ONEAC Sinergy Series User manual

ONEAC Sinergy UPS User Manual i
Sinergy™ Series User Instruction Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
Please read and save these instructions. This manual contains important instructions for ONEAC models:
• S700A
• S1000XA
• S2000XA
• S3000XA
• SBP1000
• SBP3000
Follow these instructions during installation and maintenance of the UPS and batteries.
If you have a problem with the UPS, please refer to this manual before calling the Technical Support
Department. The Troubleshooting section on page 28 addresses most UPS-related issues.
FCC Compliance
ATTENTION:
Changes or modifications to this unit not expressly approved by the party responsible or in FCC
compliance could void the user’s authority to operate the equipment.
This equipment was tested and complies with the limits for a ClassA digital device, pursuant to Part 15 of FCC Rules.These
limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial
environment. The UPS generates, uses, and can radiate radio frequency energy. If installation and use is not in accordance
with the instruction manual, it may cause harmful interference to radio communications.
ATTENTION:
Operation of this equipment in a residential area may cause harmful radio communications
interference. The user is responsible for correcting the interference.
913-459 Rev. D1
ONEAC USA
27944 North Bradley Road
Libertyville, IL 60048-9700
USA
Telephone: (847) 816-6000
Toll Free: (800) 327-8801
Facsimile: (847) 680-5124
ONEAC EUROPE
George Curl Way
Southampton, Hampshire SO18 2RY
United Kingdom
Telephone: +44 (0) 2380 610311
Facsimile: +44 (0) 2380 612039
• S700A-RM
• S1000XA-RM
• S2000XA-RM
• S3000XA-RM
• SBP1000-RM
• SBP3000-RM
• SE61XA (SE41XA)
• SE101XA (SE81XA)
• SE203XA (SE153XA)
• SBPE61
• SBPE101

ONEAC Sinergy Series UPS Manual i
Chapter 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Registering your ONEAC UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Technical Support and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Warning for SE61, SE101 and SE203 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chapter 2 Display and Operation Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Chapter 3 Rackmount Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Installation and operating notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Unit Rear View and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Chapter 4 Installation and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Installation of the S Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Installation of the SE Series (Hardwired) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Commissioning of the S Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Commissioning of the SE Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Commissioning of an External Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Chapter 5 Operational Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Ready for Operation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Self Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Chapter 6 Description of the Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Standard Interface COM A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Optional Interface COM B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Emergency Power Off (EPO) (Model SE203X only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Chapter 7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Chapter 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Chapter 9 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
ONEAC Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Chapter 10 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Battery Lifetime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Typical Emergency Supply Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45

ONEAC Sinergy UPS User Manual 1
Chapter 1 Introduction
Thank you for selecting this uninterruptible power supply (UPS). ONEAC’s Sinergy Series offers the most
reliable protection from the harmful effects of electrical line disturbances for your computing and
communications equipment.
ONEAC’s ISO 9001 certification represents our commitment to building world-class products. We take
pride in every unit that leaves our manufacturing facility.
1.1 Registering your ONEAC UPS
To ensure that your Sinergy Series model and serial number are registered, complete and mail the enclosed
postage-paid warranty card or go online at www.oneac.com.
1.2 Technical Support and Service
ONEAC offers 24-hour technical support. To contact ONEAC Technical Services:
• North America: (800) 327-8801 (opt. 3) or (847) 816-6000 (opt. 3)
• Europe: +44 (0) 1235 861962
NOTE:
All calls received before 7 a.m. or after 7p.m. Central Standard Time are forwarded to a cell phone.
An ONEAC Technical Service Representative will return your call within one half hour between 5 p.m. and
10 p.m. Central Standard Time. Except for emergencies, calls received between 10 p.m. and 7 a.m. will be
returned during normal business hours.
Please check with ONEAC Technical Services before attempting to repair or return any ONEAC product.
If an ONEAC unit needs repair or replacement, ONEAC Technical Services issues a Return Material
Authorization (RMA) number along with instructions on how to return the unit.
1.3 Safety Notes
WARNING:
Read the following information carefully! Disregard of these safety notes may endanger
your life and health as well as the functioning of your equipment and the safety of your data.
WARNING:
This equipment services power from more than one source. The output receptacles may
have voltage even when the unit is unplugged.
UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode.
Unplugging the UPS does not remove the electrical charge. To ensure that the UPS is off, push BYPASS (for a minimum of
1 second) before unplugging the UPS from the mains.
CAUTION:
Operating this equipment without proper grounding may present a risk of electrical shock.
Do not use AC adaptors with only two conductors to connect the input line cord to the wall socket as this will not connect
the earth ground to the equipment.
WARNING:
Dangerous voltages are present within this unit! There are no user-serviceable parts
inside. Any repairs or modifications by the user may result in out-of-warranty repair charges, unsafe
electrical conditions, or violation of electrical code.

