.8 Bringing out the BCD Overflow line .....................................13-4
13.9 3 Digit at a time Multiplex.....................................................13-4
13.10 6 Digit at a time Card Address.............................................13-5
13.11 Select Data Polarity: Jumper S8..........................................13-6
13.12 Decimal Point Address Code...............................................13-6
13.13 Applying Non-Isolated/Isolated Power.................................13-6
13.14 Driving a Printer...................................................................13-6
SECTION 14 RELAY OPTIONS
14.1 Features Overview...............................................................14-1
14.2 Wiring/Connections..............................................................14-3
SECTION 15 RS-232 OR RS-485 OPTION BOARD
15.1 Features Overview...............................................................15-1
15.2 Front-Panel Pushbutton Configuration ................................15-3
SECTION 16 EXTERNAL CONTROL LINES
16.1 TA E (PIN 1) .......................................................................16-1
16.2 PEAK (PIN 2).......................................................................16-1
16.3 VALLEY (PIN 3) ...................................................................16-1
16.4 SWLIN2 (PIN 4)...................................................................16-1
16.5 PEAK & VALLEY or EXTE NAL ESET (PIN 5) ................16-1
16.6 PUSH TO CAL (PIN 6).........................................................16-2
16.7 Digital eturn (PIN 7)...........................................................16-2
16.8 +5 V (PIN 8).........................................................................16-2
16.9 Display Hold (PIN 9) ............................................................16-2
16.10 LOCKOUT EEP OM (and ‘MENU’ BUTTON) (PIN 10) ......16-2
iii
Table of Contents

16.11 Print Command and/or eset of Alarms (PIN 11) ................16-2
16.12 Nonstandard X (PIN 12) and Nonstandard TX (PIN 13) ...16-2
16.13 PUSH TO CAL (PIN 14).......................................................16-3
16.14 +V EXT (PIN 15)..................................................................16-3
16.15 SP1 (PIN 16)........................................................................16-3
16.16 SP2 (PIN 17)........................................................................16-3
16.17 AL1 (PIN 18)........................................................................16-3
16.18 AL2 (PIN 19)........................................................................16-3
16.19 TN EXT (PIN 20) ...............................................................16-3
SECTION 17 DISPLAY MESSAGES AND TROUBLESHOOTING GUIDE
17.1 Error Mode Message ...........................................................17-1
17.1.1 Flashing “999999” (Numerical Overflow).............................17-1
17.1.2 Flashing “E O1” (Offset Overflow) ..................................17-1
17.1.3 Flashing “E O2” (Setpoint Overflow)...............................17-1
17.1.4 “NOSTO ” & “STO ED
(Programming Entries In EEP OM)....................................17-1
17.1.5 Flashing “+OVLD” (Positive Input Overload) .......................17-1
17.1.6 Flashing “+OPEN” (Open Sensor Indication) ......................17-1
17.1.7 Flashing “-OPEN” (Open Sensor Indication) .......................17-2
17.1.8 Flashing “I OVSC” (Input Overscale)...................................17-2
17.1.9 Flashing “ OVSC” ( eading Overscale)............................17-2
17.1.10 Flashing “CB OVF” (Count By Overflow).............................17-2
17.1.11 Flashing “UOM.OVF” (Unit Of Measure Overflow) ..............17-2
17.2 Troubleshooting Guide ........................................................17-2
SECTION 18 SPECIFICATIONS
18.1 Current Input........................................................................18-1
18.2 Voltage Input........................................................................18-1
18.3 Potentiometer Input .............................................................18-1
18.4 General................................................................................18-1
SECTION 19 FACTORY PRESET VALUES .............................................19-1
SECTION 2 RECORD YOUR SETUP VALUES......................................20-1
Table of Contents
iv

