Paradox Hellas S.A. DEVELOPED Neon 2 User manual

Installation and Operation Manual
Conventional Fire Alarm Control Panel
Version: 1
Revision: 4

IMPORTANT INFORMATION
Limitation of liability
It is mandatory for the NEON panel to be installed in ac-
cordance with this manual, applicable codes, and the in-
structions of the Authority Having Jurisdiction. The manu-
facturer shall not under, any circumstances, be liable for
any incidental or consequential damages arising from loss
of property, or other damages, or losses owing to the fail-
ure of products beyond the cost of repair, or replacement
of any defective products. The manufacturer reserves the
right to make product improvements and change product
specications at any time.
The manufacturer assumes no responsibility for errors or
omissions, whilst every precaution has been taken during
the preparation of this manual to ensure the accuracy of its
contents.
Warranty
PARADOX HELLAS warrants its products to be free from
defect in materials and workmanship under normal use for
a period of two (2) years (the “Warranty Period”) from the
production-delivery date, identied by date code(s) indicat-
ed on the products. Because PARADOX HELLAS does not
install or connect the products and because the products
may be used in conjunction with products not manufac-
tured by PARADOX HELLAS, PARADOX HELLAS cannot
guarantee the performance of the re alarm system and
shall not be responsible in any way whatsoever for faulty
installation or connection.
Declaration of Conformity
Fire alarm control panel NEON is certied from EVPU (Noti-
ed body No. 1293) according to European Regulation CPR
305/2011 with certication number Νο.1293-CPR-0604 of June
27, 2018.
-Standards:
EN 54-2: 1997/A1: 2006/AC: 1999
EN 54-4: 1997/A2: 2006/AC: 1999
Certicates can be found online at phsvesis.com.
RoHS directive compliance
The EC RoHS guideline has been released in order to
reduce the heavy metal load in electrical and electronic
products caused by e.g. lead and mercury. All manu-
facturers are obligated to provide only RoHS-compliant
products to the European market, eective from July
1st, 2006.
PARADOX HELLAS hereby states that the NEON
panel is fully compliant with RoHS 2002/95/EC direc-
tive.
Disposal of your old appliance
1. When this crossed-out wheeled bin symbol is at-
tached to a product it means the product is covered by
the European Directive 2002/96/EC.
2. All electrical and electronic products should be dis-
posed of separately from the municipal waste stream
via designated collection facilities appointed by the gov-
ernment or the local authorities.
3. The correct disposal of your old appliance will help
prevent potential negative consequences for the envi-
ronment and human health.
4. For more detailed information about disposal of your
old appliance, please contact your city oce, waste
disposal service or the shop where you purchased the
product.

3
Neon - Conventional Fire Alarm Control Panel
TABLE OF CONTENTS
1. Components Description 4
1.1 Neon Panel - Components identication - Cabinet
inside view 4
1.2 Neon Panel - Wiring diagram and information 5
2. Typing conventions and abbreviations 6
3. Installation 6
3.1 Installation checklist 6
3.2 Installing the cabinet 6
4. General Description 6
5. Keyboard Indications and Controls 6
5.1 Access Level 1 Operations 7
5.2 Access Level 2 Operations 7
5.3 Indications 8
5.3.1 POWER Indication 8
5.3.2 AUX POWER Fault Indication 8
5.3.3 Battery Fault / Replace Indication 8
5.3.4 SIREN Faults / Disablements Indication 9
5.3.5 EARTH Fault Indication 9
5.3.6 Disablements Indication 9
5.3.7 Test Indication 9
5.3.8 Outputs Delay Indication 9
5.3.9 Alarm Verication Indication 9
5.3.10 Silenced Buzzers Indication 9
5.3.11 Silenced Sirens Indication 9
5.3.12 System Fault indication 9
5.3.13 Access Level 2 Indication 9
5.3.14 General Fire Alarm Indication 9
5.3.15 Zone ALARM indications 9
5.3.16 General Fault indication (General Fault) 10
5.3.17 Zone Disablements, Test, Fault indications 10
6. Alarm Verication 10
6.1 System Overview - Alarm Verication 10
6.2 System Operation - Alarm Verication 10
6.3 Day/Night hardware input 10
6.5 System Setup - Zone assignment - Intellizone 11
6.6 System Setup - Intellizone time delay 11
7. Outputs delay operation 11
7.1 Operation Overview and operation 11
7.2 System behavior 11
7.3 System setup - Dip switches - Delay and Zone al-
location 11
8. Access Level 3 - Panel Conguration 11
8.1 Micro switches SW-A 12
8.1.1 Cross zoning (Coincidence) 12
8.1.2 System setup - Zone inputs 12
8.1.3 Alarm outputs pattern 12
8.2 Micro switches SW-B 12
8.3 Micro switches SW-C 12
8.4 H/W Reset button 13
9. Power Supply 13
9.1 Power Consumption 13
9.2 Recommended batteries 13
10. Wiring Connections of Inputs / Outputs13
10.1 Alarm output 13
10.2 Fault output 13
10.3 Fire detection zones wiring connections 13
Appendix A: Panel Specications 15
Appendix B: Calculations 15

