Orton MILL IRON TOOLS Arrow Springs AutoFire ASC/6 User manual

AutoFire® Kiln Controller
User’s Guide
Model AF4X
Orton Ceramic Foundation
The Edward Orton Jr. Ceramic Foundation
6991 Old 3C Highway
Westerville, Ohio 43082-9026
Telephone: (614) 895-2663
Fax: (614) 895-5610
www.ortonceramic.com
October 2018
Arrow Springs
ASC/6

AF4X Kiln Controller
2
TABLE OF CONTENTS
INTRODUCTION........................................................................................................................................................................ 4
PRECAUTIONS........................................................................................................................................................................... 4
FEATURES .................................................................................................................................................................................. 4
TEST FIRING WITH WITNESS CONES ................................................................................................................................ 6
KEYPAD OVERVIEW ............................................................................................................................................................... 6
DISPLAY LIGHTS.......................................................................................................................................................................... 6
STARTING A FIRING ..................................................................................................................................................................... 7
STOPPING A FIRING...................................................................................................................................................................... 7
PROGRAMMING VALUES.............................................................................................................................................................. 7
PROGRAM REVIEW...................................................................................................................................................................... 7
PROGRAM SETS........................................................................................................................................................................ 7
USER PROGRAMS..................................................................................................................................................................... 8
TEMPERATURE UNITS ................................................................................................................................................................. 8
HEATING/COOLING RATES .......................................................................................................................................................... 8
MAXIMUM RAMP RATE FOR USER PROGRAMS............................................................................................................................ 8
TARGET TEMPERATURES ............................................................................................................................................................ 9
COOLING RAMPS ......................................................................................................................................................................... 9
CHANGING A TARGET TEMPERATURE DURING A FIRING............................................................................................................. 9
HOLD TIME ................................................................................................................................................................................. 9
SET-POINT HOLD ...................................................................................................................................................................... 10
ADDING TIME TO A HOLD.......................................................................................................................................................... 10
SHORTENING A HOLD................................................................................................................................................................ 10
VENT FAN (OPTIONAL) ............................................................................................................................................................. 10
PROGRAMMING USER PROGRAMS............................................................................................................................................. 10
ERASING AUSER PROGRAM ..................................................................................................................................................... 11
USER PROGRAM EXAMPLE........................................................................................................................................................ 11
ALARMS .................................................................................................................................................................................... 12
THERMOCOUPLE ALARMS......................................................................................................................................................... 12
DEVIATION ALARMS (SEE TEDE OPTION TO ADJUST DEVIATION)............................................................................................. 12
POWER INTERRUPTION ALARMS ............................................................................................................................................... 13
DIAGNOSTIC ALARMS ............................................................................................................................................................... 13
OPTIONS MENU....................................................................................................................................................................... 13
SKIP STEP -SKIP ...................................................................................................................................................................... 14
HOLD TIME -HLDT.................................................................................................................................................................. 14
CHANGE TEMPERATURE -CHGT.............................................................................................................................................. 14
DELAY MODE -DELA .............................................................................................................................................................. 14
THERMOCOUPLE TYPE -TC ...................................................................................................................................................... 14
THRESHOLD ALARM -ALAR..................................................................................................................................................... 15
DIAGNOSTICS –DIAG /TEST .................................................................................................................................................. 15
CHANGE TEMPERATURE UNITS –F/C ....................................................................................................................................... 15
OVER-TEMPERATURE LIMIT -LIM............................................................................................................................................ 15
FIRING COST -COST ................................................................................................................................................................ 15
CONE OFFSET -OFST ............................................................................................................................................................... 16
THERMOCOUPLE OFFSET -TCOS.............................................................................................................................................. 16
TEMPERATURE DEVIATION -TEDE .......................................................................................................................................... 16
HIGH TEMPERATURE DEVIATION -HTDE................................................................................................................................. 16
PROGRAM LOCK MODE -LOCK ............................................................................................................................................... 17

AF4X Kiln Controller
3
AUXILIARY OUTPUT 1-AOP1 .................................................................................................................................................. 17
ELECTRONICS TEMPERATURE -ELEC ...................................................................................................................................... 17
CONE-FIRE COOLING RAMP -COOL ......................................................................................................................................... 17
RAMP RATE UNITS -RATE....................................................................................................................................................... 18
KILOWATT HOUR COST -CENT................................................................................................................................................ 18
KILOWATT RATING -KW........................................................................................................................................................... 18
SAFETY TEMPERATURE -SFTY ................................................................................................................................................ 18
SOFTWARE VERSION -SOFT..................................................................................................................................................... 18
CONFIGURATION NUMBER -CFG.............................................................................................................................................. 18
RESET -RST ............................................................................................................................................................................. 19
HARDWARE OPTIONS........................................................................................................................................................... 19
AUDIBLE ALARM BUZZER .......................................................................................................................................................... 19
DOOR/LID SWITCH .................................................................................................................................................................... 19
COMPUTER SOFTWARE .............................................................................................................................................................. 19
SPEED PROGRAMS................................................................................................................................................................. 19
SPEED PROGRAM EXAMPLE ...................................................................................................................................................... 20
JEWELRY PROGRAMS.......................................................................................................................................................... 21
JEWELRY PROGRAM EXAMPLE.................................................................................................................................................. 21
PMC PROGRAMS .................................................................................................................................................................... 22
PMC PROGRAM EXAMPLE ........................................................................................................................................................ 22
CONE-FIRE – HOW IT WORKS............................................................................................................................................ 23
CONE-FIRE PROGRAMS ....................................................................................................................................................... 24
CONE FIRE EXAMPLE ................................................................................................................................................................ 24
REFERENCE SECTION .......................................................................................................................................................... 26
APPENDIX A–LOW FIRE CONE PROGRAMS .............................................................................................................................. 26
APPENDIX B–MID FIRE CONE PROGRAMS............................................................................................................................... 27
APPENDIX C–HIGH FIRE CONE PROGRAMS ............................................................................................................................. 28
APPENDIX D–USER PROGRAM CHARTS................................................................................................................................... 29
APPENDIX E–CONNECTING THERMOCOUPLES......................................................................................................................... 29
APPENDIX F–TYPICAL WIRING DIAGRAM,2HEATERS ........................................................................................................... 30
APPENDIX G–TYPICAL WIRING DIAGRAM,1HEATER,1SAFETY RELAY................................................................................. 30
APPENDIX G–CONFIGURATION OPTIONS................................................................................................................................. 31
LIMITED WARRANTY ................................................................................................................................................................ 32