Figure 4-1 Front Detail.........................................................................4-1
Figure 4-2A AC Power - Connector Label for ear Connectors ............4-3
Figure 4-2B DC Power - Connector Label for ear Connectors ............4-4
Figure 4-3 ear View with the optional 4-relay output board
and a serial communications board installed. ....................4-5
Figure 4-4 ear View with the optional BCD output board
and a serial communications output board installed. .........4-5
Figure 5-1 Meter Exploded View..........................................................5-2
Figure 5-2 Board Assembly emoving/Installing Detail .......................5-3
Figure 5-3 Transformer Jumpers .........................................................5-5
Figure 5-4 Optional Printed Circuit Board Locations ...........................5-6
Figure 5-5 Signal Input Board..............................................................5-7
Figure 5-6 ac-Powered Main Board.....................................................5-8
Figure 5-7 dc-Powered Main Board.....................................................5-8
Figure 5-8 elay Option Board ............................................................5-9
Figure 5-9 4- elay Option Board.........................................................5-9
Figure 5-10 Analog Output Option Board ............................................5-10
Figure 5-11 S-232 Option Board .......................................................5-10
Figure 5-12 S-485 Option Board .......................................................5-10
Figure 5-13 BCD Option Board ............................................................5-11
Figure 5-14 Panel Mounting Assembly ................................................5-14
Figure 6-1 S1 and S2 Jumper Locations on Signal Input Board..........6-1
Figure 6-2 ac Main Board Jumper Positions S3 and S4......................6-4
Figure 6-3 dc Main Board Jumper Positions S3 and S4......................6-5
Figure 7-1 Current Input Without Sensor Excitation ............................7-1
Figure 7-2 Current Input With Sensor Excitation .................................7-1
Figure 7-3 Voltage Input Without Sensor Excitation ............................7-2
Figure 7-4 3-Wire Voltage Input With Sensor Excitation......................7-2
Figure 7-5 4-Wire Voltage Input With Sensor Excitation......................7-3
Figure 7-6 Bridge Input with External Sensor Excitation .....................7-3
Figure 7-7 Potentiometer Connections with Internal Power Supply
and atio Measurement. ....................................................7-3
Figure 7-8 Potentiometer Connections With External Power Supply
and atio Measurement ( emove jumper S2-T) ...............7-3
v
Figures

Figure 7-9 AC Connector Wiring at P1 ................................................7-4
Figure 7-10 DC Connector Wiring at P1 ................................................7-4
Figure 8-1 S3 and S4 Main Board Jumper Positions...........................8-2
Figure 8-2 S1 and S2 Signal Input Jumper Positions ..........................8-3
Figure 8-3 Internally-Powered Bridge Input .........................................8-4
Figure 8-4 S3 and S4 Main Board Jumper Positions.........................8-16
Figure 8-5 S1 and S2 Signal Input Jumper Positions ........................8-16
Figure 8-6 Sensor Input Connections ................................................8-17
Figure 8-7 S3 and S4 Main Board Jumper Positions.........................8-28
Figure 8-8 S1 and S2 Signal Input Jumper Positions ........................8-29
Figure 8-9 Sensor Input Connections ................................................8-29
Figure 8-10 S3 and S4 Main Board Jumper Positions.........................8-41
Figure 8-11 S1 and S2 Signal Input Jumper Positions ........................8-42
Figure 8-12 Sensor Input Connections ................................................8-42
Figure 10-1 Setpoints 1 & 2 Action ......................................................10-2
Figure 10-2 Setpoints 3 & 4 Action ......................................................10-2
Figure 10-3 Process Deviation ............................................................10-4
Figure 10-4 High Deviation for both Active Above and Active Below...10-4
Figure 10-5 Low Deviation for both Active Above and Active Below....10-5
Figure 10-6 Band Deviation for both Active Above and Active Below..10-5
Figure 10-7 AL CNF Hysteresis ...........................................................10-6
Figure 12-1 Analog Option Board and Connection Diagram at P5......12-3
Figure 12-2 Isolated Analog Output Board Wiring Connections. .........12-5
Figure 13-1 BCD 40-Pin Cable Connector (P8)...................................13-1
Figure 13-2 BCD Option Board............................................................13-2
Figure 13-3 Address Programming Chart for 4 -line Address..............13-5
Figure 14-1 Dual elay........................................................................14-1
Figure 14-2 4 elay Board Jumpers and Plugs...................................14-2
Figure 14-3 Dual elay Output Board Wiring Connections .................14-3
Figure 14-4 4 elay Output Board Wiring Connections.......................14-3
Figure 15-1 S-232/ S-485 Option Board and Pin Designations.......15-1
Figure 15-2a Older S-232 Option Board and Pin Designations ..........15-1
Figures
vi