2 ONEAC Sinergy UPS User Manual
This device complies with the relevant safety regulations for uninterruptible power supplies for use in a
controlled office environment. If you have any questions, please contact ONEAC Technical Service at
1- 800-327-8801 Opt. 3 or 1-847-816-6000, Opt. 3.
• Transport the unit only in suitable packaging (protect against jolts and shocks).
• If the equipment is moved indoors from a cold environment, condensation may occur. Before you place
the equipment in service it must be absolutely dry. An acclimatization period of at least two hours is
required.
• This equipment must be installed in an indoor, temperature controlled environment that is free of
conductive contaminants. See chapter 10, “Specifications” on page 30 for specific environmental
limits.
• This equipment has a safety-tested power cable and may only be connected to a properly grounded
receptacle. The special conditions for installing the hard-wired devices SE61, SE101 and SE203 in
chapter 4, “Installation and Commissioning” on page 13 must be observed.
• The switch (see chapter 2, “Display and Operation Elements” on page 3) does not isolate the
device (UPS) from the mains. To isolate completely from the mains, the main switch must be switched
off and the power plug disconnected.
CAUTION:
Removing mains power may not remove power from the device (UPS) output. See instructions above to
properly remove power from output.
• In case of interruption of the mains voltage, the integrated battery maintains the power supply to the
connected equipment.
• Lay all cables so that nobody can stand on them or trip over them. When connecting the device to the
power supply, follow the instructions in the chapter on “Installation and Commissioning” on page 13.
• No data transmission lines should be connected or disconnected during a thunderstorm.
• Make sure that no objects (e.g. pins, necklaces, paper clips, etc.) get inside the device.
• In emergencies (e.g. damaged case, controls or power cables, penetration of liquids or foreign matter)
put the device into BYPASS, disconnect the power plug and contact ONEAC Technical Services at
1-800-327-8801 Opt. 3 or 1-847-816-6000. The special conditions for installing the hardwired devices,
SE61, SE101 and SE203 are in chapter 4, “Installation and Commissioning” on page 13.
• Do not connect equipment that will overload the UPS (e.g. laser printers or vacuum cleaners) or
demand DC-current (e.g. half-wave rectifiers or hair dryers).
• When cleaning the unit, follow the instructions in chapter 7, “Maintenance” on page 27.
• The sum of the leakage currents (protective conductor current) of the UPS and the connected devices
must not exceed 3.5 mA for the types S700, S1000, S2000 and S3000.
ONEAC Sinergy UPSs are UL listed under UL1778 for North American units.
1.4 Warning for SE61, SE101 and SE203
This product may only be sold to users with qualified personnel. In order to avoid RF, restrictions for
installation or additional precautions may apply.

