OUMAN WL-Base User manual

Wireless sensor system
= Base station
= Routing wireless sensor
= Wireless sensor
22°22°22°
22°22°22°
22°22°22°
General description
The wireless Ouman sensor system
enables a quick and easy reading of
precise room temperature data in a
building without the laborious laying of
cables and drilling of walls. The sensor
system comprises a base station, sen-
sors that act as routers and are con-
nected to the mains, and battery-op-
erated wireless sensors. A predefined
register list makes it easy to connect
the wireless sensors to a SCADA sys-
tem. In the event of failure, a damaged
sensor can be replaced without chang-
ing the register list. This makes the
installation of the replacement sensor
quicker and easier.
The mesh structure of the wireless network improves network reliability. The signal has multiple routes, from
which the system automatically selects the strongest. The larger the number of routers in the coverage area,
the more routing options the signal has. One wireless base station can monitor data from up to 100 sensors.
GW Internet
connection
Internet / Ounet
PC in internal network
Initial engineering in network construction:
• Building structures are crucial in network engineering. Metal structures weaken the signal, which is also the case for
lift wells, electrical power centres, fire doors, etc.
• Old concrete buildings are easier in regard to networks than buildings constructed in the 2010s, where the amount
of steel in the structures is higher.
• From the base station, the network should be built by first finding a suitable “backbone” for the network and applying
the operating voltage to the sensors, so that they will act as routing elements in the network. See FIGURE 1.
• Once the network is operational in this regard, battery-operated sensors are placed as part of the network.
• The positioning of room sensors must take into account that the sensor should never be exposed to direct sunlight.
It must also be ensured that no other external sources of heat aect the sensor, such as refrigerators, television sets,
ventilation windows, water radiators, etc.
• It is often the easiest way to place the base station to the same space with the automation substation (heat distribu-
tion room, AHU room), but due to the weak 3G signal the optimal location can also be in the other parts of the build-
ing. Centrally selected location for the base station can improve the functionality of the sensor network, because
more sensors can be directly connected to the base station without routers.
• It is able to select external antenna to the base station which improves reception of the sensor network when need-
ed to achieve better signal levels.
• The base station requires a separate housing, e.g. K118 which also includes the needed power supply. (must be ap-
plied when certain IP protection class is needed)
FIGURE 1 structure of wireless sensor network
Base station connections:
– Direct connection to base station with browser. (over the Internet/locally)
– Ounet connection directly from the base station. (over the Internet)
– local Modbus RTU connection.
(Connections can be utilised simultaneously)

Commissioning the wireless network through the Internet connection
Base station 1. First install the base station.
2. Connect the antenna (or the extra antenna with an extension
cord) to the antenna connection of the base station. Do not detach
or attach the antenna when the base station is live!
3. Connect the Ethernet cable between the base station's RJ45
connector and the Internet connection (router/3G modem).
4. Switch on the operating voltage. The voltage is connected to the
terminal strip and ground to the adjacent connector.
5. Wait for the LINK light to remain green. This may take a couple of
minutes.
6. When the LINK light remains green, the base station has suc-
cessfully been connected to the Ouman ACCESS network.
7. If you have a QR reader, read the QR code of the base station
label. In other case, enter the label’s website address in your Web
browser.
8. Perform base station login. The default password is indicated in
the label on the side of the base station. Username = service
9. Upon your first login, the system proposes that the password be
changed. We recommend that you do that. If you do not change the
password, the default password will remain (each base station has
a unique password).
In addition, you can specify a user password in the base station; the
user password only entitles you to view measurement data. User-
name = user, password = Wireless
10. Switch on installation mode in the user interface. The RF status
of the base station is green (see p. 6 Web UI Figure 2, Section 4.)
11. It takes about one minute for the installation mode to be activat-
ed. After that, the mode will remain active for 90 minutes, unless
you interrupt it in the user interface (you can adjust the default
time in the base station settings).
12. Go to “sensor commissioning” (p. 4).
2
3
4
A B
Installation
Base station The base station is mounted to a wall or to the centre with a DIN bar.
In the centre installation, the base station requires an external an-
tenna. The base station must be installed indoors (0°C...+50°C).
The base station can be connected to Ounet, or independently to the
Internet, in which case, measurement data can be inspected from
outside the property through a remote connection. If the property
already has an Internet connection, you can use it. If there is no In-
ternet connection ready, we recommend you use the 3G connection
provided by Ouman.
The base station can also be directly connected to the computer in
the local internal network, and as part of the rest of the automation
system through the modbus RTU route.
Temperature sensor / routing temperature sensor:
1
Rooms sensors can be mounted to the wall with screws or adhesive
tape. Please note that the sensor is installed so that the black termi-
nal strips are in the bottom left corner 1.
Place the room sensor at a height of about 150 cm in a location
where it measures the average temperature of the room. Do not in-
stall the room sensor in a location where direct sunlight or another
source of heat may distort the measurement result.
The room sensor must be installed indoors (0°C ... +50°C). External
temperature measuring, digital input or transmitter measurement
(see page 5) can be connected to the sensor by using the room sen-
sor’s AUX connection
PLEASE NOTE: When connected to an external power source (5
VDC), the room sensor is a routing room sensor, but when equipped
with AA batteries, it acts as a room sensor. The room sensor will au-
tomatically recognise the power source.
7
10
5

