ONEAC ONm 300 I Operator's manual

ON Series m UPS
ON Series m UPS User Instruction Manual 1
ON Series m
UPS
Please read and save these instructions.This manual
contains important instructions for the ON Series m
UPS family. Follow these instructions during the
unpacking, installation and maintenance of the
Uninterruptible Power Supply (UPS) and batteries.
If you have a problem with the UPS, please refer to
this manual before calling Technical Services. The
Troubleshooting Section starting on page 16
addresses most UPS-related issues.
Introduction
Thank you for selecting this uninterruptible power
supply (UPS). ONEAC’s ON Series offers the most
reliable protection from the harmful effects of
electrical line disturbances for your computing and
communications equipment. ONEAC’s ISO 9001
certification represents our commitment to building
world-classproducts.Wetakeprideineveryunitthat
leaves our manufacturing facility
Technical
Support
ONEAC
®
offers 24-hour technical support. To
contact ONEAC Technical Services:
• North America: (800) 327-8801 (opt. 3) or
(847) 816-6000 (opt. 3)
• Europe: +44 (0) 2380 610311
NOTE:
Allcallsreceivedbefore 7 a.m. or after7p.m.
Central Standard Time are forwarded to a cell
phone.AnONEACTechnicalSupportRepresentative
will return your call within one half hour between 5
p.m. and 10 p.m. Central Standard Time. Except for
emergencies, calls received between 10 p.m. and 7
a.m. will be returned during normal business hours.
Please check with ONEAC Technical Services
before attempting to repair or return any ONEAC
product. If an ONEAC unit needs repair or
replacement, ONEAC Technical Services issues a
ReturnMaterialAuthorization(RMA)numberalong
with instructions on how to return the unit.

Safety
2 ON Series m UPS User Instruction Manual
Safety
Class 1 equipment
Equipmentnot suitable for useinthepresence
of a FLAMMABLE ANESTHETIC MIXTURE
WITH AIR or WITH OXYGENOR NITROUS
OXIDE.
Not designed, intended or authorized for use in
systems intended to support or sustain life.
For more details on life critical applications please
refer to full disclaimer in AppendixA: Warranty on
page 18 at the end of this manual.
WARNING:
This equipment services power from
more than one source. The output receptacles may
have voltages present even when the unit is
unplugged.
UPSs present a different safety issue than most
electrical equipment because unplugging the UPS
puts it into backup mode. Unplugging the UPS does
not remove the electrical charge. To ensure that the
UPS is off, turn the power switch “OFF” before
unplugging the UPS from the wall outlet.
CAUTION:
This unit is intended to be used in a
system that has a grounded neutral conductor.
CAUTION:
Operating this equipment without
proper grounding may present a risk of electrical
shock.
Do not useAC adaptors with only two conductors to
connect the input line cord to the wall socket as this
will not connect the earth ground to the equipment.
WARNING:
Dangerous voltages are present within
this unit! There are no user-serviceable parts inside.
Any repairs or modifications by the user may result
in out-of-warranty repair charges, unsafe electrical
conditions, or violation of electrical code.
Do not remove the cover. All repairs should be done
by qualified service personnel. Voltages inside the
UPS may be lethal. Internal components are
poweredevenwhenthepowerswitch is in the “OFF”

Features
ON Series m UPS User Instruction Manual 3
position. Even with the battery disconnected and the
unit unplugged, energy is stored in high voltage
capacitors and represents a severe shock hazard.
Features
The ON Series m UPS models are listed for
UL2601-1andCSA-C22.2complianceandcarrythe
CE Mark for testing to the EN60601-1 standard for
Medical Electrical equipment. Designs are
compliant with all specification parameters for Class
I, equipment (such as earth leakage and enclosure
leakage currents). Units are available in 120 V and
230 V 50/60 Hz with IEC connectors to facilitate
country-specific connector compatibility or NEMA
5-15R receptacles on the “A” models.An optically
isolated communications interface is standard.
Your ONEAC ON Series m UPS features full output
isolationandpowerconditioningwithVirtualKelvin
Ground
®
output filtering. This provides the highest
level of protection from power line disturbances
available.
Intelligent battery management system includes:
• Battery condition monitoring and status alerts
• Low battery indication
• Hot-swap, user-replaceable battery
• Battery charge indication
• ONBoost
®
, low line voltage compensation
without battery depletion
• Controlled inverter shutdown if battery is
depleted
ONEAC UPSs also feature a five-year warranty. See
Appendix A, page 18 for full warranty details.
See Appendix B: Typical Runtime on page 20 for
battery runtimes. Full product specifications are
available in Appendix C: Specifications and
Characteristics on page 21.