Figure 15-2b Older S-485 Option Board and Pin Designations ..........15-1
Figure 16-1 Connector Label Detail.....................................................16-1
Figure 16-2 Connection of External Power for Setpoint Transistors....16-3
Figure 18-1 Meter Housing and Panel Cutout. ....................................18-4
Table 4-1 ear Connector Descriptions .............................................4-5
Table 8-1 Meter’s Natural Gain Chart.................................................8-5
Table 8-2 eading Scale ( DG SC) vs. Decimal Point Shift............8-13
Table 8-3 eading Scale ( DG SC) vs. Decimal Point Shift............8-26
Table 8-4 eading Scale ( DG SC) vs. Decimal Point Shift............8-39
Table 8-5 Meter’s Natural Gain Chart...............................................8-43
Table 8-6 eading Scale ( DG SC) vs. Decimal Point Shift............8-52
Table 14-1 Dual elay Board Jumpers ..............................................14-1
Table 14-2 4 elay Board Jumpers....................................................14-2
Table 14-3 Pin assignments for the P6, P7 and P18 plugs ................14-3
vii
Figures

Information that is especially important to note is identified by these labels:
• NOTE
• WARNING
• CAUTION
• IMPORTANT
NOTE: provides you with information that is important to successfully setup
and use the Programmable Digital Meter.
CAUTION or WARNING: tells you about the risk of electric shock.
CAUTION, WARNING or IMPORTANT: tells you of circumstances or
practices that can effect the meter's functionality and must refer to
accompanying documents.
Notes, Warnings, and Cautions
viii
Note ☞

1.1 DESCRIPTION
This Strain Gage meter is part of a complete line of process indicators/
controllers, offering exceptional performance.
The strain gage meter is front panel programmable to accept unipolar and
bipolar DC voltage inputs and 0-20 or 4-20 mAdc inputs. The meter will
accept inputs from most of the process sensors in use today such as
transmitters, pressure transducers, and potentiometers.
Configuring the meter is accomplished through the 5 front panel buttons. If
the RS-232 or RS-485 communication option is installed, the user may
remotely set the display parameters.
Options for the meter include analog and BCD outputs, relay outputs, and
RS-232 or RS-485 communications.
1.2 FEATURES
The following is a list of features of the meter.
• 6-digit LED display in red or green
• 0.005% accuracy of reading
• 12 DC input ranges: 0-100 mV, 0-1 V, 0-5 V, 1-5 V, 0-10 V, 0-100 V,
±50 mV, ±500 mV, ±5 V, ±50 V, 0-20 mA, or 4-20 mA
• 1.5 to 11 or 24 V dc sensor excitation
• Peak & Valley detection and memory
• Tare
• Up to 13 readings per second
• 4 isolated open collector outputs (standard) and optional isolated relay or
isolated BCD and isolated analog outputs
• Optional isolated RS-232 or RS-485 communications
• NEMA 4 Front Panel/IP65
• Non-volatile memory without battery back-up
• 115 Vac, 50/60 Hz, 230 Vac, 50/60 Hz power supply
• Optional 10-32 Vdc power supply
1-1
Introduction 1