4Neon - Conventional Fire Alarm Control Panel
1. Components Description
1.1 Neon Panel - Components identication - Cabinet inside view
1. Connector for communication board: Connects to
the TCP/IP module (optional).
2. WDT (JP202): Extra Watchdog timer selector (option-
al).
3. PROGR (JP201): Firmware updating connector.
4. Panel’s earth connector bar.
5. Hardware reset button.
6. Micro-switches for access Level 3 settings and op-
tions (See section 8).
7. Battery connector (CN103): Connects to two 12V
7AH batteries in series. See section 7.2.
8. Power connector (CN102): Connection from main
Power Supply to main board.
9. Power connector: Connection to main Power Supply.
10. Main board fuse (F201): Main power supply fuse (5
A, slow blow)
11. Keyswitch selects the operation of the panel in Ac-
cess Level 1 or 2.
12. Mains power connector (CN101): Mains input for
230 V AC and earth connection.
13. Mains power supply fuse (F101): Mains supply is
protected by a 1A slow blow fuse.
14. Remote reset input.
15. Zone inputs.
16. Batteries: Secondary/standby power source. See sec-
tion 9.2.
17. JP204: NO/NC dry contacts operated during reset.
18. ‘AUX R’: Auxiliary power output interrupted during re-
set. 24 V DC / 1 A* max for devices that need resetable
power. This output is fused.
19. ‘AUX’: Auxiliary power output 24 V DC / 1 A* max. This
output is fused.
20. ‘BELL’: Bell / class change operation input. See sec-
tion 5.1, key [4] (A.L.1).
21. ‘D/N’: Day / Night mode external timer input.
22. Fault output relay: Dry contacts NO/NC general fault
relay. 50 V / 1.5A max (DC or AC).
23. Alarm output relay: Dry contact NO or NC re alarm
relay. 50 V / 1.5A max (DC or AC).
24. S1 to S4: Monitored siren outputs. 24 V DC / 0.4A**
per output
25. JP203: Alarm relay contact selector (NO or NC). 50 V
/ 0.5A max (DC or AC).
26. Signaling devices output Fuses (F202 to F205):
1.6 A, fast blow.
27. Connector to repeater board (CN203).
* IMPORTANT: The total current of the auxiliary out-
puts must not exceed 1 Amp.
**The total current of the siren outputs must not ex-
ceed 1 Amp.
The total current of the connected devices must not
exceed 1.5 Amp.
1 2 3 45 6 7 8
9
10
11
12
13
14
15
16
1718
19
20
212223
24
25
26
27

5
Neon - Conventional Fire Alarm Control Panel
4.7K 4.7K 4.7K 4.7K 4.7K 4.7K 4.7K 4.7K
Signaling Devices
Outputs
Fire Relay Output
(Dry Contact)
(NO or NC
by jumper)
Day/Night
Selection
Mode Input
Bell/Class
Change
Input
AUX
Power
Output
AUX
Power
Output
with RESET
Battery Connection
Terminal
Mains Power Supply
230 V AC / 50-60Hz / 2.5A
Fuse 1A / 250V
Slow blow
Hardware Reset Button
Fuse 5A / 250V
Slow blow
Fuse 1.6A / 250V
Fast blow
1.2 Neon Panel - Wiring diagram and information
4.7K
Signaling device 24 V DC
Active End Of Line Capacitor
End Of Line Resistor
Panic button
Photoelectric detector
Rate of Rise Heat detector
4.7K
22uF
AEOL
1. End Of Line Device
2. Active End Of Line Device
22uF
AEOL
Disable evacuation from A.L.1
MANUAL CALL POINT CONNECTION DETAIL

6Neon - Conventional Fire Alarm Control Panel
2. Typing conventions and abbreviations
Throughout this manual specic symbols and character
types have special meaning. The following list summarizes
the typing conventions:
• [Button]: A Keypad button that can be pressed.
• *Indicator*: A visual indicator that may be lit or not.
e.g. *ALARM*.
The following terminology is used:
• PSU: Power supply unit
• A.L.: Access Level
• ALM: Access Level Menu
• ALM.x.y.z: Access Level Menu x, sub-item y, sub-item z.
• EOL: End Of Line (device).
• AEOL: Active End Of Line (device).
For indicators:
• OFF: The indicator is disabled.
• ON: The indicator is steady ON.
• BLINKING: The indicator is alternating between ON
and OFF.
3. Installation
3.1 Installation checklist
*Prepare the site: Make sure the installation location is
free from construction dust, debris, extreme tempera-
ture ranges and humidity.
*Unpack the equipment
*Install the cabinet: See ‘Installing the cabinet’ below
(section 3.2 ) for cabinet dimensions.
*Install optional components
*Review wire routing.
*Connect the eld wiring.
Care should be taken when connecting eld wiring.
Do not make any connections with main or battery
power applied. The cabinet should be connected to a
suitable earth point at all times.
*Check for opens, grounds, and shorts before connect-
ing.
*Connect ground then AC power.
WARNING: Ensure that the building’s AC circuit
breaker is OFF before connecting high voltage wires
(230V AC) to the main connector.
*Connect batteries.
*Test for proper operation.
After a system power up, the user must perform an A.L.2
Reset to remove the System fault and enter normal
operational mode. This is by design.
3.2 Installing the cabinet
Cabinets can be surface or ush mounted. See Figure 1
and Table 1 for framing and mounting dimensions.
To wall mount the cabinet:
1. Position the cabinet on the nished wall surface.
2. Fasten the cabinet to the wall surface where indicated.
Cabinet dimensions
Figure 1. Neon cabinet dimensions
D1 40.5 cm
D2 7,5 cm
D3 29.6 cm
D4 38 cm
D5 22 cm
D6 23.5 cm
D7 [Ø] 0.5 cm
Table 1. Framing and mounting dimensions
4. General Description
The Neon conventional re alarm control panels have been
designed to provide full re detection coverage to buildings
or installations that require re detection systems of 2 to
8 zones.
There are three (3) basic models for the Neon panel:
Model Zones Siren Outputs
Neon 2 2 2
Neon 4 4 4
Neon 8 8 4
Table 2. Neon panel models
Operating Voltage 230V AC / 50-60Hz.
The analytic indications and the simple controls of the
Neon panel ensure the easy handling and controlling of the
system by the operator.
5. Keyboard Indications and Controls
Operating, monitoring and programming of the panel is
performed in three dierent access levels. In access level 1
only indicative operations are unlocked. Access to level 2 is
achieved by the keyswitch on the face of the panel (Figure
2) or the use of the A.L.2 PIN. Operations at access level 2
are performed with the keypad. Access level 3 operations
are accomplished with the micro switches on the main cir-
cuit board of the panel (see section 8).