Unpacking and Inspection
4 ON Series m UPS User Instruction Manual
Unpacking and
Inspection
Before shipment, this product was tested, inspected
and found to be free of mechanical and electrical
defects. Upon receipt of your UPS, carefully
examine the packing containers for any sign of
physical damage. Notify the carrier immediately if
damage is present. After inspecting, carefully
unpack the UPS. Retain the packaging materials for
reuse or dispose of the materials properly. Once
unpacked, inspect and test the unit for hidden
damage that may have occurred in transit. If damage
is evident, contact ONEAC Technical Services.
Installation
When selecting a location for your UPS, be sure that
the unit is near a properly wiredAC electrical outlet
and is easily accessible for all other connections.
Leave at least 2 inches of clearance on each side of
the UPS for proper ventilation.
CAUTION:
Do not cover or install the UPS in a
confined or enclosed space.
Changing Frequency
This ON Series m UPS was designed to operate at
frequencies of either 50 Hz or 60 Hz.
The table below shows the frequency settings as
shipped from the factory.
If an adjustment is necessary, perform the following:
CAUTION:
Before proceeding, be sure the UPS is
“OFF” and disconnected from the utility power.
Table 1. Frequency Settings
Model From Factory AdjustableTo
ONm 300 I, ONm 600 I 50 Hz 60 Hz
ONm 300 J, ONm 600 J 60 Hz 50 Hz
ONm300 A, ONm600 A 60 Hz 50 Hz

Installation
ON Series m UPS User Instruction Manual 5
1. Lay the UPS on its right side.
2. Remove and retain the two Phillips head screws
at the bottom front of the unit that secure the
battery access door (fig. 1).
3. Carefully open the access door, then slide the
batteries out of the unit.
WARNING:
Do not contact the exposed battery
terminals due to the presence of electrical charge.
4. The frequency selector switch, located at the top
of the UPS battery access panel, can be set to the
desired frequency using a small, standard
screwdriver or similar tool (fig. 1).
fig. 1: Frequency Selector Switch
5. Circle the selected frequency on the UPS label
for later reference.
6. With the battery terminals toward the rear of the
unit, slide the battery (pack) into the UPS. Make
sure the battery wires retract without binding.
7. Close the battery access door and secure with the
(2) screws removed in step 2. Return the desktop
UPS to the upright position.
Connecting External
Battery Enclosure(s)
For additional runtime, some ON Seriesm UPSs can
use extra batteries housed in a separate enclosure.
Use only ONEAC model ONMXBC-217. The UPS
power module and battery enclosure(s) are shipped
separately.
1. Connect the battery cable from the closest
battery enclosure to the external battery
receptacle on the UPS, see fig. 2.

Installation
6 ON Series m UPS User Instruction Manual
2. Connect the battery cable from the next external
battery enclosure (if any) to the external battery
receptacle on the battery enclosure connected in
the previous step.
Repeat step 2 to connect additional external battery
enclosures.
fig. 2: ON Series UPS and External Battery Connections
Connections
Before beginning, shut down and unplug the
equipment to be protected. DO NOT make any
connections or attempt to use any of the equipment
until all the following connection instructions have
been reviewed and completed.
The I and J model UPSs are equipped with (1)
IEC320 (M) Input connector and (4) IEC320 (F)
output connectors, as shown in fig. 4. The A model
UPSs have (1) IEC320 (M) input connector and
either (2) or (4) NEMA 5-15R hospital grade
receptacles, as shown in fig. 5.
fig. 3: ON Series m UPS Front Panel
Indicator Lights
Power Switch

Installation
ON Series m UPS User Instruction Manual 7
fig. 4: ON Series m UPS I and J Models Back Panel
fig. 5: ON Series m UPS A Models - Back Panel
Load to UPS
ON Series m “A” models have (2/4) NEMA 5-15R
Receptacles and are shipped with a hospital grade
IEC 5-15P line cord. Use the supplied line cord to
connect the UPS to the AC power source. Connect
the protected devices directly to the 5-15R
receptaclesonthe UPS. On ON Series I and Jmodels
a 6 foot IEC 320 (M/F) cord is provided for
connection of one device to the UPS. If more than
one device will be connected to the UPS, use
additional IEC 320 (M/F) cords as shown in figure 4.
Contact ONEAC for additional IEC 320 (M/F) cords
if needed.
IEC 320 (M) Input
Connector
IEC 320 (F) Output
Connectors
External Battery
Input Connector
ONm 300 ONm 600
IEC 320 (M) Input
Connector
IEC 320 (F) Output
Connectors
External Battery
Input Connector
ONm 300
A Models ONm 600
A Models