AF4X Kiln Controller
4
Introduction
This User’s Guide explains the features and operation of the Model AF4X Controller.
The controller has 3 keys for programming.
Orton controllers use P-I-D control algorithms to tightly control kiln temperature. This eliminates temperature
cycling. Cycling occurs when the controller turns the kiln on or off in a way where the actual temperature does not
closely follow the desired firing schedule.
Orton controllers store the firing program information in memory when turned off. If power is lost during a firing,
the controller remembers how far the firing has progressed and determines if it can resume the firing when power
is restored.
Precautions
The controller is not a safety device. The controller operates relays to turn the kiln elements on and off. It is
possible for relays to fail in the ‘ON’ position. The controller cannot protect against relay failure. To prevent over-
firing, never leave the kiln unattended, especially at the end of a firing.
Controller accuracy and performance depends on the condition and position of the thermocouple sensors in use.
Getting Started
Read all precautions and instructions before using your controller.
If your kiln has manual control switches for the heating elements, turn all the dials to the highest settings.
If you have a Kiln-Sitteron your kiln, you can use a Cone 10 bar under the sensing rod to shut off power if the
kiln reaches high temperatures. This bar will last many firings and can act as a backup safety device for the firing.
Features
The AF4X includes many standard features, a user-friendly keypad and robust temperature control software.

AF4X Kiln Controller
5
Firing Methods and Features
•User Program method: Create up to 25 custom firing schedules with unique heating and cooling rates,
target temperatures and hold times. This method can be used for ceramics, heat treating, glass fusing,
enameling or jewelry applications.
•Speed Programs:
5 speed programs are preset with different fixed heating rates. These programs are
single set-point (one step) programs.
•Jewelry Programs: 3 preset firing schedules for burnout. The various heating and cooling steps are
preprogrammed. You can fire to a preset Jewelry schedule by simply selecting the jewelry program
along with an adjustable final hold temperature.
•PMC Programs: 5 preset firing schedules for Precious Metal Clay. The heating steps are
preprogrammed. You can fire to a preset PMC schedule by simply selecting the PMC Program. These
programs are not adjustable.
•Cone-Fire method: Select a preset program for a specific cone number from Cone 022 to Cone 12.
These programs are designed specifically for ceramic firings.
•Speed adjustments - Use with Cone-fire mode to speed up or slow down a firing and to adjust for load
size or thick pieces of ware.
•Delay start - Use with either mode to delay start the kiln up to 100 hours (99hr.59min.)
•Set-Point Control - User Program option to hold kiln at temperature indefinitely.
•Full On / Full Off - User Program option to heat or cool the kiln as fast as possible.
•Add Time – Add additional hold time to firings already in progress.
•Program edit – User Program option to change the active program settings during the firing without
having to stop and restart the controller.
Advanced Options
•Cone Offset - Use with Cone-Fire to adjust the firing temperature of the kiln by ±11°C (±20°F) to fine
tune the controller to your kilns performance.
•Skip - Skip ahead in the firing program
•Alarm - Program an alarm to sound when a specific temperature is reached.
•Thermocouple Offset - Adjust display temperature by as much as ±25°C (±45°F) to offset aging
thermocouple(s).
•Auxiliary Output - Control a relay to switch on a vent fan or safety relay.
•Power Consumption – Review the calculated cost or Kilowatt usage of the kiln firing.
Display Messages and Information
•Program Review - Review the current firing program before or during a firing.
•Temperature Units - Display Temperature in Fahrenheit (°F) or Centigrade (°C) Units
•Computer Interface – Monitor/Analyze kiln data from a PC using AutofireDLS4 datalog software.

