
Operation and Maintenance Manual Nova Series
20
Constant Pressure
• Supply and return fans are controlled in relation
to the pressure in the Supply and return ducts
respectively.
• The system must be equipped with two separate
pressure transmitters, one in the Supply duct and
the other in the return duct.
• Pressure transmitters of PTH type are suitable.
• Pressure transmitters used to measure pressure
dierences across the fans cannot be omitted as
these are used to regulate the air flow.
Constant Flow
• Supply and return fans are controlled in relation
to flow/air volumes in the Supply and return
ducts respectively.
• Air volumes are measured/calculated by
measuring the dierence between static and
dynamic pressure across the fan.
• The dierence between static and dynamic
pressure is measured by means of pressure
transmitters, either the pressure transmitters built
into the OJ-Air2 FanIO or pressure transmitters of
PTH type.
Return Slave
• The Supply fan is controlled in relation to the
pressure in the Supply duct while the return fan
is controlled as a slave of the Supply fan with a
freely selected oset.
• The system need only be equipped with pressure
transmitters in the Supply duct.
• Pressure transmitters of PTH type are suitable.
• Pressure transmitters used to measure pressure
dierences across the fans cannot be omitted as
these are used to control the air flow.
Supply Slave
• The return fan is controlled in relation to the
pressure in the return duct while the supply fan
is controlled as a slave of the return fan with a
freely selected oset.
• The system need only be equipped with pressure
transmitters in the return duct.
• Pressure transmitters of PTH type are suitable.
• Pressure transmitters used to measure pressure
dierences across the fans cannot be omitted as
these are used to control the air flow.
Constant VOC/CO2
• The system must be configured with a CO2
sensor.
• The CO2 sensor can either be positioned in the
room as a room sensor or in the return duct as a
duct sensor.
• Irrespective of whether the CO2 sensor
is a room or duct sensor, the CO2
sensor must be configured under “OJ
Modules>Configure>Analogue I/O”.
VOC/CO2 Control
• If the system is not configured for “Recirculation”,
the CO2 concentration in the room is controlled
by regulating air volume via fan speed.
• If the CO2 level in the room rises, fan speed is
increased, thus increasing air volume/air turnover
towards the max. air volume setting.
• If the CO2 level in the room falls, fan speed is
decreased, thus reducing air volume/air turnover
towards the min. air volume setting.
Constant Motor Speed
• Supply air and return air fans will be controlled
on a fixed speed according to the setpoints here
– low (medium if selected) high speed.
• Setpoints can be set individually for supply air
and return/exhaust on low (medium if selected)
high speed.
• If medium speed is not available: Check if
medium speed is configured under: OJ Modules
> Configure > Settings)