Installation
8 ON Series m UPS User Instruction Manual
1. Disconnect the input power cord(s) from the
device(s) the UPS will be protecting.
NOTE:
One of the disconnected power cords will be
used as the input power cord for the UPS.
2. Use IEC 320 (M/F) cord(s) to connect the
device(s) to the UPS IEC 320 (F) output
connectors.
Contact ONEAC Technical Support if your
equipment does not have a detachable IEC 320
power cord.
UPS to Power Source
To connect the UPS to theAC power source, use the
input power cord supplied with the device to be
protected.
Connect the UPS to the AC utility power source as
shown in figure fig. 6.
fig. 6: Connecting Load(s) to UPS and Connecting UPS to AC Power Source
Utility
Power Device #3 to
be Protected
ONm UPS Device #1 to
be Protected Device #2 to
be Protected
Input power cord disconnected from protected device
IEC320 M/F power cord, (1) provided

Operating Instructions
ON Series m UPS User Instruction Manual 9
Operating
Instructions
With the UPS connected to a properly wiredAC
input power source, toggle the power switch to the
( | ) “ON” position. Power is immediately supplied to
the output connectors.
Power Switch
Toggling the power switch to the( ) “standby”
position will turn the power to the output connectors
“OFF”. The internal charger will continue to charge
and maintain the battery as long as the line cord is
connected to a live inputAC power source.
fig. 7: ON Series m UPS Front Panel
SelfTest
The UPS checks vital functions when it is first
plugged in and indicates the status with the three
LEDs on the front panel. A green LED indicates
normalACoutput.AblinkingyellowLEDshowsthe
battery is being charged.The UPS will continuously
monitor the condition of the battery. If the battery
cannot be charged, is disconnected or takes too long
to charge, a code is represented in the LED Display.
NOTE:
The System Code Status Chart on the back of
the UPS (and on page 11 of this manual) provides a
quickreference forinterpretationofthe systemstatus
LEDs.
On Battery
If the AC input power source to the UPS rises too
high, too low or fails, the UPS will switch to the
internal inverter to deliver power to the outlets from
the battery(ies). The LEDs will indicate that the UPS
is on battery.An audible alarm will also sound every
minute.
Indicator
Lights
Power
Switch

Operating Instructions
10 ON Series m UPS User Instruction Manual
Low Battery
When the battery voltage falls to a predetermined
value, the audible alarm will sound continuously and
the green and yellow LEDs will blink. If the UPS
continues to operate in this mode for two minutes or
more, the UPS will shutdown and remove power
from the output connectors.
When power returns, the UPS will return to on-line
operation and the battery(ies) will automatically
recharge.
Overload
If the load on the UPS exceeds its capacity, the red
and green LEDs will blink. The audible alarm will
sound once every minute.
If the UPS is heavily overloaded, the audible alarm
will sound continuously and will shut down in a few
seconds.Theinputbreakermayalsotrip.Toresetthe
breaker, first turn the UPS power switch to the
“OFF” position, remove the load and push the
breaker back into its housing. If the electronic
overloadhastripped,theUPSwillhavetoberesetby
toggling the power switch “OFF”, then “ON” to
restore output power.
Battery Replacement
If the UPS has determined that the battery is no
longer functional, the green and red LEDs will be on
continuously and the yellow LED will flash. The
audible alarm will sound every five minutes.
Indicator Lights
GREEN - When the green LED is on, either solid or
blinking, power is being supplied to the output. If
blinking, it indicates the UPS is on inverter or there
is an overload condition.
YELLOW - When the yellow LED is on solid, the
UPSisoninverter. If blinking, it indicates the battery
is charging when on line or low battery if running on
inverter.
RED - When the red LED is on solid, it indicates
there is a problem with the battery charger or