AF4X Kiln Controller
6
Test Firing with Witness Cones
A test firing will help in learning the operation and features of the controller. Follow your kiln manufacturer's
instructions for setting up your kiln.
Place a series of Orton Self-Supporting Cones on the middle shelf of your kiln so that they can be seen through a
kiln peephole. Use a series of cones close to the final firing temperature (see Appendix C). For example, if firing to
1945°F (Cone 04), use a Cone 03, Cone 04, and Cone 05 for the test firing.
To evaluate heat distribution, place a set of cones on each shelf during the test firing. Most kilns fire more
uniformly at Cone 06 than they do below Cone 06. Provide ventilation for the kiln in accordance with the kiln
manual or VentMaster
®
instruction manual.
After the firing, examine the fired cones. Some variation in the bending of the cones may occur, depending on how
the kiln was loaded and the location of the cones.
Keypad Overview
This key is for selecting a firing program and advancing through the programming steps. After
programming is complete, use this button to Start and Stop the firing.
This key is used to step forward the display values for specific program settings Also use this button
for access to the option menu.
This key is used to step backwards the display values for specific program settings. It is also used to
activate the Program Review feature.
When using the Increase and Decrease keys to program number values, the values will change more rapidly if the
key is held in.
In general, the user interface is very simple. Use the increase and decrease keys to change the display prompt,
when you see what you want on the display, press the Program key.
Display Lights
The controller uses (4) numerical displays and 3 indicator lights. The bottom light tells when the controller is
turning on the relays to power the heating elements. The top is lit when the controller is in programming mode, the
middle light is lit when the controller is in Program review mode.
Two of the four decimal points on the display are also used as indicators. The decimal point on the far right is used
to indicate if the controller is displaying temperature in degrees Fahrenheit (°F) or Centigrade (°C). If this decimal
point is lit, the controller is set to display temperatures in °C.
The center decimal point (between the second and third digit) lights whenever the display is showing a time value.
The decimal point separates Hours (on the left) from Minutes (on the right).

AF4X Kiln Controller
7
When the Controller is first turned on
The controller runs a brief self-diagnostic test. The display will light up and the audible alarm should beep. After a
few seconds, the display will alternate between the kiln temperature and IDLE.IDLE is the mode where the
controller is not actively firing the kiln or being programmed for a firing.
Starting a Firing
The display shows -ON- for 5 seconds when the firing begins.
The display will show kiln temperature throughout the firing. The temperature display will alternate with
alarm messages if any alarms occur. If the controller is programmed to hold at a specific temperature, the
remaining Hold Time will alternate with the temperature during the active hold period.
Stopping a Firing
When the controller completes the firing, the display alternates 4 messages: CPLT (Firing Complete); Firing
Time (hrs.mins); Final Firing Temperature and Current Kiln Temperature. Press any key to return to IDLE.
If you stop the firing before completion with the Stop key, the display will indicate ABRT (abort) in place of
CPLT. Press Stop again to return to IDLE
Programming values
Whenever a change is made from the keys, you must press the Program/Start key to load the changes. If the
key is not pressed, the controller will simply wait for your next selection. Pressing the Program/Start key will
advance you to the next option if you are setting up a program or changing settings.
Note: If you are programming the controller options and no keys are pressed for 90 seconds, the controller will
exit the options menu automatically.
Program Review
To review the current program in the controller memory before or during a firing, press the Decrease/Review
key. The entire program will automatically scroll through the display and then return to normal operation.
Delay time is included in the review.
Repeating a firing
If power is not cycled off to the controller, you can repeat a firing without viewing the entire program, simply press
the Decrease/review key when the controller display is showing the desired program group. The controller will
scroll through the program review and advance directly to the Start prompt. Press the Program/Start key to set a
delay time and again to begin the firing.
Program Sets
The controller contains several sets of preset programs. Each set can be turned on or off depending on the user
preferences. To disable a program set, see the configuration appendix of this manual.
When first powered on, the controller will show IDLE, to view the program sets, press the Program/Start key.
Then press the Increase/Option key to see all available program sets.
Note: some program sets may be disabled or turned off by the kiln manufacturer or supplier depending on the
application.
Program sets include: SPD (Speed) – JWL (Jewelry) – CLAY (PMC) – CONE (Ceramics) – USER (custom)

AF4X Kiln Controller
8
User Programs
25 User Programs are available. The User Program mode allows you to customize your firing schedule and specify
how fast the kiln heats or cools to any temperature. All Programs allow 20 ramp steps. Each ramp step consists of a
heating rate (or cooling rate), a target temperature and a hold time.
Temperature Units
If your controller is configured to display temperature values in °F, heating rates will be programmed as Degrees
Fahrenheit per hour and target temperatures will be programmed as Degrees Fahrenheit. If your controller is
configured to display temperature values in °C, heating rates will be programmed as Degrees Centigrade per hour
and target temperatures will be programmed as Degrees Centigrade. To change the temperature units, see the F/C
option.
Heating/Cooling Rates
Each program step requires you to program the desired rate value.
Rate is the speed of the ramp step. Rate is programmed as Degrees per Hour if the RATE option is set to HOUR.
Some calculations may be required to determine your desired heating rate.
Example; if you know that you want to heat the kiln from room temperature (75°F) to 212°F over a 2 hour period,
First determine the amount of temperature rise:
212 - 75 = 137 degrees
Then divide the amount of temperature rise (or drop) by the number of hours you would like it to take to get there.
(For Example, 2 hours)
137 /
//
/2 = 68.5 degrees per hour
Round the calculated rate to the nearest whole number and your heating rate would be 69 degrees/hour.
If you prefer to program heating and cooling rates in ‘degrees per minute’, adjust the RATE option in the options
menu to MIN.
If you prefer to program heating and cooling rates in ‘Hours and Minutes’, adjust the RATE option in the option
menu to TIME.
RA is the controller display for rate. Each rate segment will have its own number. The rate for the first ramp step
will be displayed as RA 1, the rate for the second ramp as RA 2 and so on.
Maximum Ramp Rate for User Programs
The range of values available for a controlled ramp rate setting is 0-1798F per hour or 0-29.97F per minute.
To program a rate that heats or cools as fast as possible, Set the rate to FULL. FULL appears as a selection for
1799F/hour or 29.98F/min. Just above the maximum ramp rate. You can also find the FULL setting by pressing
the decrease/review button one time when the display shows zero for the rate setting.
When the RATE option is set for TIME, the maximum ramp rate or FULL setting is 00.00, the range of controlled
rates is 00.01 (1minute) to 99.58 (99hours.58minutes)
When the Ramp Rate is set to FULL the controller will interpret this as full power for a heating ramp. This will
allow the kiln to heat as fast as possible to the target temperature without rate control. If the ramp is a cooling step,
the controller will interpret the same values as no power and allow the kiln to cool as fast as possible without rate
control.

