Status Explanation
15 Manual Heat Demand Manual heat demand for central heating is active.
16 Frost Protection Frost protection mode is active.
19 Reset In Progress The appliance resets.
21 Halted The appliance has stopped. It must be reset manually.
23 Factory test The factory test mode is active.
200 Device Mode The service tool interface controls the functions of the
appliance.
254 Unknown The actual state of the appliance is undefined.
Tab.10 AM014 - Sub status
Rang
e
Status Explanation
0 Standby The appliance waits for a process or an action.
1 AntiCycling The appliance waits to restart, because there were too
many consecutive heat demands (anti-short cycle).
4 WaitingForStartCond. The appliance waits for the temperature to meet the
start conditions.
10 CloseExtGasValve An external gas valve is opened, when this option is
connected to the appliance. An external option board
must be connected to drive the valve.
12 CloseFlueGasValve The flue gas valve opens.
13 FanToPrePurge The fan runs faster to pre-purge.
14 WaitForReleaseSignal The appliance waits for the release input to close.
15 BurnerOnCommandToSu A burner start command is sent to the safety core.
17 PreIgnition Ignition starts before the gas valve opens.
18 Ignition Ignition is active.
19 FlameCheck The flame detection is active after the ignition.
20 Interpurge The fan runs to purge the heat exchanger after a
failed ignition.
30 Normal Int.Setpoint The appliance operates to reach the desired value.
31 Limited Int.Setpoint The appliance operates to reach the reduced internal
desired value.
32 NormalPowerControl The appliance operates on the desired power level.
33 GradLevel1PowerCtrl The modulation is stopped due to a faster heat ex
changer temperature change than gradient level 1.
34 GradLevel2PowerCtrl The modulation is set to low load due to a faster heat
exchanger temperature change than gradient level 2.
35 GradLevel3PowerCtrl The appliance is in blocking mode due to a faster heat
exchanger temperature change than gradient level 1.
36 ProtectFlamePwrCtrl The burner power is increased due to a low ionisation
signal.
37 StabilizationTime The appliance is in stabilisation time. Temperatures
should stabilise and temperature protections are
switched off.
38 ColdStart The appliance runs at start load to prevent cold start
noise.
39 ChResume The appliance resumes central heating after a domes
tic hot water interruption.
40 SuRemoveBurner Burner demand is removed from safety core.
41 FanToPostPurge The fan runs to purge the heat exchanger after the ap
pliance stopped.
44 StopFan The fan has stopped.
45 LimitedPwrOnTflueGas The power of the appliance is decreased to lower the
flue gas temperature.