
4. Timer operation.
a. Start with all trip pins towards the center of the timer dial.
b. Push out from the center all trip pins that are between the times the aerator or lighting is
to operate.
c. Turn the outer dial clockwise to align the time of day to the stationary arrow positioned at
“2 o’clock”. Close the panel and turn the main disconnect on. When the main disconnect is
off or in the case of power failure the timer/s will not operate and the time of day will need to
be reset.
d. Timer control of the unit and lighting is enabled when in AUTO.
B. Energizing the Unit (To be performed by a qualified technician)
1. Single Phase Units: Motor rotation is factory determined and not field adjustable.
2. Three Phase Units: Verify correct motor rotation (Counter Clockwise looking at the top/impeller end of the unit). Check
current readings on each phase. Verify three phase operating currents are balanced within 5%.
To calculate the percent of current unbalance:
Determine the Average Current:
a. Measure each of the three phase currents
b. Add the three phase amperage values together.
c. Divide the sum by three.
d. This is the average current value.
Determine Current Unbalance:
a. Select the phase current with the greatest difference from the average (calculated above).
b. Determine the difference between this phase current and the average current value.
c. Divide the difference by the average.
d. Multiply the result by 100 to determine percent of unbalance.
3. Use connection diagram 1, 2 or 3 at right which results in the
lowest current unbalance. Roll the motor cable leads on the
aerator output terminal block in the
same direction to avoid motor reversal. If the current unbalance
is not corrected by rolling leads, locate the source of the
unbalance and correct it.
a. When the phase farthest from the average stays on the
same power lead after being moved the primary cause of
unbalance is the power source.
b. When the phase farthest from the average moves on each of
the hookups with a particular motor lead, then the primary DIAGRAM 1 DIAGRAM 2 DIAGRAM 3
cause of unbalance is the "motor side" of the circuit.
Consider: damaged cable, leaking splice, poor connection, or a faulty motor as possible causes.
4. After unit is operational record the operating voltage, amperage, power control center serial number, power cable
length and cable gauge on the label inside the power control panel.
MAINTENANCE
Your Otterbine aerator requires periodic maintenance
A. Once a year, disconnect the unit from the power source and physically inspect the aerator and underwater cable for
any cuts, cracks or breaks. These may cause oil leaks and/or electrical shorts. Inspect and clean the pumping chamber
components and screen.
B. After every three running seasons, a simple oil change is necessary to keep your unit running smoothly. Otterbine oil
must be used for this oil change. Please contact your local Otterbine distributor to order a maintenance kit, P/N: 12-0077.
WARNING: Use the oil level gauge. Do not overfill motor housing with oil.
When a unit is properly cared for, it will give you years of trouble free service.
If a problem does arise, please contact your Otterbine distributor or the factory directly at 1-800-AER8TER.
WINTERIZATION
Damage caused to the motor due to freezing will not be covered under warranty
In locations with extended periods of freezing temperatures the aerator may become frozen into the water possibly
causing damage.
Otterbine recommends the following Concept 3 units be removed from the water during freezing temperatures: ROCKET,
PHOENIX, TRI-STAR, CONSTELLATION, COMET, GENESIS, EQUINOX, and OMEGA.
The GEMINI, SATURN, and SUNBURST pump higher volumes of water which helps to keep the water around the aerator
from freezing and 24 hour a day operation will further decrease the opportunity for the unit to freeze-in, although during
periods of extremely cold temperatures this will not prevent the water from freezing.
TIME OF DAY ARROW
TRIP PINS
AERATOR
AERATOR
AERATOR