AF4X Kiln Controller
9
A Program Review will show the message FULL to indicate the uncontrolled rate. Deviation alarms will not be
active during the heating/cooling ramp.
Caution: Overshoot in temperature may occur when a kiln is heating at full power, especially at lower
temperatures.
Target Temperatures
Each program step requires you to program a desired target temperature.
°
°°
°
For
°
°°
°
Cis the controller display for target temperature. Like rate, each temperature segment will have its own
number. The temperature for the first ramp step will be displayed as
°
°°
°
F 1 or
°
°°
°
C 1, the temperature for the second
ramp step as
°
°°
°
F 2 or
°
°°
°
C 2 and so on.
Caution: Do not program target temperatures that exceed the temperature rating for your kiln. The maximum
programmable value for target temperatures can be viewed in the SFTY option.
Cooling Ramps
Cooling ramps are programmed the same as heating ramps. You must program the Rate for the cooling and the
target temperature. The criteria for a cooling ramp is the target temperature must be lower than the preceding target
temperature.
If you program a target temperature at the end of the firing that is below your room temperature, the controller will
never be able to complete the firing. This may result in a FTL alarm. To avoid this alarm, manually stop the firing
by pressing the Program/Stop key or program a higher temperature to complete the firing
Changing a Target Temperature During a Firing
If the kiln is firing and you need to modify the current ramp target temperature, use CHGT option. The controller
will display the current setting and allow you to change it. See the Option menu section of this manual for more
details.
Hold Time
Each program step requires you to program a desired hold time.
Hold time refers to the amount of time you want the kiln to remain at the target temperature. Hold Time is often
referred to as Soak or Dwell Time. Each ramp allows the option of programming a hold time. Hold time is
programmed in Hours and Minutes. The decimal point light in the center of the controller display separates hours
from minutes. The two digits to the left of the decimal point indicate hours while the right side indicates minutes.
Example; A 1 hour hold time should be programmed as 01.00
or A 30 minute hold time would be 00.30
During a Hold time, the controller will count-down the remaining time of the Hold on the display.
HD is the controller display for hold time. Each Hold segment will have its own number. The hold time for the
first ramp step will be displayed as HD 1,the hold time for the second ramp step as HD 2 and so on.

AF4X Kiln Controller
10
Set-Point Hold
You can program the controller to hold at a temperature indefinitely by programming a Hold Time of 99.59. The
controller will hold the kiln temperature until the Program/Stop key is pressed.
Adding Time to a Hold
If the kiln is firing and you need to increase the hold time, use the HLDT option. The controller will display the
current setting and allow you to change it. See the Option menu section of this manual for more details.
Shortening a Hold
To end a hold before the time has expired, use the SKIP option to advance to the next ramp. See the Option menu
section of this manual for more details.
Vent Fan (Optional)
If your controller has been configured to control an auxiliary vent fan, each ramp step will allow the fan to be
turned on or off during the specified ramp. Refer to the Options section for additional details on the AOP1 output.
FN is the controller display for vent fan. Each ramp will have its own fan setting. The fan setting for the first
ramp step will be displayed as FN 1,the fan setting for the second ramp step as FN 2 and so on.
Programming User Programs
During programming, default values may appear in the display. If the controller was previously programmed, the
last settings will appear.
1. Press the Program/Start key. A program group will show on the display.
2. Press the Increase/Option key until the display shows USER, then press the Program/Start key.
3. Using the Increase or Decrease key, select the desired program number (PR01-PR25) then press the
Program/Start key.
4. RA 1 shows in the display indicating the rate value for the first ramp step. Use the Increase or Decrease
keys to enter the desired heating rate. Then press Program/Start key.
5. °
°°
°F 1 or °
°°
°C 1 shows in the display indicating the target temperature for the first ramp step. Use the Increase
or Decrease keys to enter the desired temperature. Then press Program/Start key.
6. HD 1 shows in the display indicating the Hold time for the first ramp step. Use the Increase or Decrease
keys to enter the desired time for the kiln to hold at the first target temperature. Time is entered as
(Hours.Minutes). Then press Program/Start key.
7.
FN 1 shows in the display (if available). Use the Increase or Decrease key to select a fan setting; either
OFF or ON for the first ramp. Then press Program/Start key. The Fan option will not appear unless the
auxiliary output option for the controller has been configured.
8. Repeat steps 4 through 7 to program additional ramp rates, temperatures and hold times. After you have
programmed your final ramp, the controller should be displaying the next available RA number. If the
value for the next available ramp rate is set to zero degrees per Hour or Minute, press Enter. The controller
will end the programming mode. For Time mode, the value should be set to 99.59.

