2.1.2. Frequency Instruction for Compressor Operation (Page: 18 - 20)
Table on Frequency Number
No. Frequency (Hz) Remarks
E9BKP E12BKP
13 39.0 52.0 Fc
15 47.0 62.0 Fc max. (E9BKP)
16 49.0 67.0 Fc max. (E12BKP)
17 56.0 68.5 Fh
30 90.0 110.0 Fh max.
Table on Initial Frequency Zone
Temperature, X (°C) Freq. No. - E12BKP
(Intake Air - Internal Setting) Cooling
X < -2.5 1
-2.5 X < -1.5 1
-1.5 X < -1.0 1
-1.0 X < -0.5 1
-0.5 X < +1.0 4
+0.5 X < +1.0 6
+1.0 X < +1.5 9
+1.5 X < +2.5 16
X+2.5 16
Table on Shifting Frequency Zone
Temperature, X (°C) Zone Frequency No. Shifting:
(Intake Air - Internal Setting) Cooling Mode / Soft Dry Mode Heating Mode
X-2.5 0Shift to Freq. MIN Shift to Freq. MAX
-2.5 X-1.5 1Shift to Freq. MIN Shift to Freq. MAX
-1.5 X-1.0 2-2 Freq. No. +2 Freq. No.
-1.0 X-0.5 3-1 Freq. No. +1 Freq. No.
-0.5 X+1.0 4Same Freq. No. Same Freq. No.
+0.5 X+1.0 5+1 Freq. No. -1 Freq. No.
+1.0 X+1.5 6+2 Freq. No. -2 Freq. No.
+1.5 X+2.5 7Shift to Freq. MAX Shift to Freq. MIN
X+2.5 8Shift to Freq. MAX Shift to Freq. MIN
Condition: Freq. no. for E9BKP Freq. no. for E12BKP Remarks
MIN MAX MIN MAX
Cooling Mode 115 116 (a)
- if remote controller set 28°C & fan speed =
Hi 715 716 (a), (c)
- if remote controller set 28°C & fan speed =
Me-, Me, Me+, Auto 515 616 (a), (c)
- if remote controller set 28°C & fan speed =
Lo 415 516 (a), (c)
- if Powerful Mode ON 715 716 (a), (c)
Soft Dry Mode 4 7 4 8
Heating Mode 130 130 (b)
- if remote controller set 18°C & fan speed =
Hi 10 30 10 30 (b), (d)
- if remote control set 18°C & fan speed =
Me-, Me, Me+, Auto 930 930 (b), (d)
- if remote controller set 18°C & fan speed =
Lo 830 830 (b), (d)
- if Powerful Mode ON 10 30 10 30 (b), (d)
(a) If frequency decreases from MAX, the following frequency performed will be depending to outdoor temperature, as given in below table
(for 30 seconds only) and then continues as normal rule.
(b) (If frequency increases from Freq. No. 17, the following frequency performed is as below (for 30 seconds only) and then continue as
normal rule.
(c) When temperature different (intake - setting) < -1.0 °C or Thermo-Off activated and only valid for 120 seconds; not applicable during Sleep
Mode, Soft Dry Mode, and Anti-freezing control.
(d) When temperature different (intake - setting) > +1.5 °C or Thermo-Off activated and only valid for 130 seconds.
(b) The frequency judged falls on frequency shifting zone number 0 or 1 (shift to Frequency MIN) at Cooling mode operation.
(d) The frequency judged falls on frequency shifting zone number 7 or 8 (shift to Frequency MAX) at Cooling mode operation.
The instructed frequency is the value referred by the frequency number, which resulted from previous instructed frequency
number with the numbers of frequency numbers to be shifted, in Table on Frequency Number at automatic fan speed.
3
CS-E9BKP CU-E9BKP5 / CS-E12BKP CU-E12BKP5