Base station signal light legend
INIT / ERR
Red light is on
Blinking green light
Upon start-up, the light will be red for about 30 seconds.
The light is green and blinking when the base station is active.
LINK
Yellow light on
The light is almost continuously on,
but is o at times.
The light is o most of the time, but
blinks at times.
No light
The light is on when the connections are in order (both the In-
ternet connection and the ACCESS connection are operational)
Internet connection is operational, but there is no ACCESS con-
nection
LAN connection is operational, but there is no Internet and AC-
CESS connection.
No LAN connection.
If the LINK LED is not blinking or is not on at all, check that the
LAN cable is properly connected to the base station and router.
The signal lights of the base station's Ethernet connector are on
if the network cable is physically in order and connected.
RF STATUS
Green light on
Blinking green light
The base station is in installation mode
The base station is in normal mode
1
2
3
4
A B
Commissioning the wireless base station without the Web browser interface
1. Connect the antenna (or the extra antenna with an extension
cord) to the antenna connection of the base station. Do not de-
tach or attach the antenna when the base station is live!
2. Switch on the operating voltage. The voltage is connected to
the terminal strip and ground to the adjacent connector.
3. Press the base station's installation mode button.
4. Check that the RF-Status light of the base station is on. When
the light is green, the commissioning mode is active.
5. Go to “sensor commissioning” (p. 4).

Room sensor battery replacement The Web UI shows the remaining battery life of each wireless
sensor. If life is less than 10%, the figure is red, and there is a red
exclamation mark in the right upper corner of the user interface.
Battery replacement does not require any special measures. You
only need to replace batteries with fresh ones. The sensor is au-
tomatically connected to the network, and continues to operate
as usual.
Commissioning the sensors
1. Commission the base station before commissioning the sen-
sors (see pp. 2–3).
2. Open the room sensor's cover and install the batteries or
switch on the operating voltage if you intend to make the sen-
sor a routing sensor. Do not put batteries in the sensor if you
apply the operating voltage to the sensor!
3. The LEDs indicate the network status when the batteries are
connected or when the operating voltage is applied:
In commissioning mode:
Rapidly blinking green light = Connected to network
Red light blinking 2 times = Connection failure
When the button is pressed in normal mode:
Green light on (3 s.) = Connected to network
Red light blinking 2 times = Not connected to network
4. If neither LED is blinking rapidly, briefly press the sensor in-
stallation button.
5. If the network is not found, move closer to the base station or
the already installed routing sensor.
6. You can remove the sensor from the network by keeping the
installation button pressed down for five seconds. (You also
need to separately remove the sensor from the user interface).
(see p. 6)
Sensor configuration
1. When the sensor has found the network, it will automatically
appear last in the user interface list (or in place of a sensor re-
moved from the list).
2. You can edit the default name (SensorX) of the added sensor
to match the location. Example: Room 101 (see p. 6 Web UI, Fig-
ure 2)
3. In the sensor route table, you can see how the added sensor
is connected to the network (see p. 7 Web UI, Figure 3). Please
note: The sensor will automatically find its route by the best re-
ception. You cannot change the route manually.
4. Set the failed response alert limit and updating interval for
the base station on a sensor-specific basis. (see p. 5 Web UI, Fig-
ure 1)
Instructions: You can define joint maximum and min-
imum limits for all base station sensors. (Default 21°C
and 24°C) Example: if the calculation interval is 10 h
and temperature is 2h of the timeline over the max-
imum limit or under the minimum limit → The perma-
nence value is 80% for the calculated time.
5. Likewise, the calculation interval of the permanence value.
(see p. 5 Web UI, Figure 1)
The RSSI figure indicates signal strength
Good … -85dBm
Medium: -85 … -95dBm
Poor: -95dBm ...
Pay extra attention to the reception of the rout-
ing sensors, because they are the “backbone” of
the network (see FIGURE 1, p. 1).
2
43

AUX connection of wireless room sensor
12
43
21 + -
In the wireless sensor or routing sensor, it is possible to connect
an external temperature measurement, digital input, status data
or 0–10 VDC transmitter measurement by using the AUX con-
nection.
AUX connection in temperature measurement 1. Connect temperature measurement in terminal strips 3 and 4
AUX connection as digital input 1. Connect the digital input in terminal strips 3 and 4
AUX connection as transmitter measurement 1. First remove the jumper on the battery side from the sensor's
circuit board
2. Connect the transmitter measurement to terminal strips 2 and
3 (power source's ground )
AUX connection settings from WEB UI:
Web UI, Figure 1
1. Select the type of
AUX input in the drop-
down menu.
2. You can name the input
as you like. The name will
appear in the AUX connec-
tion tooltip in the Web UI.
Setting the stability inter-
val for the sensor's perma-
nence value (see p. 5).
Usually, you do not need to adjust other settings.
2
1
1
1
Reception alert will be
indicated with a red
exclamation mark in
the right upper corner
of the Web UI.