AF4X Kiln Controller
11
The controller will advance to STRT. The programmed firing schedule is automatically stored and ready
to START the firing.
9.
If the Delay Start feature is active, the display will show DELA alternating with a Time value. use the
Increase or Decrease key to set a time for the kiln firing to begin. Time is shown as (Hours.Minutes). If no
Delay is needed, set zero hours and zero minutes (00.00). Then press the Program/Start key.
10.
Press the Program/Start key to begin the firing.
Erasing A User Program
If you enter a zero value for a rate (RA #), all settings beyond that point will be erased. This feature can be used to
erase an entire user program by entering a zero rate at RA 1.
User Program Example
Use Program #1 (Bead Annealing)
To fire to 960ºF at 1500ºF/hour
30-minute hold at temperature
Cool down to 500ºF at 100ºF/hour
Shut off.
Follow these steps: starting with the controller at IDLE.
Press Display Shows
…………………………………………. A program group
..……..…………………………………. USER
………………………………………….A program number
………………………………………….PR01
…………………………………………... RA 1 / 0
…………………………………………… 1500

AF4X Kiln Controller
12
……………………………………….….. °F 1 / 32
………………………………………….…. 960
……………………………………………. HD 1 / 00.00
…………………………………………….. 00.30
……………………………………………. RA 2 / 0
…………………………………..……..….. STRT
………………………………..………….... DELA / 00.00
…………………...……………….………..-ON-
Alarms
Alarms are used to notify the operator of problems with the kiln performance or controller performance. Some
alarms will terminate the kiln firing while others allow the firing to continue with the alarm condition on the
display. Some alarms have no affect on the outcome of the kiln firing.
Thermocouple Alarms
- - - - Thermocouple not detected during power up.
FAIL
Thermocouple failed during a firing, firing stopped
TC 2
Thermocouple failed while controller Idle
TCR
Thermocouple polarity reversed , firing stopped
LAG
Thermocouple temperature is lagging, firing stopped (kiln not heating)
OTL
Over Temperature Limit detected – firing stopped (check LIMIT option)
FTL
Firing too Long – kiln temperature has stalled, firing stopped
Deviation Alarms (See TEDE option to adjust Deviation)
FTH
Fail to Heat - kiln is heating too slow, firing continues
FTC
Fail to Cool - kiln is cooling to slow, firing continues
LTDE
Low Temp Deviation - kiln is losing temperature, firing continues
HTDE
High Temp Deviation - kiln is overheating, firing stopped

AF4X Kiln Controller
13
Power Interruption Alarms
PF
Power failed and firing was resumed
PF 1
Power failed during cooling and firing was stopped because cooling temperature exceeded
PF 2
Power failed during heating and firing was stopped because temperature was below 212°F
PF 3
Power failed during heating or hold and firing was stopped because temperature dropped by 72°F
Diagnostic Alarms
BADP
Invalid User Program. Check current kiln temperature is below program temperature.
ETH
Electronics too Hot – controller temperature above 80°C, firing stopped
FE 1
Failed to read or write to memory device
FE 4
Errors detecting thermocouple input signal
Options Menu
Advanced settings and features are available through the Options menu. Press the Increase/Option
Key to advance through the options menu. During a firing, not all options can be changed. To exit
Options, select the EXIT prompt within the option menu.
To view an Option setting, press Program/Start key when the option code is displayed. Use the Increase or
Decrease key to change the setting for the option. Press Program/Start after making the change.
Option List
SKIP Skip Step Skip ahead in the running program
HLDT Hold Time Add Time to the current hold segment
CHGT Change Temperature Change the current target temperature
DELA Delay Change Delay start mode
TC Thermocouple Type Select thermocouple type (Type K, N, S or R
ALAR Threshold Alarm Set Alarm temperature
DIAG/TEST Diagnostics View output amps or test outputs.
F/C Temperature Units Change temperature units to °F or °C
LIM Over-Temperature Limit Set the maximum limit temperature
COST Firing Cost View calculated firing cost
EXIT Exit option menu
OPT2 Level 2 Options
OFST Cone Offset Adjust firing temperature to match witness cones by
±
20
°
TCOS Thermocouple Offset Change a thermocouple temperature reading by
±
25
°
C
TEDE Temperature Deviation Deviation value for alarms FTH, FTC, and LTDE
HTDE High Temperature Deviation Deviation value for alarm HTDE
LOCK Program Lock Lock or Unlock the programs to prevent changes
AOP1 Auxiliary Output #1 Enable a vent fan, external alarm or safety relay output on Output 1
ELEC Electronics Temperature Displays temperature of the electronics
EXIT Exit option menu
OPT3 Level 3 Options
COOL Cone-Fire Cooling Enable or disable cooling option for Cone-fire
RATE Ramp Rate units Select ramp rate units of degrees per hour, minute or Time
CENT Cost per Kilowatt Hour Set firing cost for Kilowatt Hours
KW Kiln Power Rating Set power consumption Kilowatts
SFTY Safety Temperature Displays maximum programmable temperature
SOFT Software Version Displays factory software version
CFG Configuration Number Displays factory configuration #
RST Factory Reset Reset all values to OEM settings.

