Ormazabal velatia cpg.0 Instruction manual

LIB
cpg.0
GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
General instructions
IG-123-EN, version 10, 19/06/2019

In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject
to change without prior notice. These characteristics, as well as the availability of components, are subject to confirmation by
Ormazabal.
CAUTION!
When medium-voltage equipment is operating, certain components are live, other parts may be in movement and some may
reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
• Elimination of hazards wherever possible.
• Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
• Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protective equipment.
• Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the
environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of Standard
IEC 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the
requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near
electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other
recommendations of a more general nature which are applicable to the situation according to current legislation[1].
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also
on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
• The equipment must be handled and transported appropriately from the factory to the place of installation.
• All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment
or its essential components.
• Service conditions must be compatible with the equipment rating.
• The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable
operating and safety principles must be clearly understood.
• Maintenance should be performed properly, taking into account the actual service and environmental conditions in
the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the warranty, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Warranty
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual
belongs to Ormazabal.
[1] For example, in Spain the “Regulation on technical conditions and guarantees for safety in high-voltage electrical installations” – Royal Decree
337/2014 is obligatory.

IG-123-EN version 10; 19/06/2019 3
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Contents
Contents
1. General description ...................................................4
1.1. Models ......................................4
1.2. Standards applied............................4
1.3. Main components ...........................5
2. Technical characteristics..........................................12
2.1. Electrical characteristics .....................12
2.1.1. Name plate .................................14
2.2. Mechanical characteristics ..................15
2.2.1. Dimensions.................................15
2.3. IP rating ....................................16
3. Normal service conditions(a) ....................................17
4. Handling and transport...........................................18
4.1. Transport conditions ........................18
4.2. Lifting means ...............................18
5. Storage......................................................................20
6. Installation ...............................................................21
6.1. Unpacking the equipment ..................21
6.2. List of assembly materials supplied ..........21
6.3. Minimum installation distances..............22
6.4. Cable trench ................................22
6.4.1. Recommended dimensions .................23
6.5. Fastening to the floor .......................23
6.6. Connecting cubicles ........................24
6.6.1. cpg.0-v 24 kV 630 A .........................25
6.6.2. cpg.0-v 1250 A y 1600 A/cpg.0-pt/cpg.0-vl...25
6.6.3. cpg.0-v 2500 A ..............................26
6.6.4. cpg.0-c......................................26
6.6.5. cpg.0-s ......................................27
6.6.6. cpg.0-f/cpg.0-fl..............................27
6.6.7. cpg.0-rb.....................................28
6.7. Equipment earthing ........................29
6.7.1. Top section .................................29
6.7.2. Bottom section .............................30
6.7.3. Side area ...................................30
7. Operations sequence...............................................32
7.1. Operation and commissioning
sequence ...................................32
7.1.1. Disconnector function operating
sequence (cpg.0-s)..........................32
7.1.2. Circuit-breaker function operation
sequence (cpg.0-v/cpg.0-vl).................38
7.1.3. Busbar coupling function operation
sequence (cpg.0-c)..........................45
7.1.4. Busbar rise cubicle (cpg.0-rb)................50
7.1.5. Busbar earthing function operating
sequence (cpg.0-pt).........................50
7.1.6. Operating sequence in fuse protection
function (cpg.0-f/cpg.0-fl)...................53
8. Safety elements........................................................63
8.1. ekor.ivds voltage detectors .................63
8.2. Locking with a padlock......................63
8.2.1. Locking with lock ...........................63
8.3. Interlocks ...................................64
9. Maintenance.............................................................65
9.1. Voltage indicator test .......................65
9.2. Preventive maintenance circuit-breakers.....65
10. Spares and accessories ............................................66
11. Environmental information ....................................67
11.1. Sulphur hexafluoride SF6....................67
11.2. Recyclability ................................67

