Connected Lighting Module | Installation guide
Top mounting
Side mounting
8
Mounting and Labeling
Placement of barcode labels:
1. Place one barcode on the fixture next to
the CLM mounting location.
2. Tape the bag containing the remaining
barcode label to the top surface of the
fixture. This can be easily found by the
commissioning team during installation.
Note: If these instructions are not adhered to or the
barcode is not shipped with the luminaire, problems
will arise during installation.
End-of-Line (EOL) Testing
The end-of-line testing routines for 58050 (ZBHA-CLM-DIM
for ZigBee wireless network) and 57400 (ZBHA-CLM-DEXAL)
involve a pre-programmed test routine.
When the luminaire is powered, the fixture turns ON and
reaches its full output. The CLM then cycles through the entire
dimming range starting from 100% output level to OFF* two
times. This confirms that the module is receiving power and is
able to communicate the dimming signals to the power supply.
The blinking of the LED module is also an indicator that the
module has not been paired and that it is actively scanning for
open networks. The end-of-line testing routine repeats at each
power cycle. Before commissioning, this routine can be used
to determine if a device has been paired to a network.
To test 45678 (ZBHA-CLM-DIM for ENCELIUM ZigBee
Wireless Network) at end of line, use the OSRAM Wiring Test
Tool (56306) to toggle the luminaire ON and OFF and go
through a defined dim to minimum sequence prior to
commissioning. This would indicate that the CLM is wired
correctly and ready to be paired to an open network. For more
information, please refer to the Wiring Test Tool User Guide.
*Only when dim-to-off feature is enabled via the OT Programmer for OPTOTRONIC®LED Power Supply. If feature set not enabled,
the fixture would go to the minimum dimming level.