7
Neon - Conventional Fire Alarm Control Panel
Figure 2. Neon keyboard overview
Naming:
AL1 to AL8 (Zones in Alarm): Alarm indicators *1* to *8*.
FL1 to FL8 (Disablements|Test|Faults): Fault Indicators
*1* to *8*.
S1 to S4: Siren relay indicators *S1* to *S4*.
5.1 Access Level 1 Operations
Access Level 1 operations are those that do not require
authorization (by entering a pin or using the key). On the
mask of the panel the A.L.1 operations are enclosed in {}.
They are mainly informational and aimed toward the install-
er or advanced user that wants to verify the programming
of the panel or to identify faults.
The supported access level 1 operations are performed
while the user keeps the required key pressed for more
than 2 seconds and for as long as the information is need-
ed.
Below is a list of the implemented functionality:
Key [1]: [Siren Faults] (Long Press)
While key [1] is kept pressed the panel uses the 4 LEDs
marked *S1*, *S2*, *S3* and *S4* to indicate the Siren Re-
lay outputs that may have a fault. While in this mode, all
other indicators are turned o and only the *SIREN FAULT
/ DISABLEMENTS* indicator ashes every half a second.
The panel returns to normal indication when the key is re-
leased.
Key [2]: [Silence Buzzers]
When pressed will silence the panel’s buzzer. The *SI-
LENCED BUZZERS* indicator illuminates.
Any new event will automatically cancel the silence.
If the buzzer has no reason to be active, the silence op-
eration will only momentarily activate the corresponding
indicator.
Key [3]: [ZONE Conf.] (Long Press)
Conguration check: Alarm verication, Cross Zoning
While key [3] is kept pressed, the indicators corresponding
to zone faults (FL1 to FL8) show the conguration of the
input zones as below:
• OFF: Corresponding zone has no special program-
ming.
• ON: Corresponding zone belongs to cross zone pair.
• BLINKING (0.5 seconds period): Corresponding
zone belongs to Alarm Verication group.
While the panel is in this mode, all other indicators are
turned o except for the *Alarm Verication* that ashes
every second.
Key [4]: [SIR Conf.] (Long Press)
Conguration check: “Output delay” relays (S1-S4), “De-
layed from” Zones (F1-F8), Pre-alarm Relay
While key [4] is kept pressed the panel shows the congu-
ration related to the 4 Siren (relay) outputs:
• Fault indicators (FL1-FL8): Zones that will be de-
layed if triggered by an alarm are blinking.
• Siren Indicators (S1 to S4): Siren outputs that will be
delayed are blinking.
• Siren Indicator 2 (S2): If allocated to Pre-alarms is
ON (steady).
Key [6]: Test
On Normal press or while kept pressed, all the visual indi-
cators along with the panel’s buzzer are activated.
Key [7]: [EVACUATION] (Long Press)
This operation may be locked for A.L.1. from SW-C-8
On long press (more than 2 seconds) the panel enters
evacuation mode. In this mode all Alarm Outputs are acti-
vated according to their conguration.
• All Fire Indicators (AL1 to AL8) that were not already
active including the General Alarm are activated (blink-
ing).
• Alarm indicators that were already in Alarm, keep a
steady ON indication.
• Any new alarm event detected by a zone, changes the
corresponding zone indication to steady ON.
• The Silence operations will not aect the system.
• All alarm outputs will be activated
• The evacuation requires an Access Level 2 reset to be
canceled.
5.2 Access Level 2 Operations
To enter Access Level 2:
• Key method: Turn key counter-clockwise to horizontal
position.
• PIN method: Press keys to enter AL.2 PIN: “1357”.
The *Access Level 2* indicator illuminates.
If the PIN method is used, the panel will cancel the A.L.2
state if the keys are idle (not pressed) for 30 seconds.
In Access level 2:
Key [1]: Disable SIRENS
The use of this button will cause the disablement of all four
siren outputs (S1 to S4). Successive presses will toggle
the disablement ON and OFF. While disabled:
• There is no way that the system or the user will acti-
vate any of the siren outputs.
• Any already activated output(s) will be deactivated.
• Any faults on S1 to S4 will be ignored and/or sup-
pressed.
• The *Siren Fault / Disablements* and the *Disable-
ments* indicators will be activated (steady ON).
Key [2]: Silence / Restore Sounders
Bell / Class change (Long Press)
Silence / Restore Sounders
The initial press will silence any active sounder output de-
vices. The *SILENCED SIRENS* indicator illuminates.
A second press will remove any previously applied silence.
The *SILENCED SIRENS* indicator extinguishes.
The aected outputs are Siren Relays 1 to 4 regardless of
conguration. The Fire relay is not aected.