ONEAC Sinergy UPS User Manual 3
Chapter 2 Display and Operation Elements
The Uninterruptible Power System (UPS) is connected betweenAC power and the load. It protects the load
against mains disturbances, especially power failures.
Its operation is based on the on-line principle. The connected load is supplied power through the UPS’s
inverter. Power disturbances from the mains are suppressed which increases the loads’operational security
(PC, network server, multi-user systems etc.)
In the event of a mains failure, maintenance-free batteries provide an uninterrupted supply of energy. In
practice, mains failures are of relatively short duration, dependent on the mains quality. Therefore, the UPS’
energy is in most cases sufficient to ensure continuous operation of the connected systems, until the mains
is reestablished. In the event of a longer lasting mains failure it allows for controlled shutdown of connected
systems.
The UPS indicates by acoustical (buzzer) and optical (LED) alarms that a mains failure has occurred and is
still persistent. Battery runtimes vary depending upon load, number of batteries and environmental
conditions.
The following chart shows the approximate values of the emergency runtime (assuming fully charged
battery at the onset of the mains failure.)
• The actual battery capacity can be read from the LED-”battery” chain (see table below).
The most reliable method for determining actual battery runtime is the application of ONEAC MopUPS
®
software. With this software, the prospective remaining battery capacity is indicated before and during an
AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application
program, operating system and computer hardware, it can be ensured that in the event of a power failure the
application programs are automatically closed, the subscribers logged in at the server are logged out, the
data is stored and the operating systems are shut down. For further information please refer to our
publication about the ONEAC ManageUPS™
NET
SNMP Adapter.
After return of the mains voltage, the UPS automatically initiates a restart. The connected systems are
restarted according to their specifications.
In the event of overload or internal failure, the load is supplied from the mains via an automatic bypass.As
soon as the normal status is reestablished, automatic switchover to inverter operation is performed.
This operation manual contains all relevant information to install and operate the UPS.
Load in % S700 S1000 S2000 S3000 SE61 SE101 SE203*
OVERLOAD >105 w/SBPE101
95-105 6 min 7 min 10 min 6 min 9 min 12 min 15 min
LOAD 75-95 7 min 8 min 11 min 7 min 10 min 13 min 20 min
55-75 10 min 11 min 16 min 10 min 13 min 19 min 25 min
35-55 15 min 17 min 24 min 15 min 21 min 25 min 45 min
1-35 28 min 33 min 37 min 28 min 40 min 40 min 90 min
N
OTE: *Model SE203 does not contain internal batteries.
Battery Capacity
Battery 1 - 35%
35 - 55%
55 - 75%
75 - 95%
95 - 100%

4 ONEAC Sinergy UPS User Manual
2.1 Front
NOTE:
To switch from BYPASS to INVERTER, press the | switch for at least 1 second. (A tone sounds
confirming the switch).
The OVERLOAD indicator is on when the UPS is overloaded.
The LED-chain LOAD indicates the load state of the UPS.
The BYPASS indicator is on when the UPS supplies a voltage via the bypass.
The INVERTER indicator is on when the inverter is in operation.
The LED-chain BATTERY indicates the battery’s charge state (normal operation)
or the % of battery time remaining when mains fail.
The LINE indicator is on when there is mains voltage at the UPS input.
The ALARM indicator is on when the UPS is faulty. Simultaneously, an acoustical
signal is given, which can be reset by pressing the BYPASS switch.
The switch switches the inverter off and the bypass on. The UPS still has output
voltage.
Operating the switch | activates the inverter. After a delay of approximately 5
seconds the BYPASS indicator extinguishes and the INVERTER indicator
illuminates.

ONEAC Sinergy UPS User Manual 5
2.2 Rear
2.2.1 Type S700 and S1000
Fig. 1: S700 Rear View
Fig. 2: S1000 Rear View
* Call ONEAC Technical Services for information on setting output voltages (1-800-327-8801, opt. 3
or +1-847-816-6000).
Selector switch
Interface COM A
Interface COM B (optional)
Fan
Input fuse
Mains connection
Output receptacles
Selector switch - for output voltage. The
selection of the output voltage must be made
with the UPS switched off and unplugged.*
Input fuse - the fuse may only be changed
when the device is switched off and unplugged.
Selector switch
Interface COM A
Interface COM B (optional)
Connection for additional batteries
Fan
Input fuse
Mains (input) connection
Output receptacles
Selector switch - for output voltage.
The selection of the output voltage must be
made with the UPS switched off and unplugged.*
Input fuse - the fuse may only be changed
when the device is switched off and unplugged.

6 ONEAC Sinergy UPS User Manual
2.2.2 Type S2000 and S3000
Fig. 3: S2000 Rear View
Fig. 4: S3000 Rear View
* Call ONEAC Technical Services for information on setting output voltages
(1-800-327-8801, opt. 3 or +1-847-816-6000)
Selector switch
Interface COM A
Interface COM B (optional)
Connection for additional batteries
Fans
Output Receptacle
Output Receptacle Fuses
Input circuit breaker
Linecord
Output receptacles
Selector switch - for output voltage.
The selection of the output voltage must be
made with the UPS switched off and unplugged.*
Selector switch
Interface COM A
Interface COM B (optional)
Connection for additional batteries
Fans
Output Receptacle
Circuit Breakers
Input circuit breaker
Output receptacles
Linecord
For output voltage
The selection of the output voltage must be
made with the UPS switched off and unplugged.*