Operating Instructions
ON Series m UPS User Instruction Manual 11
inverter. If blinking, it indicates no battery, overload
or high line and no battery present.
Communications
(Factory Installed
Options)
The isolated Basic Interface Option will send On
Battery and Low Battery signals to the host
computer. It will also accept a shutdown signal to
turn the inverter off to conserve battery life.
Pins 1 and 10 (simulated relay closures) are open
collector transistor outputs which must be pulled up
to a common reference supply no greater than +15V
DC.Theyareopto-isolatedopencollectortransistors
capable of a maximum noninductive load of 10mA
DC. Pin 11 is the common for all of the relay closure
pins and is isolated from the UPS chassis ground.
Pins 20 and 21 are used to shut down the UPS when
it is operating on battery.A positive signal (3 to 24V
DC) on pin 20 with respect to pin 21 shuts down the
UPS.A signal at or below ground allows the UPS to
keep running.
Table 2. System Code Status Chart
Power Battery Fault Unit Status
O O O OFF
●
O O ON/AC Present
●❋❋
ON AC/No Battery
●❋
O ON AC/Battery Charging
●❋●
ON AC/Replace Battery
❋
O
❋
ON AC/Overload
❋●
O ON Battery Power
❋❋
O ON Battery/Battery Low
OO
❋
Off/Overload
O
●●
Off/No AC - Fault
OO
●
Off/Unit Fault
O = Off,
●
= On,
❋
= Blinking

Replacing Battery(ies)
12 ON Series m UPS User Instruction Manual
The shell of the interface connector is connected to
the UPS chassis ground.
fig. 8: ON Series m UPS Rear Panel
Replacing
Battery(ies)
NOTE:
To obtain new battery(ies), contact ONEAC
Technical Services at (847) 816-6000, or toll free at
(800)-327-8801, ext. 3. In Europe, dial
+44 (0) 1235 534721.
Battery replacement is a safe procedure that is
isolated from electrical hazards.You can leave the
UPS and attached loads powered “ON” during the
procedure. If the unit is “ON,” the audible alarm will
sound when the battery is disconnected and the
yellow and red LEDs will blink.
NOTE:
The UPS cannot protect against power
outages while the batteries are disconnected.
Table 3. Pin Signals
Interface Pin No. Signal
1 Low Battery - normally open
10 Line Fail - normally open
11 Output Signal Common
20 Shutdown (to UPS)
21 Shutdown (to UPS)
Interface Port
ONm 300 ONm 600

Replacing Battery(ies)
ON Series m UPS User Instruction Manual 13
Procedures
1. Lay the UPS on its right side.
2. Open the battery access door on the bottom by
removing the two (2) Phillips head screws at the
front. Retain the screws for use in step 8 later.
3. Carefully open the battery access door and slide
the batteries out of the unit.
4. For the ONm Series 300VA UPS disconnect the
black wire, then the red wire from the battery
pack.
For the ONm Series 600VA UPS remove the
batteryconnectorby squeezing the two“ears”on
the sides of the connector and pulling straight
out.
WARNING:
Once the wires are removed from the
battery(ies), use caution to not contact the exposed
battery terminals due to the presence of electrical
charge.
5. For the ONm Series 300VA UPS, using the new
battery(ies), connect the red wire to the red
positive (+) terminal on the battery.
NOTE:
Inthenextstepbeaware that a small arcmay
occur while connecting the black wire to the battery
terminal.
6. Connect the black wire to the (-) terminal on the
battery.
For the ONm Series 600VA UPS, insert the
battery connector in the plug in the battery
compartment.
NOTE:
The plug is polarized and only will fit in one
way.
7. With the battery terminals toward the rear of the
unit, slide the battery (pack) into the UPS. Make
sure the battery wires retract without binding.
8. Close the battery access door and secure with the
(2) screws removed in step 2. Return the desktop
UPS to the upright position.
9. Dispose of the old battery pack according to

Replacing Battery(ies)
14 ON Series m UPS User Instruction Manual
current environmental regulations. See Battery
Disposal, below, if you would like ONEAC to
dispose of battery.
fig. 9: ON Series m UPS Battery Replacement
Replacing External
Battery Enclosure(s)
For additional runtime, some ON Seriesm UPSs can
use extra batteries housed in a separate enclosure.
The UPS power module and battery enclosure(s) are
shipped separately.
NOTE:
The UPS and attached loads may remain
powered ON during the battery enclosure(s)
replacement procedures.
The batteries inside the external battery enclosure(s)
arenotuser-replaceable.Theentirebatteryenclosure
must be replaced or the enclosure may be returned to
ONEAC for battery replacement.
To disconnect the battery cable coming from an
external battery to the UPS or another external
battery, squeeze the two locking “ears” on the sides
of the battery connector and pull straight out (see fig.
10).
fig. 10: ON Series m External Battery Replacement
ON Series m UPS
Battery Wires
Battery