1.3 AVAILABLE MODELS
The following models and options are available. Optional boards are either
installed at the time of purchase, or available as separate items and installed
by the user after purchase.
MAIN ASSEMBLIES
MODEL
NUMBER DESCRIPTION
DP41-S Red LEDs, 115 V ac, 50/60Hz
DP41-S-230 Red LEDs, 230 V ac, 50/60Hz
DP41-S-GN Green LED’s, 115 V ac, 50/60 Hz
DP41-S-230-GN Green LED’s, 230 V ac, 50/60Hz
DP41-S-DC Red LEDs, 10-32 V dc
DP41-S-DC-GN Green LED’s, 10-32 V dc
NOTE: The following options are available installed at the time of purchase
or as separate items installed by the user after purchase:
Analog Output Board, BCD Output Board, Relay Output Board, RS-232
Communications Board, and RS-485 Communications Board.
CONTROL/BCD OUTPUT OPTIONS
MODEL
NUMBER DESCRIPTION
- Standard four open-collector outputs are standard
DP40-B Isolated BCD Output Board
DP40-R Dual A Form-C Relays
DP40-R4 Dual A & Dual 1A Form-C Relays
NOTE: Choose only one Control/BCD output option per meter. A 40-pin
mating connector is included with the BCD option.
ANALOG OUTPUT
MODEL
NUMBER DESCRIPTION
- None
DP40-A Isolated configurable analog (4-20 mA, 0-1, 0-5, 1-5,
0-10 V dc, 0-20 mA) output
1Introduction
1-2
Note ☞
Note ☞

SERIAL COMMUNICATIONS OPTION
MODEL
NUMBER DESCRIPTION
DP40-S2 * Isolated RS-232 Communications
DP40-S4 ** Isolated RS-485 Communications
NOTES: Choose only one option per meter. Both computer communications
comes with 6 ft. communications cable with phone plug termination.
Free configuration software is available from www.omega.com or on the
CD-ROM enclosed with your shipment.
* Recommend purchase of DP40-9SC2 or DP40-25SC2
(see OPTIONS below)
** Recommend purchase of DP40-9SC4 or DP40-25SC4
(see OPTIONS below)
OPTIONS
MODEL
NUMBER DESCRIPTION
DP40-9SC2 9-pin Serial Connector for RS-232
DP40-9SC4 9-pin Serial Connector for RS-485
DP40-25SC2 25-pin Serial Connector for RS-232
DP40-25SC4 25-pin Serial Connector for RS-485
SPC4 1/8 DIN NEMA 4 heavy duty cover with thumb screws
SPC18 1/8 DIN NEMA 4 Splash Proof lens cover with spring clip
1-3
Introduction 1
Note ☞

Unpack all items and make sure that every item on the packing list is
present. The items you should receive are listed below. If something is
missing, use the phone number for the Customer Service Department
nearest you.
Also, inspect the shipping container and enclosed equipment for any signs of
damage. Take particular note of any evidence of rough handling in transit.
Immediately report any damage to the shipping agent.
NOTE: The shipping agent will not honor any claims unless all shipping
material is saved for their examination. After examining and removing
contents, save all packing material and containers in the event that
reshipment is required.
When you ordered your process meter, you will receive the following items in
the shipping box:
QTY DESCRIPTION ILLUSTRATION
1 Basic Meter in a Mounting
Sleeve with Gasket
1 Front-Panel Button Cover
AC Power Connector
(orange - P1)
2 Input Connectors
(gray - P3 and P9)
2Unpacking
2-1
1
2
3
P1
N
L
1
2
3
Note ☞

1 Rear Protective
Cover with Screw
1 20-Socket Ribbon
Connector
(P2 Connector)
2 Panel-Mounting
Gaskets (1 Spare)
1 Strain Gage Owner’s Guide
1 Quick Start Manual
Other items may also be in the box depending on the options ordered. Refer
to specific options described previously.
2-2
Unpacking 2