ONEAC Sinergy UPS User Manual 7
2.2.3 Type SE61 and SE101
Fig. 5: SE41 or SE61
Fig. 6: SE81 or SE101
* Call ONEAC Technical Services for information on setting output voltages
(1-800-327-8801, opt. 3 or +1-847-816-6000)
Selector switch
Interface COM A
Interface COM B (optional)
Fans
Output circuit breaker
External battery connector
Input circuit breaker
Optional PDU
Selector switch - for output voltage
The selection of the output voltage must be
made with the UPS switched off.*
(SE61 with optional PDU shown)
Selector switch
Interface COM A
Interface COM B (optional)
Fans
Output circuit breaker
Input circuit breaker
Mains fuse and
Battery switch
Optional PDU
Selector switch - for output voltage
The selection of the output voltage must be
made with the UPS switched off.*
(SE101 with optional PDU shown)

8 ONEAC Sinergy UPS User Manual
2.2.4 Type SE203
Fig. 7: SE203
* Call ONEAC Technical Services for information on setting output voltages
(1-800-327-8801, opt. 3 or +1-847-816-6000)
Selector switch (must be set to 230 V)
EPO connection
Interface COM A
Interface COM B (optional)
Fans
Output circuit breaker
Input circuit breaker
Maintenance bypass switch
Wiring box cover
(or optional PDU)
Selector switch - for output voltage
The selection of the output voltage must be
made with the UPS switched off.*

ONEAC Sinergy UPS User Manual 9
Chapter 3 Rackmount Series
The technical data of the Sinergy Series Rackmount UPS corresponds to the standard unit series Sinergy,
except for the details which are explained below. The Sinergy Series Rackmount consists of the following
types:
• S700-RM, with 700 VA nominal rating
• S1000-RM, with 1000 VA nominal rating
• S2000-RM, with 2000 VA nominal rating
• S3000-RM, with 3000 VA nominal rating,
• SBP1000-RM
• SBP3000-RM
The above listed units with a mounting height of 2 U (2 U = 3.50 inches) are designed for installation in a
standard 19-inch industrial rack.
3.1 Safety
3.1.1 Intended use
This system, called “unit” in the following text, serves as an uninterruptible power supply of connected
loads in a 19-inch rack. In certain configurations battery packs are part of the unit. These battery packs may
only be connected electrically with the corresponding base unit.
3.1.2 Further safety notes
• When mounting the unit into a rack, it has to be attached on both sides and the front plate of the unit
has to be fixed to the rack by screws.
• There may be connected:
- up to 2 battery packs to the S1000-RM.
- up to 5 battery packs to the S2000-RM or S3000-RM.
• The vents for air intake and outlet at the front and rear side must not be obstructed.
3.2 Installation and operating notes
3.2.1 Selection of the mounting location
TheSinergy SeriesRackmountunits are designedtobemounted in a 19-inch rack.When installing the UPS,
please consider the heavy weight of some components. Preferably, they should be installed in the lower
sectionof the rack. UPS systems consisting of several components must be installed so that the batterypacks
are mounted in the lower section with the UPS mounted directly above them.

10 ONEAC Sinergy UPS User Manual
3.2.2 Mechanical Attachment
The units must be attached in the rack on both sides.When using the attached mounting rails, the single unit
can easily be inserted into a 2 U mounting space or removed from it. In order to attach the unit in the
horizontal position, the front-plate has to be attached to the 19-inch rack at the indicated points on both sides
of the unit.
Do not attach the unit only at the front-plate. This may damage the unit and/or other mounted units.
Fig. 8: Mounting the rails at the body of the UPS or Battery-Pack.
The following table shows the maximum configuration.
3.2.3 Connection of a battery pack
NOTE:
Before connecting a battery pack to the UPS, the miniature circuit breaker of the battery pack must
be switched to “OFF.” After electrical connection with the UPS, this breaker has to be switched “ON.”
NOTE:
The S2000-RM and S3000-RM have no internal batteries.
Table 1. Battery Cabinets
UPS Type of Battery Packs Maximum Number of Packs
S700-RM None None
S1000-RM SBP1000-RM 2 units
S2000-RM SBP3000-RM 5 units
S3000-RM SBP3000-RM 5 units

ONEAC Sinergy UPS User Manual 11
3.3 Unit Rear View and Connections
3.3.1 S700-RM and S1000-RM
The following figures show the S700-RM, S1000-RM, S2000-RM and S3000-RM with battery extensions.
NOTE:
No battery extension can be connected to the 700 VA unit.
Fig. 9: S700-RM
Fig. 10: S1000-RM
Fig. 11: Battery Pack - SBP1000-RM
To connect the battery pack to the unit, use the separate cable supplied.