AF4X Kiln Controller
14
The options list will vary depending on the controller configuration. If the program loaded is not a CONE program,
Cone fire options do not appear.
Level 1 Options
Skip Step - SKIP
The Skip option allows you to end a ramp segment or hold period before the time has expired, use the SKIP option to advance
to a later ramp in the program. This option is available only during an active firing.
Press the Increase/Option key until SKIP appears, then press Program/Start to see the next available ramp. Use the
Increase/Option key to select a new ramp or to cancel, then press Program/Start to exit the option menu.
Hold Time - HLDT
The Hold time option allows you to edit a hold period for the current ramp step, use the HLDT option to add hold time in five
minute increments. This option is available only during an active firing.
Press the Increase/Option key until HLDT appears, then press Program/Start to see the program step hold time. Use the
Increase/Option key to increase the time, then press Program/Start to exit the option menu.
Change Temperature - CHGT
The target temperature can be changed during the active ramp step. Use the CHGT option to edit the temperature setting. This
option is available only during an active firing.
Press the Increase/Option key until CHGT appears, then press Program/Start to see the program temperature. Use the
Increase or Decrease key to edit the setting, then press Program/Start to exit the option menu.
Delay Mode - DELA
To program the controller to begin a firing at a later time, use the Delay start feature. Enter a time delay in Hours.Minutes
format. Delay time is set during the programming sequence just before the firing is started. Once the firing is started, the delay
time will count down on the display.
The DELA option provides a preference for the delay start feature. The settings are:
DFLT - Resets the delay time value to zero after each firing
ALL - Retains the delay time value for all firings
OFF - Removes the delay feature from the programming sequence entirely.
Press the Increase/Option key until DELA appears, then press Program/Start to see the setting. Use the Increase or Decrease
key to edit the setting, then press Program/Start to exit the option menu.
Note: you can skip or end the Delay time once the delay period has started by pressing the Program/Start key.
Thermocouple Type - TC
The TC Option allows Type “K”, “N”, “S”, or “R” thermocouples. The setting must match the actual thermocouples in use.
Settings Meaning
K Type K
N Type N
S Type S
R Type R
Press the Increase/Option key until TC appears, then press Program/Start to see the setting. Use the Increase or Decrease key
to edit the setting, then press Program/Start to exit the option menu.

AF4X Kiln Controller
15
Threshold Alarm -ALAR
To sound an audible alarm when the controller reaches a temperature, Use the ALAR option. When the kiln reaches the alarm
temperature, the display will flash ALAR and the buzzer will sound. Silence the alarm by pressing any key except Stop.
Pressing Stop ends the firing.
Press the Increase/Option key until ALAR appears, then press Program/Start to see the program temperature. Use the
Increase or Decrease key to edit the setting, then press Program/Start to exit the option menu.
Note: You can program the Alarm before you start the firing or reset it during the firing. Setting the alarm value to 32F (0C)
will disable the Alarm.
Diagnostics – DIAG / TEST
Diagnostics allows the operator to check the current draw on the main supply line. The accuracy is +/-1amp. To accomplish
this, the relays are switched on for a brief time period to get a measurement. During a firing, the test cycle is limited to full load
amps with all relays energized.
Note: the controller must be equipped with a current transformer to achieve a result.
Press the Increase/Option key until DIAG appears, then press Program/Start to see the TEST. Use the Increase or Decrease
key to see AMPS on the display, then press Program/Start to view the measurement. When done, the controller will exit the
option menu.
The TEST Option allows the heater outputs to be turned on for 2 minutes while monitoring the thermocouple temperature. You
can press Program/Start key to advance to the next output before the 2 minutes expires. TEST will also activate the Auxiliary
output identified as AOP1.
Press the Increase/Option key until DIAG appears, then press Program/Start to see the TEST. then press Program/Start to
start the test cycle. When done, the controller will exit the option menu.
Change Temperature Units – F/C
The F/C Option allows the temperature units to be displayed in either degrees Fahrenheit (°F) or degrees Centigrade (°C).
Press the Increase/Option key until F/C appears, then press Program/Start to see the setting. Use the Increase or Decrease key
to edit the setting, then press Program/Start to exit the option menu.
Over-temperature Limit - LIM
The LIM Option allows the operator to set a value for the maximum temperature of the kiln.. The operator can set a value as
low as 200F or as high as the Safety Temperature SFTY temperature.
The controller will abort the kiln firing with alarm OTL if the actual thermocouple temperature is detected 1 degree above the
LIM setting.
Press the Increase/Option key until LIM appears, then press Program/Start to see the setting. Use the Increase or Decrease
key to edit the setting, then press Program/Start to exit the option menu.
Firing Cost - COST
To review the current power consumption during or after the kiln firing, use the COST option. The display will show the
calculated electric usage for the firing if the option KW is programmed with a known wattage rating for the kiln. In addition, the
display will show a calculated firing cost if the CENT option is programmed with a known price for KWHR usage. Note: These
calculations are estimates and are dependent on the accuracy of the values set by the operator.
Press the Increase/Option key until COST appears, then press Program/Start key to view the calculation. Press Program/Start
again to exit the option menu.