3.1 SAFETY CONSIDERATIONS
This device is marked with the international caution symbol. It is important to read
this manual before installing or commissioning this device as it contains important
information relating to Safety and EMC (Electromagnetic Compatibility).
Unpacking & Inspection
Unpack the instrument and inspect for obvious shipping damage. Do not attempt to
operate the unit if damage is found.
This instrument is a panel mount device protected in accordance with Class I of EN
61010 (115/230 AC power connections), Class III for the DC power option (10-32Vdc).
Installation of this instrument should be done by Qualified personnel. In order to ensure
safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-breaker shall be included
in the building installation as a disconnecting device. It shall be marked to indicate this function,
and it shall be in close proximity to the equipment within easy reach of the operator. The switch or
circuit-breaker shall not interrupt the Protective Conductor (Earth wire), and it shall meet the
relevant requirements of IEC 94 –1 and IEC 94 -3 (International Electrotechnical Commission).
The switch shall not be incorporated in the mains supply cord.
Furthermore, to provide protection against excessive energy being drawn from the
mains supply in case of a fault in the equipment, an overcurrent protection device shall
be installed.
• The Protective Conductor must be connected for safety reasons. Check that the
power cable has the proper Earth wire, and it is properly connected. It is not safe
to operate this unit without the Protective Conductor Terminal connected.
Conductor Terminal connected.
• Do not exceed voltage rating on the label located on the top of the instrument
housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure instrument does
not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to
minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems
persist.
Failure to follow all instructions and warnings may result in injury!
Note ☞
3Safety Considerations
3-1
Note ☞

4.1 FRONT OF THE METER
The following is a brief description of each part of the front of the meter.
Figur 4-1. Front D tail
ITEM DESCRIPTION
1 –.8.8.8.8.8. or 8.8.8.8.8.8.
6-digit, 14 segment, alphanumeric 0.54” high LED display with
programmable decimal point.
2 SETPOINT LED
These LEDs, labeled 1 through 4, display the status of setpoints
1, 2, 3 (Alarm 1), and 4 (Alarm 2).
3SETPTS BUTTON
This button functions only in the run mode. When the
Setpoint/Alarm features are unlocked, pressing this button
sequentially recalls the previous setpoint settings to the display.
After the ‘MIN’ and ‘MAX’ buttons are used to alter those
values as desired, pressing the ‘SETPTS’ button, again, stores
these new values.
Unless the ‘SETPTS’ button is pressed, each of the four setpoint
values is displayed for approximately 10 seconds after the last
press of the ‘SETPTS’ button. Holding the ‘SETPTS’ button
depressed stalls this automatic sequence, retaining the most
recent setpoint number on the display.
SETPTS MAX MIN MENU RESET
1234
2 2 2
3 4 567
2
1
4-1
Parts of the Meter 4

ITEM DESCRIPTION
4/MAX BUTTON
During run mode, pressing this button displays the “HI RDG”
(peak reading) value that has occurred up to the moment the
‘MAX’ button is pressed. This peak reading flashes, to
distinguish its value from the current readings. Since this is a
dynamic peak reading, the value will change if the value
increases while reviewing it.
To return to display of the current readings without resetting the
peak-value memory to zero (0), press the ‘MAX’ button once
again.
To reset the peak-value memory (start a new peak determining
period), press the ‘RESET’ button once.
During the configuration mode, the ‘MAX’ button is used to
change the numerical value of the flashing digit displayed. For
submenu items, such as “L1C.1=0”, pressing the ‘MAX’ button
toggles the choice from “0” to “1”.
The meter allows rapid changes of a displayed numerical value
by making “0” the first value to occur when the ‘MAX’ button is
pressed. After that, the numbers increase to “9” and then roll
over to “0” again. A negative (“–”) symbol may be displayed in
the most significant digit (i.e. the digit at the far left such as
shown here “–.8.8.8.8.8.”)
In the SETPT (SETPOINT) mode (SP1, SP2, etc), pressing the
‘MAX’ button causes the flashing digit to increment by 1 from 0
to 9.
5 /MIN BUTTON
During run mode, pressing the ‘MIN’ button recalls the “LO
RDG” (valley reading) measured since the last press of the
‘RESET’ button. This lowest value flashes, to distinguish it from
the current process display. Since this is a dynamic valley
reading, the value will change if the value decreases while
reviewing it.
4Parts of the Meter
4-1