12 ONEAC Sinergy UPS User Manual
3.3.2 S2000-RM and S3000-RM
NOTE:
Each battery cabinet SBP3000 contains two battery connections.The first battery pack is connected
to the battery cables of the UPS, each further extension is connected by means of the two cables. Each cable
is non-interchangeable, because the sockets are coded.
Fig. 12: S2000-RM
Fig. 13: Battery Pack - SBP3000-RM
3.3.3 S3000-RM
Fig. 14: S3000-RM
Fig. 15: SBP3000-RM

ONEAC Sinergy UPS User Manual 13
Chapter 4 Installation and Commissioning
Uponreceipt of your UPS, carefullyexaminethe packing containers for any sign of physical damage.Notify
the carrier immediately if damage is present. Carefully unpack the UPS. Retain the packaging for reuse or
dispose. Check the packing for damages.
NOTE:
If damages are detected, please inform the shipping agent immediately.
UPS includes:
• UPS device
• Connection cable for the UPS input (except SE61, SE101 and SE203)
• Output receptacles are on the UPS (except SE61, SE101and SE203)
• A recharging cable is connected to external battery cabinets SBPE61.
NOTE:
The casters on the types SE61, SE101 and SE203 are not suitable for moving the devices over a long
distance.
4.1 Installation of the S Series
Connect the UPS to a grounded wall receptacle.
CAUTION:
As soon as the UPS is connected to the AC mains, the output receptacles are energized, even if the UPS
is not yet switched on with the front-panel switch.
The LED indications “LINE” and “BYPASS” are illuminated.
4.2 Installation of the SE Series (Hardwired)
WARNING:
Only qualified electricians should install an ONEAC Sinergy SE61 (SE41), SE101,
(SE81)or SE203 (SE153) hardwired UPS. When installing the unit, follow applicable local and
national regulations (such as the U.S. National Electric Code), good wiring practices and this
manual.
1. Unpack and move Sinergy UPS and battery cabinet(s), if supplied, into desired installation location.
2. Adjust leveling jacks under the UPS and battery cabinet(s) to remove wheels of the units from the floor
and avoid movement of connections.
3. Turn off input and output breakers on the back of the UPS and any battery cabinets to be used.
4. Turn off and isolate the power source to be used for the UPS input using proper lock-out/tag-out
procedures.
5. Confirm that the power source to be used for the UPS is 208 V (208/120 3
φ
for SE203).
6. Remove the connection plate on the back of the UPS to expose connection terminals.
7. Wire input of the UPS by first connecting ground (earth) wire to GND (ground) terminal. Next, connect
the input power leads to L1/N and L2 (for SE61 and SE101) or L1, L2, and L3 (for SE203). See Table 2,
“Minimum Requirements for Sinergy Series UPS Installation,” on page 15 for minimum wire gauge,
wire temperature and screw torque requirements.
NOTE:
Always use grounding conductor that is equal to or larger in size than the current carrying

14 ONEAC Sinergy UPS User Manual
conductors.
8. If the UPS does not have an attached Power Distribution Unit (PDU), wire the output of the UPS to
appropriate load as follows:
Wire 208 V load between terminals marked 120A (x1) and 88B (x3).
Wire 120 V loads between terminals marked 0 (x2) and 120A (x1) or 0 (x2) and 120B (x4).
CAUTION:
The load connected to 120A and 120B must each be no more than 1/2 the nameplate rated 120V current.
User must properly fuse these outputs to this rating.
9. Connect the UPS to the battery cabinet(s) (if required)
See Table 2, “Minimum Requirements for Sinergy Series UPS Installation,” on page 15 for minimum
wire gage, wire temperature and screw torque requirements.
For model SE61 (if using an external battery cabinet), first remove the connection plate from the rear
of the battery cabinet, then connect the battery cable (supplied with the battery cabinet) from the
battery connector on the UPS to the terminals on the battery cabinet. Confirm that (+), (-) and GND
terminals are connected to proper wires. Connect any additional battery cabinets in a “daisy-chain”
manner until all GND terminals, (-) terminals and (+) terminals are connected together. See Table 2,
“Minimum Requirements for Sinergy Series UPS Installation,” on page 15 for minimum wire gage,
wire temperature and screw torque requirements.
For models SE101 and SE203, first remove the connection plate from the rear of the battery cabinet.
Next, connect the wires from GND terminal on the UPS to GND wire on the battery cabinet, and then
from (-) terminal on the UPS to the (-) terminal on the battery cabinet. Finally, connect (+) terminal
on the UPS to the (+) terminal on the battery cabinet. Connect any additional battery cabinets in a
“daisy-chain” manner until all GND terminals, (-) terminals and (+) terminals are connected together.
See Table 2, “Minimum Requirements for Sinergy Series UPS Installation,” on page 15 for minimum
wire gage, wire temperature and screw torque requirements.
10. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires
are pinched or damaged.
11. Confirm that all input and output breakers on the UPS and battery cabinet(s) are in the OFF position.
12. Restore power source to the UPS.
WARNING:
Make sure that all circuit breakers on the battery cabinet and UPS are in the“OFF”
postion before removing any covers.