AF4X Kiln Controller
16
Level 2 Options
Cone Offset - OFST
This offset feature allows you to adjust the final heating step of the Cone programs. This is useful when the kiln does not quite
bend witness cones to the desired angle. Cone Offset is a calibration feature that allows a temperature offset for the final
heating ramp of the cone program.
First, start a CONE program to make the OFST option appear in the option menu. Press the Increase/Option key until OPT2
appears, then press Program/Start key, Press Increase/Option until OFST appears. Press Program/Start to see the setting. Use
the Increase or Decrease key to edit the setting, then press Program/Start to exit the option menu.
OFST settings are stored in memory and will apply to all future Cone fire programs.
Settings (
°
F) Settings (
°
C) Meaning
-20 -11 Decreases final ramp temperatures
-15 -8 Decreases final ramp temperatures
-10 -6 Decreases final ramp temperatures
-5 -3 Decreases final ramp temperatures
0 0 No adjustment in temperatures
+5 +3 Increases final ramp temperatures
+10 +6 Increases final ramp temperatures
+15 +8 Increases final ramp temperatures
+20 +11 Increases final ramp temperatures
Thermocouple Offset - TCOS
This offset adjusts the thermocouple reading on the controller up to ±45°F(25°C). TCOS can be used to compensate for
inaccurate temperature readings resulting from aged or poorly positioned thermocouples. Temperature offset applies to all
firings.
To Program the offset, Press the Increase/Option key until OPT2 appears, then press Program/Start key, Press
Increase/Option until TCOS appears. Press Program/Start to see the setting. Use the Increase or Decrease key to edit the
setting, then press Program/Start to exit the option menu.
If you want the kiln to fire Hotter, the display will show zero for offset, press the Increase key to see H-1. Continue pressing
until the desired thermocouple offset shows in the display (e.g. H-15 for a 15°offset) and press Program/Start.
If you want the kiln to fire Cooler, the display will show zero for offset, press the Decrease key to see C-1.Continue pressing
until the desired thermocouple offset shows in the display (e.g. C-10 for a 10°offset) and press Program/Start.
Temperature Deviation - TEDE
The TEDE Option sets a temperature deviation value to activate an audible and visual alarm. The temperature deviation
applies to the following alarms - FTH, FTC and LTDE. The factory setting is 100°F (56°C). The alarms can be disabled by
setting the value to zero.
Press the Increase/Option key until OPT2 appears, then press Program/Start key, Press Increase/Option until TEDE appears.
Press Program/Start to see the setting. Use the Increase or Decrease key to edit the setting, then press Program/Start to exit
the option menu.
High Temperature Deviation - HTDE
The HTDE Option sets a temperature deviation value to abort the kiln firing. The temperature deviation applies only to the
HTDE alarm. The factory setting is 100°F (56°C). The alarm cannot be disabled. The range is 18ºF – 200ºF (10ºC - 111ºC)
Press the Increase/Option key until OPT2 appears, then press Program/Start key, Press Increase/Option until HTDE appears.
Press Program/Start to see the setting. Use the Increase or Decrease key to edit the setting, then press Program/Start to exit
the option menu.

AF4X Kiln Controller
17
Program Lock Mode - LOCK
The LOCK Option allows individual User Programs or a Cone Fire programs to be locked into memory, preventing the settings
from being changed.
LOCK requires a passcode to enable this feature, the default passcode is ‘3’. Once enabled, the user can set a new passcode
that is private. Lock options will appear at the end of each program sequence. If the passcode is entered during the program
sequence, the program will no longer be available for editing without the passcode.
To turn off the lock feature, the passcode must be re-entered. To reset the passcode, see RST option
Press the Increase/Option key until OPT2 appears, then press Program/Start key, Press Increase/Option until LOCK appears.
Press Program/Start to see PASS. Use the Increase or Decrease key to set the passcode then press Program/Start. use the
Increase or Decrease key to change the setting or to set a new passcode, then press Program/Start.
Auxiliary Output 1 - AOP1
The AOP1 Option sets the Auxiliary relay output to the desired functions for controlling a Vent fan, External alarm or Safety
relay. Setting the AOP1 option to VFAN enables the FN ramp segment for User Programs.
Settings Meaning
NONE No external relay functions
VFAN Vent fan is enabled on output 2
ALRM Alarm is enabled on output 2
SAFE Safety Relay is enabled on output 2
Press the Increase/Option key until OPT2 appears, then press Program/Start key, Press Increase/Option until AOP1 appears.
Press Program/Start to see the setting. Use the Increase or Decrease key to edit the setting, then press Program/Start to exit
the option menu.
Electronics Temperature - ELEC
ELEC displays the controller electronics temperature. This can be useful in monitoring the electronics temperature in hot
environments or for diagnosing a controller problem. The ETH alarm will activate if the controller temperature is above 80°C
(176°F)
Press the Increase/Option key until OPT2 appears, then press Program/Start key, Press Increase/Option until ELEC appears.
Press Program/Start to see the result. Press Program/Start to exit the option menu.
Level 3 Options
Cone-fire Cooling Ramp - COOL
The Cooling Option is used for Cone-fire programs only. The controller programming sequence for Cone-fire can include a
cooling step at the end of the firing or this option can be removed from the programming sequence.
Settings Meaning
OFF COOL options inactive and will not appear for Cone-fire
ON COOL option active and will appear for Cone-fire
First, start a CONE program to make the COOL option appear in the option menu. Press the Increase/Option key until OPT3
appears, then press Program/Start key, Press Increase/Option until COOL appears. Press Program/Start to see the setting.
Use the Increase or Decrease key to edit the setting, then press Program/Start to exit the option menu.