Battery Disposal
ON Series m UPS User Instruction Manual 15
Connect the battery cable from the closest battery
enclosure to the external battery receptacle on the
UPS, see fig. 2.
Connect the battery cable from the next external
battery enclosure (if any) to the external battery
receptacle on the battery enclosure connected in the
previous step.
Repeat to connect additional external battery
enclosures.
Battery Disposal
UPS batteries contain toxic and acidic materials.
Disposal method must adhere to local/national
recycling laws. Dispose of the battery in one of three
ways:
1. Return batteries prepaid to ONEAC for proper
recycling. Contact ONEAC Technical Services
at (847) 816-6000, toll free at (800) 327-8801
option 3 or in Europe at +44(0)1235534721for
an RMA number. Mark the RMA number on the
packing slip and shipping carton.
2. Phone ONEAC Corporation for the number of a
local battery collection site (US only).
3. Make arrangements with a local auto shop that
collects automotive batteries for reprocessing.
CAUTION:
DO NOT dispose of battery in a fire. The
battery may explode. Do not open or mutilate the
battery or battery enclosure. Released electrolyte is
harmful to the skin and eyes and is toxic.
UPS Disposal
Once your UPS has reached the end of its useful life
and it is necessary to dispose of the unit:
1. Remove the batteries as instructed in Replacing
Battery(ies) on page 12.
2. Dispose of the batteries as instructed in Battery
Disposal on page 15.
3. Dispose of the unit in accordance with local/
national recycling or disposal ordinances.

Troubleshooting
16 ON Series m UPS User Instruction Manual
Troubleshooting
ONEAC offers 24-hour technical support. If you
have questions or problems regarding your ON
Series m UPS:
1. Referto theTroubleshootingtableonpage 17for
corrective or recommended action.
2. If you are unable to troubleshoot the problem,
contact Technical Services. Refer to page 1,
Technical Support, for the correct telephone
number in your area. Technical Services will ask
youtodescribetheproblem.Theywillhelpsolve
the problem over the telephone or issue a Return
Material Authorization (RMA) number along
with instructions on how to return the UPS for
repair.
NOTE:
You will need to supply the service
representative with the UPS part number and serial
number. You can access these numbers on the back
panel of the unit on a label located near the
receptacles.
Always check with ONEAC Technical Services
before attempting to repair or return any ONEAC
product.

Troubleshooting
ON Series m UPS User Instruction Manual 17
If you have questions or problems regarding you ON Series m UPS, refer to the
troubleshooting table below.
Table 4. Troubleshooting
Problem Possible Cause Solution
UPS will not turn ON
Front Panel Switch not
“ON”. Switch the Power Switch to (I)
UPS’s input circuit
breaker tripped.
Reduce the load on the UPS by
unplugging the load and press
the circuit breaker in on the rear
panel.
Unit not plugged in. Plug unit into wall outlet.
UPS operates on battery
even with line voltage
present.
UPS’s input circuit
breaker tripped.
Reduce the load on the UPS by
unplugging the load and press
the circuit breaker in on the rear
panel.
High or low line. Contact qualified electrician.
Out of frequency range. Check for UPS compatibility
with power source.
Fault LED is ON.
If yellow LED is blinking,
the battery needs to be
replaced.
Allow batteries to charge for 4
hours.If the problem continues,
replace the battery(ies).
If yellow LED is off or on
solid, there is an internal
UPS fault.
Do not attempt to use the UPS.
Turn the UPS off, unplug from
the power line and call
Technical Service:
(800)-327-8801, opt. 3
immediately.
Fault LED is blinking
If yellow LED is blinking,
there is no battery
connected or detected.
Connect install or replace the
battery(ies).
If green LED is blinking
or off, the output is
overloaded.
Reduce the load on the UPS
until the LED goes out. If green
LED is off, recycle power switch
to reset.