ONEAC Sinergy UPS User Manual 15
Fig. 16: Wiring Diagram for the SE61
Fig. 17: Wiring Diagram for the SE101
NOTE:
120 A or 120B must be limited to 1/2 nameplate rated current. It is user’s responsibility to fuse or
breaker these outputs.
Table 2. Minimum Requirements for Sinergy Series UPS Installation
Term ID Description
SE61 (SE41) SE101 (SE81) SE203 (SE153)
Min.
Wire
Gauge
(awg)
Term
Torque
(in-lbs)
Min.
Wire
Temp.
(°C)*
Min.
Wire
Gauge
(awg)
Term
Torque
(in-lbs)
Min.
Wire
Temp.
(°C)*
Min.
Wire
Gauge
(awg)
Term
Torque
(in-lbs)
Min.
Wire
Temp.
(°C)*
GND Chassis Ground ** 40 75 ** 45 75 ** 45 90
L1/N Line 1 8 40 75 6 45 75 4 45 90
L2 Line 2 8 40 75 6 45 75 4 45 90
L3 Line 3 N/A N/A N/A N/A N/A N/A 4 45 90
120A 120 V from Neutral 10 35 75 6 45 75 4 45 90
0 Neutral 10 35 75 6 45 75 4 45 90
88B 208 V from 120A 10 35 75 6 45 75 4 45 90
120B 120 V from Neutral 10 35 75 6 45 75 4 45 90
GND Chassis Ground opt 35 75 opt 45 75 opt 45 90
+ +240 VDC to - N/A N/A N/A 4 45 75 4 45 75
- Battery Common N/A N/A N/A 4 45 75 4 45 75
GND Chassis Ground N/A N/A N/A 4 45 75 4 45 75
* Use insulated copper wire rated 75 C minimum.
** Must be no smaller than wire connected to L1/N and L2 (for SE61 and SE101) or L1, L2, L3 (for SE203).
GND L1/N L2 120A 0 88B 120B GND
208
120 120
LINE OUTPUT
X3 X4X2X1
GND L1/N L2 120A 0 88B 120B GND
208
120 120
LINE OUTPUT
+ - GND
BATTERY
X3 X4X2X1
LINEBATTERY OUTPUT

16 ONEAC Sinergy UPS User Manual
Fig. 18: Wiring Diagram for the SE153 and SE203
Fig. 19: SE203 Power System
NOTE:
120 A (X1-X2) or 120B (x2-x4) must be limited to 1/2 nameplate rated current. It is user’s
responsibility to fuse or breaker these outputs.
4.3 Commissioning of the S Series
When connected to the mains, the batteries automatically begin charging. The UPS may be used
immediately, however, full run time will not be available until the batteries are fully charged.
1. Before using the device, charge the batteries for 8 hours.
2. After charging, connect the loads to the UPS.
NOTE:
Do not connect any devices that overload the UPS or draw DC current from the UPS (e.g. hair
dryers, vacuum cleaners).
3. When the signal interface is used, then the connection cable (accessories) is linked between UPS and
computer system. Please see instructions in the documentation for the accessories.
4. Switch on the loads.
5. Switch on the UPS by operating the switch | on the front panel.