IG-123-EN version 10; 19/06/2019
4
General description General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
1. General description
The cpg.0 switchgear is made up of a series of GIS-type
cubicles, with complete insulation in gas, for primary
distribution in medium-voltage networks up to 40.5 kV.
1.1. Models
Model Function
cpg.0-v Circuit breaker
cpg.0-vl Circuit breaker with side connection on the left
cpg.0-c Longitudinal busbar coupling
cpg.0-s Disconnector
cpg.0-f Fuse protection
cpg.0-fl Fuse protection with side connection on the right
cpg.0-rb Busbar rise
cpg.0-pt Busbar earthing
cpg.0-rc Cables side rise
Table 1.1. cpg.0 switchgear models
1.2. Standards applied
Standard Description
IEC 62271-1 Common specifications for high voltage switchgear standards
IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-100 Alternating current circuit breakers
IEC 62271-103 High voltage switches for rated voltages above 1 kV up to and including 52 kV
IEC 62271-102 Alternating current disconnectors and earthing switches
IEC 62271-105 A.C. fuse combination switch for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-206/IEC 61243-5 Voltage presence indicating systems
IEC 60529 Degrees of protection provided by enclosures (IP Code)
IEC 60282-1 Current-limiting fuses
Table 1.2. Standards applied

IG-123-EN version 10; 19/06/2019 5
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
General description
1.3. Main components
1Busbar compartment
2Gas tank
3Gas pressure relief duct
4Cable compartment
5Control compartment
6Driving mechanism compartment
Figure 1.1. Main components of cubicles cpg.0

IG-123-EN version 10; 19/06/2019
6
General description General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Gas tank
This is a sealed compartment, made of stainless steel and
sealed for life, which houses the switching and breaking
switchgear, with gas as insulating medium.
Depending on the function for which the cubicle was
designed, it may contain the following components:
• Disconnector.
• Earthing switch.
• Internal busbar and connections.
• Vacuum circuit-breaker.
• Switch - disconnector.
• Fuse holders.
Connection to the busbar is possible via upper bushings.
Connection to the medium voltage cables is made with the
lower and/or side bushings.
The gas pressure is tested, in each cubicle visually by means
of a pressure switch with a volt-free contact, allowing it to
be used as a remote alarm or blocking/trip for the position.
Figure 1.2. Example of bushing position in gas tank (1)
Busbar compartment
The busbar compartment, designed to withstand an
internal arc inside (optional), meeting the criteria of Annex A
of Standard IEC 62271-200, class IAC: AFL/AFLR, is located
at the top of the cubicle, separate from the gas tank. It is
made from metal sheet, offering the degree of protection
necessary for the connection device.
It comprises a fully assembled, tested unit, separated
by phases (segregating them as an option), by way of
earthed metal plates, with solid, screened insulation,
earthed through an earth collector plate specific to the
compartment.
Toroidal current transformers and/or plug-in voltage
transformers can also be installed, thus avoiding the need
for metering cubicles.
Figure 1.3. Phase segregation in the busbar (optional)

IG-123-EN version 10; 19/06/2019 7
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
General description
Cable compartment
[2] There are four or six in the case of cubicles with rated branch current of 2500 A.
Located in the bottom part of the cubicle, this has a cover,
interlocked with the earthing circuit, which allows front
access to the medium voltage cables. This compartment
is prepared to withstand an internal arc in terminals up to
31.5 kA - 1 s, meeting the criteria of Annex A of Standard
IEC 62271-200, class IAC: AFL/AFLR.
In the most complete case, the base can house the following
components:
• Phase segregation assembly (optional) consisting of the
main box and the segregating cover.
• Three[2] symmetrical shielded terminals with reinforced
connection (screwable) by phase or four asymmetric
ones.
• Clamp flanges for the medium voltage cables.
• Earthing bars.
• Toroidal current transformers.
• Voltage transformers, with connection via medium
voltage cable or plug-in/disconnectable.
All the elements making up the enclosure are earthed
by means of a conductor consisting of a copper plate,
sized to withstand the rated short-time current. This is
located in the base, meaning it does not need to be
dismantled in order to insert or remove a cable and its
corresponding termination.
Figure 1.4. Detail of the main box and the segregating cover