8Neon - Conventional Fire Alarm Control Panel
Any new alarm event will automatically cancel the silence.
If no sounders are active, the silence operation will only
momentarily activate the corresponding indicator.
Bell / Class change (Long Press)
While key [2] is kept pressed, the Sounders normally used
for Fire Alarms, are activated with a constant pattern. This
is typically used in schools to sound a class change.
Siren 2 output will not be used if allocated to the pre-
alarm function.
While the panel is in this mode, all indicators are turned o
and only the activated relay indicators (S1 to S4) are blink-
ing every 0.25 seconds.
The panel returns to normal indication when the key is re-
leased.
Key [3]: Alarm Verication Toggle
Only useful if the installation uses the Alarm Verication
functionality.
The Alarm Verication operation may be disabled and re-
enabled with successive presses of key [3] (see section
5.3.9 for indication).
The user may verify which zones (if any) belong to the
alarm verication group by pressing and holding key
[3]. While this key is kept pressed the *ALARM
VERIFICATION* indicator ashes at a slow rate while
blinking disablement indicators show the group
members (see section 5, Alarm Verication).
Key [4]: Output Delays Toggle
Only useful if the installation uses the “Output Delays”
feature.
The Output Delays operation may be disabled or re-en-
abled with successive presses of key [4] (see section 5.3.8
for indication).
Key [5]: ZONES Disablement
Used to selectively place zones in disabled mode. A dis-
abled zone is fully ignored by the system in both faults and
alarms.
How to operate:
1. Press Key [5]: *DISABLEMENTS* indicator starts
blinking: the panel is in zone selection mode.
2. Use keys [1] to [8] to toggle the disablement of the
corresponding zone.
3. The *Disablements | Test | Faults* indicators show
any zones that are disabled (“steady on” state).
Panels with 2 or 4 zones will ignore the keys with no
corresponding zone.
Zone selection mode will be cancelled after 10 seconds
of user inactivity.
Disabling a zone in alarm will cancel the alarm state but will
not reset any automatic detectors that may have caused/
latched the alarm.
Key [6]: ZONES test
Used to place zones in the “Test” state. It is used for testing
the panel as well as any automatic detectors attached to
the zone of interest.
Any alarm condition detected from a zone in test will cause
the panel’s buzzer and the local Sirens (relays 1 to 4) to be
activated for 3 seconds. After the 3 second activation the
panel performs a zone reset (useful for automatic detec-
tors).
Any zone in this state is considered disabled and is so in-
dicated.
If any zone is in test mode, the *TEST* indicator is
illuminated.
Key [7]: EVACUATION (Long Press)
This operation requires Access level 2 if SW-C-8 is set
(see section 8.3 key [7], above).
Key [8]: RESET panel
Exit A.L.2 (Long Press)
The reset operation will:
• Remove power from the zone circuits for 3 seconds,
resetting all automatic detectors.
• Restore all Outputs to their idle state.
• Cancel any pending pre-alarms.
• Cancel all Alarm Verication timers (if active and run-
ning).
• Cancel all faults including the startup System Fault.
“Remote Reset” Hardware input.
The remote reset input, if used, is connected to a
momentarily activating push-button (shorted while kept
pressed). This will cause the panel to do an Access Level
2 reset operation.
5.3 Indications
5.3.1 POWER Indication
The *POWER* indication is permanently ON if the main
power is present and batteries are healthy. This condition
signies normal system operation.
*POWER* indicator OFF signies a total power failure of
the system. This can be due to a number of reasons. Some
of them are:
• Main power failure for an extended period of time during
which the batteries have been depleted.
• Blown main board fuse (see section 1.1).
• Other malfunction of the power supply, main board
disconnected from PSU (power supply unit) etc.
Blinking power indicator signies one of the following:
(a) Removal or power loss of the batteries.
(b) Main power loss.1
(c) Blown main power fuse or PSU fuse (see section 1.1).
In the above cases the on board buzzer sounds continu-
ously.
1The *POWER SUPPLY FAULT* indicator turns ON.
5.3.2 AUX POWER Fault Indication
When active, this indicator signies that an overcurrent
condition at the auxiliary power outputs (section 1.1, items
18 & 19) is detected. The maximum allowed total current
for the two auxiliary outputs is 1 Amp. The panel is capa-
ble of continuous operation even with a full short circuit at
these outputs. Please note that a short on any one of the
two outputs will disable both as well as any device powered
from them.
If more than 1 Amp is required, a compatible EN 54-4 ap-
proved re alarm power supply must be used. When such
a power supply is used, the negative output of the external
power supply must be connected to the negative terminal
of the AUX terminal (-AUX).
IMPORTANT: The total current of the auxiliary out-
puts plus the siren outputs must not exceed 1.5 Amp.
5.3.3 Battery Fault / Replace Indication
The Neon panel uses a battery fault detection system that
will generate a battery fault indication in the following cases:

9
Neon - Conventional Fire Alarm Control Panel
• Battery missing: Indicator steady ON.
• Battery wiring open circuit: Indicator steady ON.
• Battery not able to charge (low voltage): Indicator steady
ON.
• Battery wear (increased internal resistance of batteries):
Indicator BLINKING.
This indication means that a battery replacement is in
order.
When the battery power is the only available source the
supplied voltage is constantly checked. In the case that this
voltage drops bellow the 21.7 V DC ±5% the panel enters
a fault state with all zone fault indications activated. At the
same time the power to the zone circuits is removed. This
state is automatically reset once the mains power is re-
stored.
This mechanism ensures that the low voltage from deplet-
ed batteries will prevent the zone detection circuits from
giving false alarms.
5.3.4 SIREN Faults / Disablements Indication
Siren Faults (blinking)
When active (blinking), this indicator signies a fault condi-
tion on one of the signaling devices outputs. The fault can
be one of the following:
• Short circuit of the two output wires.
• Open circuit in the connecting cable between the block
connector and the signalling device. The signalling
device must be terminated with a 4.7K Ohm resistor
(EOL).
• Blown fuses that protect the system from shorts while
the signalling devices are in operation (Fuses F202 to
F205 1.6A, item 26, page 4).
To identify the particular output (there are 4 siren outputs)
keep key [1] pressed for more than 2 seconds. Indicators
S1 to S4 will illuminate if the corresponding output is in
Fault (see section 5.1).
Siren Disablements
When active (steady ON), this indicator signies that the
four siren outputs S1 to S4 have been disabled with an
A.L.2 operation.
5.3.5 EARTH Fault Indication
When active (steady ON), this indicator signies a short
circuit between the panel’s wiring (zones, relays, outputs
etc.) and the building’s earth.
The signaling device output wires are also monitored for
the earth short condition.
5.3.6 Disablements Indication
The *Disablements* indicator is activated when:
• In access level 1 when any zone is disabled or in
test mode (steady ON) or when the sirens are disabled
(steady ON)
• In access level 2, in zone selection mode for disable-
ment (blinking).
5.3.7 Test Indication
The *TEST* indicator is activated when:
• In access level 1, at least one zone is in testing mode
(“steady on”).
• In access level 2, the system is in test selection zone
mode (blinking).
5.3.8 Outputs Delay Indication
The meaning of this indication is as below:
• OFF: No delays to outputs are active or programmed.
• ON: The system has programmed and active delays
to outputs.
• BLINKING: The system has programmed delays to
outputs but they are currently disabled with an Access
Level 2 operation.
See also Long Press of key [4].
5.3.9 Alarm Verication Indication
The meaning of this indication is as below:
• OFF: No alarm verication is active or programmed.
• ON (steady): The system has programmed and active
alarm verication.
• BLINKING: The system has programmed alarm veri-
cation but it is currently disabled with an Access Level
2 operation.
See also Long Press of key [3] section 5.2.
5.3.10 Silenced Buzzers Indication
This indicator is active when the user has silenced the pan-
el’s buzzer (with an Access Level 2 operation).
See A.L.2 key [2].
5.3.11 Silenced Sirens Indication
This indicator is active (steady ON) when the user has si-
lenced the relay siren outputs (with an Access Level 2 op-
eration).
See A.L.2 key [1].
5.3.12 System Fault indication
The system fault is active (steady ON) in one of the follow-
ing cases:
• After a system startup from power down
• After a watchdog reset
• If the microprocessor is not able to operate and ex-
ecute code.
After a system power up, the user must perform an A.L.2
Reset to remove the System fault and enter normal
operational mode. This is by design.
5.3.13 Access Level 2 Indication
The indicator is active (steady ON) when the user has
entered Access Level 2. The Access level may be elevat-
ed either by the use of the standard key or the A.L.2 Pin
(“1357”).
5.3.14 General Fire Alarm Indication
When the system detects a condition of re (smoke, high
temperature etc), the panel goes into Alarm Mode and the
General Fire Alarm indication *FIRE* turns ON (blinking).
At the same time the re relay is activated and all siren
outputs are used according to the programming (delayed
or immediate). The on-board sounder is also activated pro-
ducing a continuous audible alarm sound.
5.3.15 Zone ALARM indications
*Zones in ALARM* indicators AL1 to AL8 activate every
time a detector or a manual call point from the correspond-
ing zone is triggered.
All indications will remain ON (steady ON) until the system
[RESET] button is pressed.
Activated AL1 to AL8 indicators without the General
Alarm Indicator signies a pre-alarm condition from the
corresponding zones.