ITEM DESCRIPTION
To return to the actual process display, without resetting the low-
value memory, press the ‘MIN’ button once again.
To reset the memory for current-value readings (start a new
observation period), press the ‘RESET’ button once and the
meter will return to the run mode.
In the configuration mode, once in a submenu (like input type)
the ‘MIN’ button allows you scroll through the available choices
such as, 0-20 mA or 4-20 mA, etc.
In the SETPT mode, the ‘MIN’ button advances the flashing digit
to the right.
6MENU BUTTON
In the run mode, this button terminates the measurement
process and allows you to enter the configuration mode,
advancing through the configuration menus.
In the configuration mode, this button will store changes in the
non-volatile memory at the same time advancing the display to
the next menu item.
RESET BUTTON
In the run mode, pressing the ‘RESET’ button once erases the
memories of peak (“HI RDG”), valley (“LO RDG”), and ALARM
latches. The display then returns to the run mode.
WARNING: Pressing the ‘RESET’ button two (2) times will
result in a hard reset of the meter. This will clear the Peak &
Valley, Alarm latches and meter reading and immediately begin
a new measurement.
In the configuration mode, pressing the ‘RESET’ button once,
displays the previous selection. For example, if you were in
“IN CNF” then pressed the ‘RESET’ button once, the display will
then show “RD.SC.OF”. Press the ‘RESET’ button two times to
return to the run mode.
4-2
Parts of the Meter 4

4.2 REAR OF THE METER
The following is a brief description of each part of the rear of the meter. The
label on the top of the mounting sleeve (not the case) identifies the location
of the connectors found at the rear of the meter. Figure 4-2A & figure 4-2B
shows this label.
Figur 4-2A. AC Pow r - Conn ctor Lab l for R ar Conn ctors
P2 / CABLE CONNECTOR
TARE(T) 1
VALLEY(V) 3
DIG RTN 7
PEAK/VALLEY OR EXT RESET 5
DISPLAY HOLD 9
RESET ALARMS AND/OR 9
PRINT COMMAND 11
NONSTANDARD TX 13
+V EXT 15
SP2 17
AL2 19
2 PEAK(P)
4 SWLIN2
6 PUSH TO CAL
8 +5V
LOCKOUT EEPROM &
MENU PUSH BUTTON
12 NONSTANDARD RX
14 PUSH TO CAL
16 SP1
18 AL1
2 RTN EXT
P4 / RS232
6 N/C
5 COMM RTN
4 RX
3 TX
2 RTS
1 N/C
P4 / RS485
6 N/C
5 B,-RX
4 A, +RX
3 COMM RTN
2 B, -TX/RX
1 A, +TX/RX
P5 / ANALOG OUT
1 RETURN
2 4-20MA
3 0-10V
P6 / RELAY P7 / RELAY
P7
P1 P2 P3
P4 P5
P6 P9
1 2 3 1 2 3
NO1
CM1
NC1
NO2
CM2
NC2
1 2 3 4 5 6
* P18 / 4RELAY
NO3
CM3
NC3
NO4
CM4
NC4
+E
+S
- S
- E
+R
- R
CONNECT TO LOW VOLTAGE LIMITED ENERGY CIRCUITRY ONLY.
LINE L
NUETRAL N
GND
P1 / AC
POWER
P8 / BCD (see manual for pinout) P9&P3 / SIGNAL IN
1
1
1
1
1
1
11P8 or P16
19
* NOT AVAILBALE
WITH=DC POWER
1
11
4Parts of the Meter
4-3
Other manuals for DP41-S
1
This manual suits for next models
5
Table of contents
Other Omega Touch Panel manuals
Popular Touch Panel manuals by other brands

YASKAWA
YASKAWA VIPA HMI TP 62I-JID0 manual

Avalue Technology
Avalue Technology APC-2138 Quick reference guide

SKYDANCE
SKYDANCE T15 user manual

Renu Electronics
Renu Electronics WP6101TN Plus quick start guide

Advantech
Advantech UTC-515 user manual

IEI Technology
IEI Technology AFL2D-12A-N270-ECIL user manual