IG-123-EN version 10; 19/06/2019
8
General description General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Fuse compartment
[3] There are four or six in the case of cubicles with rated branch current of 2500 A.
The fuse protection cubicle cpg.0-f, has separate fuse
holders to house medium voltage limiter fuses.
The compartments are pipe-shaped and are fully enclosed
in the gas tank, making them unaffected by pollution. To
remove and insert the fuses in the fuse holder, a carriage
is used to simplify the operation and ensure correct fuse
placement.
The pipe seal consists of an elastic membrane with the
following functions:
• To ensure the water-tightness of the fuse holder
against flooding and thus avoid interior pollution and
degradation.
• Additional insulation to that provided by the fuse holder
carriage insulator.
• To transmit the movement of the fuse striker to the
tripping mechanism, while maintaining the water-
tightness of the fuse holder tube.
By the very nature of its construction, this sealed solution
is subject to the internal overpressure caused by abnormal
overheating of the internal air. In this case, the trip device
can act as protection against overheating, thus preventing
damage to both the fuse and the fuse holder.
Figure 1.5. Fuses compartment detail
Exterior cable connections (bushing)
The cpg.0 cubicles have bushings on the front for medium-
voltage cable connection. These are made of epoxy resin
and can, thanks to their configuration, withstand the
current transformers. They are duly screened and designed
in line with Standard EN 50181, being of type “C”.
They allow the connection of conductors of up to 800 mm2
via screw-in T-type connectors of any manufacturer. The
cable compartment allows the installation of up to three
cables[3] per phase, with a symmetrical terminal, or up to
four cables per phase, with an asymmetric terminal.
Figure 1.6. Cable compartment

IG-123-EN version 10; 19/06/2019 9
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
General description
The cpg.0-vl and cpg.0-fl models have side bushings for
connection of up to two medium voltage cables per phase,
up to 800 mm2. These side bushings do not allow it to
withstand current transformers.
Figure 1.7. Side bushings in cpg.0-vl for connection of medium voltage
cables
Figure 1.8. Side bushings in cpg.0-fl for connection of medium voltage
cables
Model cpg.0-rc (cable side rise) protects the cable side
connection of models cpg.0-vl (cpg.0-rci, left cable rise) and
cpg.0-fl (cpg.0-rcd, right cable rise).
Figure 1.9. Left side cable rise cubicle (cpg.0-rci) for cubicle cpg.0-vl
Figure 1.10. Right side cable rise cubicle (cpg.0-rcd) for cubicle cpg.0-fl

IG-123-EN version 10; 19/06/2019
10
General description General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Gas pressure relief duct (optional)
[4] In accordance with model; see the unit's Name Plate.
The entire cubicle is prepared to withstand an internal arc
in the gas tank up to 31.5 kA - 1 s[4], meeting the criteria of
Annex AA of Standard IEC 62271-200, accessibility class IAC:
AFLR.
1Gas pressure relief diaphragm
2Gas vent from cable compartment
Figure 1.11. Pressure relief diaphragm and gas vent detail
A duct made of metal sheet, which conducts the gases
produced by an internal arc towards the top of the cubicle,
from any of the three compartments: gas tank, cable
compartment and busbar compartment.
Figure 1.12. Gas pressure relief duct detail (1)
Control compartment
Placed at the top of the cubicle and separate from the
medium-voltage area, this is ready for installation of the
measuring equipment and protection relays. It contains
the terminal block with the control signals duly identified
in accordance with the wiring diagram provided with
the equipment. All the connections between the driving
mechanisms compartment and the control box are made
via connectors, which makes the assembly more flexible,
and allows the control box to be assembled and connected
on site in a straightforward, direct way.
Figure 1.13. Control compartment detail

IG-123-EN version 10; 19/06/2019 11
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
General description
Driving mechanism
In addition to a mimic diagram customised for each type
of function, this has the driving elements in its middle
section: disconnector/earthing switch and circuit breaker
driving mechanisms, circuit breaker opening/closing push-
buttons, status indicators, groove for access of the spring
loading lever, etc.
Figure 1.14. Example of driving mechanism area