10 Neon - Conventional Fire Alarm Control Panel
5.3.16 General Fault indication (General Fault)
GENERAL FAULT, indicates a problem in the system. It
turns ON (steady ON) in case of:
• Zone wiring connection problems,
• Signalling devices output wiring problems
• Relay outputs wiring problems.
• Auxiliary and power faults
• Earth fault condition
The above mentioned problems could be open circuits,
shorts between wires or shorts between wires and earth.
Consequently the Fault relay output is activated (Item 22,
page 4). At the same time there will be a continuous audible
notication from the on board Buzzer.
It is possible to silence the Buzzer by pressing the SILENCE
BUZZERS key [2], with the keyswitch in A.L.1 position.
When the problems causing the fault(s) are restored all the
above indications will turn o automatically.
Short Normal Open
Min Max Min Max Min Max
Signaling
devices
0 400 1.6K 7K 10K ∞
Zone 0 15 1.5K 7K 10K ∞
Table 4. Fault detection values (Ohm)
Zones also recognize the range of 40 to 1200 Ohms as
alarm.
5.3.17 Zone Disablements, Test, Fault indications
These indicators, referenced as FL1 to FL8, show that the
corresponding zone is:
• In “zone open” Fault if blinking at 1 sec interval
• In “Zone Shorted“ fault if blinking at 0.5 sec interval.
• Disabled by an A.L.2 operation, if continuously ON with
the *DISABLEMENTS* indicator also active (steady
ON).
• In test (and thus disabled), if continuously ON with
*TEST* indicator also active (steady ON).
Zone faults
Possible causes of a zone fault indication are:
(a1) Disconnection or interruption of wiring of the zone.
(a2) Short-circuit in the wiring of the zone.
(a3) Removal of sensor from its base.
(a4) Removal of the terminating resistor or capacitor
(EOL).
See also section 10.3.
Watchdog System
The Neon panel contains a watchdog circuit that will ac-
tivate when the microprocessor is either faulty or unable
to execute the programmed rmware. Upon detection, the
Fault relay, the on board sounder and the system and gen-
eral fault indicators on the user interface are all activated.
6. Alarm Verication
(also called Intellizone in this manual)
6.1 System Overview - Alarm Verication
The purpose of the Alarm Verication feature is to minimize
false alarms. The concept of alarm verication is to have
the system receive a Second Alarm signal from the same
or another zone within a predened time after the First
Alarm signal. Only then will the General Alarm condition be
activated. To prevent the First Alarm signal from causing a
General Alarm, it must originate from an intellizone.
Please note that the terms Alarm Verication and intelli-
zone are treated as synonymous in the following sections.
6.2 System Operation - Alarm Verication
Each zone may be programmed to be an “Intellizone” (from
microswitch SW-B). The sum of the intellizones form the
intellizone group.
The operation of the intellizone system is as follows:
When an alarm condition is detected on an intellizone (First
Alarm):
• The “Intellizone Delay” is activated (can be set from
SW-A 6,7,8).
• The “Automatic Alarm Cancel Delay” (5 minutes) timer
is activated.
• The pre-alarm is indicated on the corresponding Alarm
Indicator (AL1-AL8). The General Alarm Indicator is
not activated.
• The system buzzer produces a notication sound.
• The Main Siren relays are NOT activated (General
Alarm condition is not established).
• The Siren 2 relay, if congured so by SW-A-5, is acti-
vated.
• After the “Intellizone Delay” time, the automatic detec-
tors are reset.
• During the “Intellizone Delay” any other zone (NOT
only intellizones) except the initial may provide the
Second Alarm signal (see below).
• The intellizone pre-alarm will remain active for the
remainder of the 5 minutes before the initial alarm is
completely canceled.
During the above delay (Automatic Alarm Cancel Delay)
any zone (not only intellizones), including the initially trig-
gered intellizone may provide the Second Alarm.
The Second Alarm will:
• Activate the General Alarm Condition.
• Activate the alarm siren relays.
• De-activate the Siren 2 relay, if congured for pre-
alarms by SW-A-5.
The Intellizone feature may be disabled/re-enabled from
Access Level 2, Key [3] “Alarm verication toggle”. The
system status is indicated accordingly with the “Alarm Veri-
cation” as below:
• OFF: No Alarm verication programmed.
• ON: Alarm verication active for selected zones.
• BLINKING: Alarm verication is programmed but not
active at the moment, either due to Day/Night or man-
ual disablement.
6.3 Day/Night hardware input
The disablement of the Alarm Verication system, can also
be controlled by the “Day/Night input” hardware input. If
left unused (nothing connected to the input) the system will
use Alarm Verication, unless the user has disabled it.
If connected to a switch (for example to a periodic timer),
when the contacts are closed (shorted together) the Alarm
Verication is disabled. The panel will indicate the disabled
condition by blinking the *ALARM VERIFICATION* indica-
tor.