AF4X Kiln Controller
18
Ramp Rate Units - RATE
The RATE Option sets the units for programming and review of heating and cooling rates. The factory default setting is for
Degrees per Hour.
Settings Meaning MAX ‘FULL’ rate
HOUR Degrees per Hour 999°C (1799°F)/Hour
MIN Degrees per Minute 16.65°C (29.97°F)/Minute
TIME Time to Temperature (Hours.Minutes) 00.00 Hours.minutes
Press the Increase/Option key until OPT3 appears, then press Program/Start key, Press Increase/Option until RATE appears.
Press Program/Start to see the setting. Use the Increase or Decrease key to edit the setting, then press Program/Start to exit
the option menu.
Kilowatt Hour Cost - CENT
The CENT Option allows the operator to set a value for the Kilowatt Hour usage of the electric service. This value is used to
calculate a firing cost for review on the controller display. The value must be entered by the user, it can usually be found on
your electric bill. Cost calculations first require a second value entry in the KW option. Cost calculations are only as accurate as
the programmed variables. To view the cost calculations, see the COST option.
Press the Increase/Option key until OPT3 appears, then press Program/Start key, Press Increase/Option until CENT appears.
Press Program/Start to see the setting. Use the Increase or Decrease key to edit the setting, then press Program/Start to exit
the option menu.
Kilowatt rating - KW
The KW Option allows the operator to set a value for the Kilowatt rating of the kiln. This value is used to calculate a
Kilowatt/Hour usage for review on the controller display. The wattage rating must be entered by the user, it can usually be
found on the kiln manufacturer label. KWHR and COST calculations are only as accurate as the programmed KW value. To
view the KWHR or COST calculations, see the COST option.
Press the Increase/Option key until OPT3 appears, then press Program/Start key, Press Increase/Option until KW appears.
Press Program/Start to see the setting. Use the Increase or Decrease key to edit the setting, then press Program/Start to exit
the option menu.
Safety Temperature - SFTY
This option displays the maximum programmable temperature allowed by the controller.
Press the Increase/Option key until OPT3 appears, then press Program/Start key. Press Increase/Option until SFTY appears.
Press Program/Start to view the setting. Then press Program/Start again to exit the option menu.
Software Version - SOFT
SOFT displays the factory software version of the controller.
Press the Increase/Option key until OPT3 appears, then press Program/Start key. Press Increase/Option until SOFT appears.
Press Program/Start to view the version number. Then press Program/Start again to exit the option menu.
Configuration Number - CFG
CFG displays the factory configuration number. this identifies the controller model.
Press the Increase/Option key until OPT3 appears, then press Program/Start key. Press Increase/Option until CFG appears.
Press Program/Start to view the configuration number. Then press Program/Start again to exit the option menu.

AF4X Kiln Controller
19
Reset - RST
The RST feature restores the original OEM values supplied with the controller. Do not perform a reset unless all other efforts to
correct faults with the controller have failed. A reset may change important option settings for your kiln. Before attempting a
reset, you should become familiar with the correct option settings for your controller. Most important is the TC option setting.
To reset, Press the Increase/Option key until OPT3 appears, then press Program/Start key. Press Increase/Option until RST
appears. Use the Increase or Decrease key to edit the setting from NO to YES and press Program/Start. This will reset the
controller settings. Verify the controller is accurately displaying temperature after the reset. You may need to adjust the TC
setting for the thermocouple and the F/C setting for the display temperature.
Hardware Options
Audible alarm buzzer
The audible alarm can be disabled by removing the circuit board jumper on the back side of the controller. remove
the jumper shunt labeled BUZZ ENABLE along the top edge of the circuit board.
Door/Lid switch
An optional door switch can be installed and connected to the controller. If not used, a jumper shunt is placed at
circuit board location labeled LID.
LID is also a display alarm that indicates when the switch connection is open.
The door switch acts an optional safety device to prevent the relay outputs from being energized whenever the kiln
door or lid is open.
Computer software
Computer software is available for remote monitoring and datalogging. The controller has a USB interface that
outputs TIME, Temperature and Setpoint data. For more information on the optional computer software, contact
Orton or visit www.ortonceramic.com
Speed Programs
5 speed programs are preset firing schedules with different fixed heating rates. These programs are single set-point
(one step) programs.
The 5 programs are;
Display code
Program
Rate Target Hold
SPD1 Speed 1 200F(111C)/hour 1112F(600C) * 00.00 *
SPD2 Speed 2 500F(278C)/hour 1112F(600C) * 00.00 *
SPD3 Speed 3 1000F(555C)/hour
1112F(600C) *
00.00 *
SPD4 Speed 4 1500F(833C)/hour
1112F(600C) *
00.00 *
SPD5 Speed 5 Full 1112F(600C) *
00.00 *
* The operator can adjust the final firing temperature and optional hold time
For information on rates, target temperatures and hold times, see the user program section of this manual.

AF4X Kiln Controller
20
Speed Program Example
To fire at Speed 4 (1500F per hour), to 960F with a 15 minute hold at temperature.
Follow these steps: starting with the controller displaying IDLE
Press Display Shows
…………………………………………. a program group
..……..…………………………………. SPD
……………….………………………….a Speed number
………………………………………….SPD4
………………………………………… o F 1 / 1112
………………………………………… 960
………………………………………… HD 1 / 00.00
….……………………………..………. 00.15
………………………………………… STRT
……………………………………….... DELA / 00.00
…………………...……………………..-ON-
This manual suits for next models
1
Table of contents
Other Orton Controllers manuals
Popular Controllers manuals by other brands

Samson
Samson Type 5824 Mounting and operating instructions

DUNIWAY Stockroom
DUNIWAY Stockroom Terranova 906A instruction manual

Newport
Newport MM4006 user manual

ILX Lightwave
ILX Lightwave LDC-3700 Series instruction manual

AAON
AAON Orion VCCX2 Technical guide

SMC Corporation
SMC Corporation LECSB Operation manual

Desoutter
Desoutter CVIR II Operator's manual

Grundfos
Grundfos Vaccuperm VGA-117 Installation and operating instructions

Cansec
Cansec H1000 installation guide

clage
clage DTK Operating and installation instructions

Distech Controls
Distech Controls VA-024ZS Series Hardware installation guide

Tylo
Tylo IR-Eye Installation instruction