Appendix A:Warranty
18 ON Series m UPS User Instruction Manual
Appendix A:
Warranty
ONEAC products are warranted free from defects in
materials and workmanship for five years. This
warranty is limited to repairing or replacing, at
ONEAC’s option, any defective component, circuit
board, or module contained within the product only
when it is returned with an ONEAC Return Material
Authorization (RMA) number to ONEAC or to an
ONEAC-designated repair facility. In all cases, the
customer is responsible for shipping charges to and
from ONEAC or the ONEAC-designated repair
facility.
Batteries
Certain modules or peripherals included with the
product, but not manufactured by ONEAC,
including but not limited to batteries or battery
enclosures, are warranted for two years or the extent
of the manufacturer’s warranty, whichever is longer.
Life Critical
Applications
While ONEAC believes it designs and manufactures
very reliable products, many of the vendors that
ONEAC sources components from do not
recommend or endorse the use of their products in
life critical applications. By extension, ONEAC
mustadhere to the same businesspolicyanddoesnot
recommend the use of our products in life critical
applications.
Disclaimer
ONEAC products are not designed, intended or
authorized for use in systems intended to support or
sustain life, or for any other application in which the
failure of the ONEAC product could create a
situation where personal injury or death may occur.
Should the Buyer purchase or use ONEAC product
foranysuchunintendedorunauthorizedapplication,
the Buyer shall indemnify and hold ONEAC and its
officers, employees, subsidiaries, affiliates and
distributors harmless against all claims, costs,
damages and expenses, and reasonable attorney fees
arising out of, directly or indirectly, any claim or
personal injury or death associated with such
unintended or unauthorized use, even if such claim
alleges that ONEAC was negligent regarding the
design or manufacture of the part.

Appendix A: Warranty
ON Series m UPS User Instruction Manual 19
Limitations of
Warranty
This limited warranty does not cover any losses or
damage resulting from shipment to or from the
customer, or from improper installation,
inappropriate environment, abuse, modifications,
adjustments, or unauthorized repair.
For full details of the warranty, see ONEAC
Warranty, Policy and Procedures (part number
955-053).
Exclusive Remedies
Except as set forth herein and except as to title, there
are no warranties, express or implied, or any
affirmations of fact or promises by ONEAC for the
products, their merchantability, or fitness for any
particular purpose. In no event shall ONEAC be
liableforlostprofits,goodwilloranyotherspecialor
consequential damages.
Return Procedure
To return a UPS, contact ONEACTechnical Support
for a Return MaterialAuthorization (RMA) number.
This number must be marked on the shipping carton
and packing slip of the unit returned. The customer
is responsible for repair charges for damages
incurred in shipment that result from inadequate or
improper packing of the product.

Appendix B:Typical Runtime
20 ON Series m UPS User Instruction Manual
Appendix B:
Typical Runtime
Table 5. Typical Runtime by System Load
Typical Runtime by System
Load ONm300 A, I and J Models
One 12V, 7AH Battery ONm300D A, I and J Models
Two 12V, 7AH Batteries
VA LOAD RUNTIME (HOURS:MINUTES)
75 VA 0:41 1:32
100 VA 0:21 1:09
150 VA 0:16 0:40
200 VA 0:10 0:30
250 VA 0:07 0:20
300 VA 0:05. 0:15
NOTE: Due to application specific conditions, your actual run time may be different.
Table 6. ON Series m 600 VA Extendable Runtimes
TypicalRuntime
by System Load ONm600X
Two 12V,7 AH
Batteries
Plus1
External
Battery
Plus2
External
Batteries
Plus 3
External
Batteries
Plus 4
External
Batteries
Plus 5
External
Batteries
VA LOAD RUNTIME (HOURS:MINUTES)
100 VA 1:05 4:40 8:50* 10:30* 13:30* 16:40*
200 VA 0:35 2:40 5:00* 7:00* 9:00* 11:10*
400 VA 0:15 1:20 2:20* 3:30* 4:30* 5:30*
600 VA 0:05 0:30 1:10* 2:20* 3:00* 3:45
NOTE: Due to application specific conditions, your actual run time may be different.
NOTE: External Battery - Two 12V, 17AH per battery enclosure.
* Values shown are calculated.
This manual suits for next models
2
Table of contents
Other ONEAC UPS manuals

ONEAC
ONEAC Sinergy Series User manual

ONEAC
ONEAC ON Series Operator's manual

ONEAC
ONEAC S07KXAU User manual

ONEAC
ONEAC ONE404AG-SE Operating instructions

ONEAC
ONEAC ON Series User manual

ONEAC
ONEAC ONePlus Series Operator's manual

ONEAC
ONEAC ON Series Operator's manual

ONEAC
ONEAC SE041XAT Operator's manual

ONEAC
ONEAC ON Series Operator's manual
Popular UPS manuals by other brands

Liebert
Liebert GXT3-10000T230 user manual

Eaton
Eaton Tripp Lite SmartPro Series Advanced user's guide

Energenie
Energenie EG-UPS-033 user manual

NewMar
NewMar AC UPS Series Installation & operation manual

OPTI-UPS
OPTI-UPS Clever Series CS385B Specification sheet

TCW Technologies
TCW Technologies Integrated Back-up Battery System manual