11
Neon - Conventional Fire Alarm Control Panel
This input may also be used with a manual external switch,
to provide an easier operation of the “Alarm Verication
Disable/enable” functionality.
6.4 System Setup - Zone connections - Intellizone
The system should have one or more zones connected to
automatic detectors. Manual call formats may also be con-
nected to intellizones but the alarm signal will be delayed
by the Intellizone Delay time.
6.5 System Setup - Zone assignment - Intellizone
To assign zones to the intellizone group set the required
corresponding microswitches on SW-B to ON (top posi-
tion).
Zones assigned to cross-zoning cannot be assigned to
the intellizone group. If both micro-switches are set, the
cross zone conguration takes precedence.
6.6 System Setup - Intellizone time delay
The Intellizone Delay can be set from the three micro-
switches SW-A-6,7,8. The three switches form a binary
value from 0 to 7. Each unit corresponds to 10 seconds.
The table below summarizes the settings:
SW-A-6 SW-A-7 SW-A-8 Alarm Verication
OFF OFF OFF No Alarm Verication
ON OFF OFF 10 sec
OFF ON OFF 20 sec
ON ON OFF 30 sec
OFF OFF ON 40 sec
ON OFF ON 50 sec
OFF ON ON 60 sec
ON ON ON 70 sec
Table 5. Alarm Verication time set
IMPORTANT: To congure an EN54-2 compliant installation,
do not exceed 30 seconds of Intellizone delay time.
7. Outputs delay operation
The Neon panel implements the “Output delays” fea-
ture as dened in the EN54-2 standards.
“Output delays” refers to the process of delaying the acti-
vation of an alarming output, after the system enters the
general re alarm state.
Indications
The *OUTPUTS DELAY* indicator shows the status of the
system as below:
• OFF: No output delays have been programmed.
• ON: Output delays are in eect for selected outputs
(once an alarm occurs).
• BLINKING: Output delays have been programmed but
are currently disabled due to user operation.
7.1 Operation Overview and operation
The system consists of the following:
• A group of zones that, when trigger an Alarm event,
will activate some Siren outputs with delay (called “De-
layed Zones”).
• A group of zones that, when trigger an Alarm event,
will activate all Siren outputs without delay (called “Im-
mediate Zones”)
• A group of outputs (relays) that will always activate
without delay (called “Immediate Outputs”)
• A group of outputs (relays) that will activate with de-
lay if the Alarm is triggered by a “Delayed zone”(called
“Delayed Outputs).
Additionally, there is a predened delay in access level 3
(dip switches SW-C-1,2,3) called “Output Delay”.
7.2 System behavior
The term “Delayed Zone” is only meaningful in the con-
text of Delayed outputs. Even “Delayed Zones”, will ac-
tivate the General Fire Alarm without delay.
The following list describes the behavior of the output de-
lay system:
• As soon as an alarm event is triggered by an “Immedi-
ate Zone” all Siren output relays are activated imme-
diately.
• As soon as an alarm event is triggered by a “Delayed
Zone”:
○The timer of the output delays is started with “Out-
put Delay” time.
○Siren output relays not in the “Delayed Outputs”
group are activated immediately.
○Siren output relays in the “Delayed Outputs” group
are activated after the “Output Delay” time has
passed.
7.3 System setup - Dip switches - Delay and Zone al-
location
The dip switches SW-C-(1 to 5) dene the operation and
options of the output delays as follows:
SW-C-1,2,3: This is the binary value of the output delay.
An output delay of 0 means that no outputs are delayed. In
this case the rest of the switches are ignored. Delay time
other than 0 activates the output delays. Values are shown
below:
SW-C-1 SW-C-2 SW-C-3 Output Delays
OFF OFF OFF No Output Delay
ON OFF OFF 1 min
OFF ON OFF 2 min
ON ON OFF 3 min
OFF OFF ON 4 min
ON OFF ON 5 min
OFF ON ON 6 min
ON ON ON 7 min
Table 6. Outputs delay time set
SW-C-4: Delayed Zone selection
This option denes if all or half of the available zones are
used as “Delayed Zones”.
0: All available zones are “Delayed Zones”
1: The rst half zones are “Immediate Zones”
SW-C-5: Delayed Outputs selection
The setting of this switch denes the Output relays that
form the “Delayed Outputs” group.
0: Only outputs 3 and 4 (Siren3 and Siren4) are “Delayed
Outputs”.
1: All 4 Siren relays are “Delayed Outputs”.
If Relay Output 2 is allocated to the pre-alarm feature, it
is not aected by the above operation.
8. Access Level 3 - Panel Conguration
Settings in Access Level 3 can be performed via the mi-
cro switches on the main board. This procedure must be
performed only by the installation engineer. On the main