IG-123-EN version 10; 19/06/2019
12
Technical characteristics General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
2. Technical characteristics
2.1. Electrical characteristics
Functions
cpg.0-v
cpg.0-vl(1)
cpg.0-c
cpg.0-s
cpg.0-f(1)
cpg.0-fl(1)
cpg.0-rb
cpg.0-pt
cpg.0-rc(1)
Rated voltage [Ur]kV 24 36 40,5(1)
Industrial frequency [Ud]
Between phases kV 50 70 95
Isolating distance kV 60 80 118
Lightning impulse [Up]
Between phases kV 125 170 185
Isolating distance kV 145 195 215
(1) For rated voltage of 40.5 kV there are no models available cpg.0-vl, cpg.0-f, cpg.0-fl and cpg.0-rc.
Table 2.1. Table of common electrical characteristics to the cpg.0 family
For rated voltage of 24 kV cpg.0-v cpg.0-vl cpg.0-c cpg.0-f cpg.0-fl cpg.0-s cpg.0-pt cpg.0-rb cpg.0-rc
Rated current [Ir]
General busbar A
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
According
to side
cable con-
nection
Branch A
630
1250
1600
2000
≥ 2500*
1250** NA 200 1250**
1250
1600
2000
2500
NA 1250 630/1250
Short-circuit [Ik] tk= 1 or 3 s kA 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5
(*) With forced ventilation from 2250 A.
(**) Also for side branch.
Table 2.2. Specic electrical characteristics for 24 kV series

IG-123-EN version 10; 19/06/2019 13
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Technical characteristics
For voltage of 36 kV cpg.0-v cpg.0-vl cpg.0-c cpg.0-s cpg.0-f cpg.0-fl cpg.0-pt cpg.0-rb cpg.0-rc
Rated current [Ir]
General busbar A
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
2000
2500
1250
1600
According
to side
cable con-
nection
Branch A
630
1250
1600
2500*
1250** NA
1250
1600
2000
2500*
200 1250** NA 1250 630/1250
Short-circuit [Ik] tk= 1 or 3 s kA 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5
(*) With forced ventilation from 2250 A.
(**) Also for side branch.
Table 2.3. Specic electrical characteristics for 36 kV series
For voltage of 40.5 kV cpg.0-v cpg.0-c cpg.0-s cpg.0-pt cpg.0-rb
Rated current [Ir]
General busbar A1250
1600 1250 1250
1600 1250 1250
1600
Branch A630
1250 NA 1250 NA 1250
Short-circuit[Ik] tk= 1 or 3 s kA 25/31.5 25/31.5 25/31.5 25/31.5 25/31.5
Table 2.4. Specic electrical characteristics for 40.5 kV series
Other characteristics cpg.0-v/cpg.0-pt/
cpg.0-vl cpg.0-c cpg.0-s/cpg.0-rb/
cpg.0-rc cpg.0-f/cpg.0-fl
Automatic reclosing sequence O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO NA
Motorised spring loading time s < 15 NA
Short-circuit breaking rated current kArms 25/31.5 NA
With Fuse:
25/31.5*
(*): only up to 36 kV
Short-circuit closing rated current kApeak 65/82 NA
With Fuse:
63/82*
(*): only up to 36 kV
Opening time ms < 45 NA With Fuse:
< 72
Short-circuit break-time ms < 50 NA
Vacuum feeder rated current A 10 NA
Vacuum cable rated current A 31.5 50 31.5 50 NA 50
Transfer rated current A NA NA NA 820 A
Capacitor bank rated current A 400 NA
Internal fault rated current kA 65/82 peak - 25/31.5 rms
Internal fault rated time s 1
Electrical endurance
Circuit breaker: E2
Feeder disconnector: E0
Earthing switch: E2
Feeder disconnector:
E0
Earthing switch: E2
(cpg.0-rb NA,
cpg.0-rc NA)
Switch: E3
Earthing switch: E2
Mechanical endurance
Circuit breaker: M2
Feeder disconnector: M1
Earthing switch: M1
M1
(cpg.0-rb NA),
cpg.0-rc NA
Switch: M1
Earthing switch: M0
Internal arc classication in
accordance with IEC 62271-202 AFL[R] 25/31.5 kA 1
NA: Not applicable.
Table 2.5. Additional electrical characteristics