4. You can also enter
the installation mode
through the Web UI
by clicking this icon.
To exit the installation
mode, click the icon. Or,
if you do not do that, an
automatic exit will take
place after 90 minutes.
2. Select “Edit location”
to rename the sensor
location.
3. Enter a new, unique
name for the sensor
location.
1. Click the icon with
three dots, and the func-
tion menu will open.
Web UI, Figure 2

Web UI, Figure 3
Base station configuration
OK button – In the installation mode, the sensor sampling interval is 10 seconds by default. When there are 15 or more
sensors in “join mode”, the sampling interval will slow down the device. When you press “OK”, the sensor’s sampling inter-
val will change to two minutes, which will accelerate the device.
If you do not change the sampling interval in the install mode, it will automatically change to 15 minutes when you exit
the install mode. The minimum sampling interval is one minute.

Base station sensor settings
1
2

Selections of average calculation
Go to the “Sensor selection” tab or the sensor-specific settings to select the measurements to be included in the calculation.
Avg calculation time span: The calculation can be performed as sliding for a specific period. If the value is 0, the value is an “on-
line” value.
Normal: Will calculate the average of all sensors included in the calculation
Min – max limited: In the calculation, this function removes measurements not in the minimum and maximum range
Pick out mode: This function removes the selected number of measurements from the calculation. Example: The two lowest tem-
peratures and the highest temperature.
Min - max and pick out combination” A combined selection of the above. The program will first perform the selection and then the
limiting process.

Base station configuration

xx.xx.xx.xx
xx.xx.xx.xx
xx.xx.xx.xx
xx.xx.xx.xx
xx.xx.xx.xx
The base station will automatically retrieve
the network settings once the device is
connected to the network and the power is
switched on.
You can open the function menu by clicking
the three dot icon in the upper right corner
of the Web UI. You can download a modbus
CSV file, Ounet template and a Modbus RTU
template onto your computer. The menu
also includes the Web UI version informa-
tion, password change, and logout.

Temperature sensor / routing temperature sensor
Case ABS plastic
Operating temperature 0°C...+50°C
Protection class IP20
Measurement accuracy +- 0.2°C
NTC-10 thermistor 10kΩ/ 25°C
AUX temperature measurement
Operating temperature
Measurement accuracy
AUX 0-10VDC measurement accuracy
-30°C...+50°C
+/- 0.3°C
0.5% / 50mV
Power source when used
as temperature sensor
2 x AA batteries
Battery life (not included in delivery):
Energizer L91 Ultimate Lithium 3100 mAh:
15 min measurement interval
60 min measurement interval
Energizer EN91 2800 mAh
15 min measurement interval
60 min measurement interval
Key factors aecting battery life:
– Sampling interval
– Ambient temperature
– Sensor placed in a weak field
(Occasionally dropped out from the network)
9.5 years
11 years
6 years
7.5 years
External power source (operated as routing
temperature sensor)
5 VDC
Dimensions 80 x 85 x 30 mm
Installation Surface installation
Base station
Case ABS plastic
Operating temperature 0°C...+50°C
Protection class IP20
Measurement interval in installa-
tion mode
10 seconds
Measurement interval in normal
mode
can be adjusted (1–240
min).
Dimensions 80 x 85 x 30 mm
Installation Mounted to DIN bar
Operating voltage 24 VAC / 5.5 VA
or
10...30 VDC / 3W
Power consumption in use 12 VDC 160mA
24VDC 85mA
24 VAC 210mA
Network size up to 100 sensors
Technical details
Base station
– Access feature
– Built-in Web server to facilitate installation
– Short measurement interval in installation mode
– Ethernet, Modbus TCP/IP
– RS-485, Modbus RTU slave
Temperature sensor:
• Built-in antenna
• Sensor coverage is not impaired when the
battery is low.
• 868 MHz ZigBee technology
• Connector for outdoor temperature sensor
(with a fixed cable connection to outside)
• Option to connect second temperature
measurement, 0–10 V transmitter measure-
ment or contact terminal information.
OUMAN OY
www.ouman.fi
NOTE! Base station should not be connected to the public internet without firewall! That is, for example, a fixed IP address that
is visible from outside network. Typically 3G-modem, adsl/wdsl/cable modem operates firewall functionality, wherein the separa-
te accessory is not required.
17052016
Table of contents
Other OUMAN Microphone System manuals