12 Neon - Conventional Fire Alarm Control Panel
board of the panel there are three (3) sets of micro switch-
es modules SW-A to SW-C. Every module consists of 8
micro switches No.1 to No.8 as shown on Figure 3. Their
position during hardware reset dene the eective congu-
ration. Hardware reset is performed either during power
up or after pressing the button labeled SW-RESET on the
PCB (see section 1).
Figure 3. Micro switches
The ON position of the micro switches equals to EN-
ABLED status.
The OFF position of the micro switches equals to DIS-
ABLED status
All switches that are not used must be set to the OFF
position.
The various settings of the micro switches along with their
operation are listed in the following sections.
8.1 Micro switches SW-A
Micro switches SW-A
1Cross zones 1 and 2
2Cross zones 3 and 4
3Cross zones 5 and 6
4Cross zones 7 and 8
5Relay 2 active only during pre-alarm
(Cross or Alarm Verication)
6Binary value of Alarm Verication delay.
0: disabled.
Increments of 10 seconds.
7
8
Table 6. Micro switches SW-A
8.1.1 Cross zoning (Coincidence)
The Neon re panel may be congured to require two si-
multaneous and dierent zone alarms to trigger the gen-
eral re alarm. This minimizes the chances of false alarms.
The operation of the system is based on the denition of
zone pairs. A zone pair is activated by the corresponding
microswitch as shown in table above (SW-A-1,2,3,4).
A zone pair is considered by the system as one zone. Both
zones have to be in alarm for the general re alarm to be
active.
If only one zone has been triggered, the pre-alarm state is
activated. In this state:
• the panel’s buzzer is activated.
• the relay output 2 (S2) is activated if dedicated to pre-
alarms (SW-A-5)
• The user can cancel the pre-alarms condition and reset
the triggered zone with the Reset operation (in A.L.2).
• If the second zone of the pair gets activated as well,
then the system enters the Fire Alarm state. Both
zones of the pair are indicated in alarm.
8.1.2 System setup - Zone inputs
To enable the cross zoning function place the appropriate
micro-switches to the ON position according to Table 6. Ex-
ample: switching SWA-1 to ON, will activate cross-zoning
on zones 1 and 2. The two zones (1st and 2nd) should be
connected to the detectors that are installed in the pro-
tected area. A common practice is to install dierent types
of detectors. Example: the rst zone has a photoelectric
smoke detector and the second zone has a temperature
detector (Rate of Rise Heat detectors).
8.1.3 Alarm outputs pattern
The Neon main board provides four supervised* outputs
for the connection of Notication appliances (signalling de-
vices) namely S1 to S4.
The alarm outputs S3 and S4 may be set to one of two dif-
ferent patterns:
The rst option is to provide constant power.
The second option is to provide a periodic and interrupted
pattern that conforms to the ANSI standards for evacuation
(Figure 4).
The ANSI evacuation sound has three (3) half second ON
periods that repeat after a silence of 1.5 seconds.
500msec
4sec
Pattern a
Pattern b
Notification
appliance
sound
1.5sec
Continuous Sound
Interrupted Sound
Time
Figure 4. Alarm outputs pattern
If the ANSI pattern is selected the activation of Sirens 3 and
4 is synchronized. This makes possible the use of notica-
tion appliances without the need for extra synchronization
modules, thus lowering the cost of the system.
The option is controlled by switches SW-C-6 and SW-C-7
for relays S3 and S4 respectively.
*A supervised output is one that is monitored by the system
for fault conditions.
8.2 Micro switches SW-B
Micro switches SW-B
1
The corresponding zone belongs to the Alarm
Verication group
2
3
4
5
6
7
8
Table 7. Micro switches SW-B
8.3 Micro switches SW-C
Microswitches SW-C
1Binary value of Output Delay.
0: feature disabled.
Increments of 1 minute.
2
3
4Output delay is not applicable if alarm event comes
from rst half zones
5Output delay also aects relays 1 and 2 (Siren 1 & 2)
6Siren relay 3 produces ANSI evacuation pattern
7Siren relay 4 produces ANSI evacuation pattern
8Disable evacuation from A.L.1

13
Neon - Conventional Fire Alarm Control Panel
Table 8. Micro switches SW-C
8.4 H/W Reset button
The PCB RESET button (Item 5, page 4) should only be
used by the installer. It is used to restart the microcontroller
or to make eective any changes made via the micro dip
switches.
In order to activate changes of settings via the micro
dip switches a PCB RESET is required (by pressing
the PCB RESET button on the main board, item 5 page
4). To distinguish this reset operation from the System
(Zones) reset, the term “PCB reset” is used through
out this manual.
9. Power Supply
Neon panel uses a switching power supply for a stabilized
output of 27.6V DC, 2.5A. The connection to the mains
power is through the Mains Power Connector (item 12,
page 4).
The Switching Power Supply connects to the main board
through a 4-wire power connector.
To avoid equipment damage, the connection of the
main power and the batteries must be done only AF-
TER the connection of all the required wiring includ-
ing peripherals and detection devices.
9.1 Power Consumption
On Table 9 the current consumption of the Neon panel is
listed.
Model ZONES
POWER
SUPPLY
CURRENT
IN
STANDBY
MODE
CURRENT
IN
ALARM
MODE
MAX No
OF DETECTORS
PER ZONE
Neon 2 2 27.6V DC 55 mA 165 mA 20
Neon 4 4 27.6V DC 55 mA 180 mA 20
Neon 8 8 27.6V DC 55 mA 210 mA 20
Table 9. Panels’ current consumption
The above numbers do not include consumption from
the detectors. They do include consumption of the EOL
resistors.
9.2 Recommended batteries
The batteries recommended for the Neon panel are 12V,
7AH Sealed lead acid batteries (two units per panel). The
standby time of the panel obtained with these batteries
depends on the panel type, the quantity/type of the con-
nected peripheral appliances and the quantity/type of the
connected detectors. See Appendix B for battery autonomy
calculation.
10. Wiring Connections of Inputs / Outputs
10.1 Alarm output
In case of an alarm, the ALARM output relays (Notication
appliance outputs S1 to S4) provide 24V DC to the notica-
tion appliances that are connected to the panel. Maximum
current for each output is 0.4 Amp (fused at 1.6A). Total
current for alarm outputs must not exceed 1 Amp.
IMPORTANT: The total current of the auxiliary out-
puts plus the siren outputs must not exceed 1.5 Amp.
The Alarm output also monitors the notication appliances
wiring for open lines and short circuits. The connection of a
4.7K Ohm EOL resistor is required as shown in below (see
section 1.2).
4.7K 4.7K 4.7K 4.7K 4.7K 4.7K 4.7K 4.7K
Signaling device 24V DC
Panic button
Photoelectric detector
Rate of Rise Heat detector
Figure 5. Zone inputs and Siren outputs wiring connections.
Pay special attention when connecting loads less than
2.2K Ohm! They may interfere with the fault detection
circuit causing a fault condition. In this case use a di-
ode between the output “+” and the load. Connect the
anode of the diode to the output “+” terminal. The di-
ode must be able to withstand the maximum current
during the operation of the load. See Figure 6 for an
example connection.
4.7K
IN4003
Figure 6. Typical load connection
10.2 Fault output
Neon provides an output to activate external de-
vices in the case of faults. The output is acti-
vated on zone faults, output relay faults, power
faults (auxiliary, main or battery) and earth fault.
Dry relay contacts are provided on the “FAULT” terminal
that may activate any device or indicator. Maximum han-
dling current is 3 A.
10.3 Fire detection zones wiring connections
The re detection zones have 18V DC in standby mode
with the positive power supply terminal common and are
terminated via a 4.7K Ohm EOL resistor or a 22uF capaci-
tor.
The circuit recognizes ve dierent resistances which cor-
respond to four dierent states of the system.
The four dierent resistance ranges are:
Resistance Ranges
0 up to 15 Ohm Short-circuited Zone
40 up to 1.2K Ohm Zone in alarm state
1.5K up to 7K Ohm Zone in standby state
10K up to ∞ Open-circuited Zone
Table 10. System’s resistance ranges
Each zone that is not used must be terminated with
EOL resistor of 4.7K Ohm.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If de-
tectors are not so located, a developing re may dam-
age the alarm system, impeding the ability to report a
re.
Wiring connections of detectors and other devices to the
main board with 4.7K Ohm EOL resistors are analytically
shown in section 1.2.
In case the installation requires Active End Of Line termi-