IG-123-EN version 10; 19/06/2019
14
Technical characteristics General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
2.1.1. Name plate
Each unit includes a name plate, with some of the
following data, reflecting each cubicle's individual electrical
characteristics:
Figure 2.1. Example of name plate
Name plate
N° Cubicle serial number(*)
Type Ormazabal cubicle system
Designation Cubicle model
Standard Standards applied to the equipment
UrEquipment rated voltage (kV)
UpLightning impulse withstand voltage (kV)
UdIndustrial frequency withstand voltage (kV)
frEquipment rated frequency (Hz)
IrEquipment rated current (A)
Ik/IpShort-time withstand current/Short-time withstand peak value
tkShort-time withstand current time
Pre Gas pressure inside the cubicle (MPa)
Pme Minimum operating gas pressure (MPa)
SF6Weight of insulating fluid (g)
Year Year of manufacture
TC Thermal class
IAC Internal arc classification
(*) In the event of incident, this number should be reported to Ormazabal.
Table 2.6. List of information contained on the name plate

IG-123-EN version 10; 19/06/2019 15
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Technical characteristics
2.2. Mechanical characteristics
2.2.1. Dimensions
Figure 2.2. cpg.0 dimensions
Model
Ioutgoing
a ap h hp f Weight
v
630 600 - 2425 665 1365* 280
1250 600 - 2425 665 1365* 850
1600 700 - 2425 665 1365* 900
2000/2500 1000 - 2425 665 1365* 1100/1200
vl 1250 600 789 2425 665 1365* 870
f 200 600 - 2425 665 1402** 550
fl 200 600 789 2425 665 1402** 850
s
1250 600 - 2425 665 1365* 550
1600 700 - 2425 665 1365* 600
2000/2500 1000 - 2425 665 1365* 1100/1200
c
1250 1200 - 2425 665 1365* 1300
1600 1400 - 2425 665 1365* 1550
2000/2500 2000 - 2425 665 1365* 2300/2500
rb 1250 600 - 2425 665 1365* 500
pt - 600 - 2425 - 1365* 850
rci - 500 - 2425 - 1365* 260
rcd - 430 - 2425 - 1365* 250
(*) 1410 mm in the case of cubicles with IAC AFLR rating.
(**) 1447 mm in the case of cubicles with IAC AFLR rating.
Table 2.7. cpg.0dimensions and weights

IG-123-EN version 10; 19/06/2019
16
Technical characteristics General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
2.3. IP rating
All power circuit elements are installed inside a stainless
steel gas tank, providing IP65 degree of protection. The
standard degree of protection for the cubicle assembly, in
all designations, is IP3X, and as an option it can reach IP4X.

IG-123-EN version 10; 19/06/2019 17
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Normal service conditions(a)
3. Normal service conditions(a)
Installation Indoor
Maximum ambient temperature + 40 °C
Minimum ambient temperature - 5/- 15/- 25 °C
Maximum mean ambient temperature, measured over a 24-hour period + 35 °C
Maximum mean relative humidity, measured over a 24-hour period < 95 %
Maximum mean vapour pressure, measured over a 24-hour period 22 mbar
Maximum mean vapour pressure, measured over a 1-month period 18 mbar
Maximum height above sea level 1000 m
Solar radiation Negligible
Ambient air pollution (dust, smoke, corrosive and/or flammable gases, vapours or salt) Insignificant
Vibrations caused by causes external to the switchgear or by seismic movements Insignificant
(a) For special service conditions (maximum ambient temperature above + 40 °C, transport height, storage or installation over 1000 m above sea level,
significant pollution level, or others different to those described) check with Ormazabal.
Table 3.1. Normal service conditions
The specifications refer to the section 'Normal service
conditions for indoor cubicles' in the IEC 62271-1
standard 'Common specifications for high-voltage
cubicles'.