ONEAC Sinergy UPS User Manual 17
The “LINE” and “BYPASS” indicators and the “LOAD” (output load) indicator are illuminated.After a few
seconds the “INVERTER” indicator illuminates and the “BYPASS” indicator turns off. The UPS is now in
ON-LINE operation.
NOTE:
If the “LOAD” indicator is beyond 100%, then too many devices are connected to the UPS. If only
one device is connected to the UPS, then its energy demand exceeds the nominal rating of the UPS, which
means that a UPS with a higher power rating has to be used.
An overload alarm signal (1 signal per second) is heard.
NOTE:
The UPS devices may be commissioned even without being supplied by the grid. The batteries,
however, should be charged sufficiently (see above).
4.4 Commissioning of the SE Series
NOTE:
Confirm mains voltage is 208 VAC forSE61 and SE101and 208/120 VAC 3
φ
for SE203.
1. Switch on the input circuit breaker on the back of the UPS.
WARNING:
As soon as the UPS is connected to the AC mains, the output receptacles are energized,
even if the UPS is not yet switched on with the front-panel switch.
The “LINE” and “BYPASS” LED indicators are illuminated.
2. When connected to the mains, the batteries automatically begin charging. The UPS may be used
immediately, however, full run time will not be available until the batteries are fully charged
3. Before using the device, charge the batteries for 8 hours.
4. After battery charging is completed, switch on the output circuit breaker at the rear side of the UPS.The
loads are now supplied by the UPS.
NOTE:
Do not connect any devices that overload the UPS or draw DC current from the UPS (e.g. hair
dryers, vacuum cleaners).
5. If a signal interface cable is used, connect the cable (accessory) between the UPS and the computer
system. Please observe further instructions in the documentation for the accessory.
6. Switch on the loads.
7. Switch on the UPS by operating the switch | at the front plate.
NOTE:
If unit will not switch on, confirm that the batteries are properly connected to the unit and any
battery breakers are “ON.”
The “LINE” and “BYPASS” indicators and the “LOAD” (output load) indicator are illuminated.After a few
seconds the “INVERTER” indicator illuminates and the “BYPASS” indicator turns off. The UPS is now in
ON-LINE operation.
NOTE:
If the “LOAD” (output load) indicator is beyond 100%, then too many devices are connected to the
UPS. If only one device is connected to the UPS, then its energy demand exceeds the nominal rating of the
UPS, which means that a UPS with a higher power rating has to be used.
An overload alarm signal (1 signal per second) is heard.

18 ONEAC Sinergy UPS User Manual
4.5 Commissioning of an External Battery Cabinet
The following table shows the designations of the battery cabinets which are available for the UPS devices.
Disconnect the UPS from the mains and the loads from the UPS.
CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.
CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.
Connect the battery cabinet types SBP1000, SBP3000 and SBPE61 to the UPS using the supplied cable.
The connection scheme is shown in the figures below. With type SBPE101, make the hard-wired connection
between UPS and the battery cabinet (see figure 22 and 23 on page 20).
Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.
NOTE: Battery charging times may be longer when using an external battery cabinet.
WARNING:
Fig. 20: Connection of Battery Extensions for devices S1000
Table 3. External Battery Packs
Model Cabinet Batteries
S700 NA NA
S1000 SBP1000 2x (3x7. 2 Ah)
S2000 SBP3000 2x (8x7. 2 Ah)
S3000 SBP3000 2x (8x7. 2 Ah)
SE61 (SE41) SBPE61 2x (20x7. 2 Ah)
SE101 (SE81)/
SE203 (SE153) SBPE101 1x (20x38 Ah)
Battery Plug 1
Circuit Breaker
Battery Plug 2
This manual suits for next models
20
Table of contents
Other ONEAC UPS manuals

ONEAC
ONEAC ONePlus Series Operator's manual

ONEAC
ONEAC ON Series User manual

ONEAC
ONEAC ONm 300 I Operator's manual

ONEAC
ONEAC ONE404AG-SE Operating instructions

ONEAC
ONEAC ON Series Operator's manual

ONEAC
ONEAC S07KXAU User manual

ONEAC
ONEAC ON Series Operator's manual

ONEAC
ONEAC SE041XAT Operator's manual

ONEAC
ONEAC ON Series Operator's manual
Popular UPS manuals by other brands

Huawei
Huawei UPS2000-G-3KRTL-V2 user manual

OPTI-UPS
OPTI-UPS RS650B Specification sheet

MGE UPS Systems
MGE UPS Systems Pulsar Extreme 3200C Installation and user manual

ReDeal
ReDeal ZP120N user manual

Toshiba
Toshiba 1600XP SERIES Installation and operation manual

Eaton
Eaton 9315 Installation and operation manual