14 Neon - Conventional Fire Alarm Control Panel
nation, the EOL devices must be 22uF electrolytic capaci-
tors (25V DC).
The Active EOL (AEOL) method of detection,recognizes
the removal of a single detector while the rest of the detec-
tors down the zone remain in operation (alarms are recog-
nized).
ZONES DESCRIPTION
Zone 1:_______________________________________
Zone 2:_______________________________________
Zone 3:_______________________________________
Zone 4:_______________________________________
Zone 5:_______________________________________
Zone 6:_______________________________________
Zone 7:_______________________________________
Zone 8:_______________________________________
Installed by
Name:
Company:
Address:
Phone:
For service contact
Company:
Address:
Phone:
Acceptance Inspection by
Date:
DEVELOPED BY
PARADOX HELLAS S.A.
Korinthou 3, Metamorfosi
144 51 - Athens, Greece
Compliance Statement
Neon panel is designed and manufactured so that it fulls
the requirements of CPR 305/2011 european regulation and
are certied to directive CPR 305/2011 and EN 54 Part 2
and 4,1998 Standards.

15
Neon - Conventional Fire Alarm Control Panel
Appendix A: Panel Specications
Neon 2 Neon 4 Neon 8
Number of zones 2 4 8
Maximum number of detectors per zone 20
Notication appliances outputs (e.g. sirens) 2 4 4
Notication appliances current 4 x 400mA (total maximum current 1Amp)
Mains Power 230V AC 50/60Hz
Zones input voltage (with EOL & AEOL) 16 to 21 V
Maximum input power 100 VA max input power (0.5 Amp)
Battery placement 2 x 12V 7Ah VRLA batteries will t in the panel
Standby Power 5 VA (25 mA)
Auxiliary power outputs 24V DC 1Amp total (‘AUX’ + ‘AUX R’)
Zone termination 4,7 KOhm 5% 1/2W resistors or 22uF / 25V electrolytic capacitors
Monitored output termination 4,7 KOhm resistors 5% 1/2W
Fire relay output Dry contacts NO or NC selectable. 50 V / 1.5 A max (DC or AC)
Fault relay output Dry contacts NO or NC selectable. 50 V / 1.5 A max (DC or AC)
Environmental Temperature: -2 to 45 °C (32 to 120 °F)
Humidity: 5 to 95% RH, non condensing
Panel’s dimensions (HxWxD) [mm] 315 x 425 x 105 mm. In semi ash wall mounting extruding depth: 25mm
Weight (without the batteries) 2.800gr
Appendix B: Calculations
Battery calculation worksheet
Use this worksheet to determine the minimum capacity required for the panel’s standby battery. You can obtain operating current re-
quirements for notication appliances from their respective installation sheets.
Standby
Current (mA)
Alarm
Current (mA)
Base panel [1]
Aux current
Detector’s consumption [3]
Total current
Required standby and alarm
time
x
Standby
time 24hr x
Alarm time 5 min = 0.083 hr
10 min = 0.167 hr
15 min = 0.250 hr
30 min = 0.500 hr
mAh + mAh = mAh
÷1000
Battery amp hour total = Ah
x 1.2
Minimum battery size[2] = Ah
[1] Base panel includes the main controller board with no load, only EOL resistors. Consumption on Standby mode: See Appendix A.
[2] The maximum battery size the panel can charge is 2x7 Ah 12 V.
[3] Use maximum value or actual calculated value from the Form below.
Zones detector’s consumption calculation
Zones Quantity of Detectors Detectors consumption Total standby consumption[4]
(quantity x consumption in mA)
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Total consumption for all zones =
[4] Maximum standby consumption per zone may not exceed 15 mA.

Document Part Number: NEON-PI01, CPR
version 1, revision 4 - 12/2018
This manual suits for next models
2
Table of contents
Other Paradox Hellas S.A. Control Panel manuals