IG-123-EN version 10; 19/06/2019
18
Handling and transport General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
4. Handling and transport
4.1. Transport conditions
During transport, the switchgear must be perfectly seated
and fixed so that it cannot move about and possibly
damage the equipment. Always in upright position, un palé
directly on the ground or on a wooden pallet, depending
on the type of handling involved. Check that the cubicle is
perfectly balanced at all times.
4.2. Lifting means
The cpg.0 cubicles can be handled by lifting (with slings) or
with a forklift truck (with a pallet):
Figure 4.1. Lifting a cpg.0cubicle using chains Figure 4.2. Lifting a cpg.0-c cubicle with a forklift truck

IG-123-EN version 10; 19/06/2019 19
General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
Handling and transport
During the installation period, Ormazabal provides a
specific tool for lifting the cpg.0-c coupling cubicle:
Figure 4.3. Lifting of a cpg.0 cubicle with a specic tool
Figure 4.4. Lifting a cpg.0-c cubicle using a forklift truck and specic tool
Elevating caster wheels can be used to put the cubicles in
their final position.
Optional supply. Please check with Ormazabal.
Figure 4.5. Wheel anchors in the cubicle
Figure 4.6. Detail of the positioned wheel

IG-123-EN version 10; 19/06/2019
20
Storage General instructions
cpg.0: GIS-type medium-voltage switchgear
with full insulation in gas, up to 40.5 kV,
in accordance with IEC Standards
5. Storage
If it needs to be stored, the equipment must be placed on
dry ground or on top of damp-proof insulating material, still
in its original packaging, ensuring it is not damaged during
the storage period.
After prolonged storage, clean all the insulating parts
carefully before commissioning the equipment. The
enclosure should be cleaned with a clean, dry lint-free cloth.
Figure 5.1. Storage conditions detail
Storage must always be INDOORS, with the following
conditions recommended:
1. Ambient air temperature should not exceed 40 °C
and its mean value, measured in a period of 24 hours,
should not exceed 35 °C.
2. The ambient air temperature should not drop below
-5 °C. There are also cubicles with storage temperature
up to - 15 °C and up to - 25 °C.
3. The switchgear must be protected from direct solar
radiation.
4. Maximum altitude is 1000 m.
5. The environmental air must not have any significant
contamination from dust, smoke, corrosive and/or
inflammable gases, vapours or salt.
6. The switchgear must be protected from the rain, and
the humidity conditions should be as follows:
a. The mean relative humidity value, measured over a
period of 24 hours, must not exceed 95 %.
b. The mean water steam pressure value, measured in
a period of 24 hours, must not exceed 2.2 kPa.
c. The mean relative humidity value, measured over a
period of one month, must not exceed 90 %.
d. The mean water steam pressure value, measured
in a period of one month, must not exceed
1.8 kPa.
7. During transport, vibrations caused by external factors
or seismic movements must be insignificant.
Any other conditions must be notified beforehand,
since the equipment must be factory-adjusted to the
atmospheric pressure. Otherwise, the needle may indicate
an incorrect value (red scale), even though the value of
the equipment internal pressure is correct. Otherwise, the
manometer needle may indicate an incorrect value, even if
the equipment's internal pressure is correct.
Other manuals for velatia cpg.0
3
Table of contents
Other Ormazabal Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Zirkon zahn
Zirkon zahn titanium spectral-colouring anodizer Operator and maintenance manual

EarthLinked
EarthLinked PHXTI Series installation manual

DOYMA
DOYMA Curaflex Nova Uno/M/Z installation instructions

Diamond Products
Diamond Products CVG1 Operator's manual

JUKI
JUKI AMS-221F instruction manual

schmersal
schmersal AZM400Z-ST-I1-1P2P manual