
Example:
On: View settings without the ability to alter settings.
Off: User has ability to alter settings.
OFF
ON SETTINGS REVIEW
Example:
English, Francais, Duetsch, Italiano,
Espanol, Nederlandse, Portugues
ENGLISH
FRANCAIS
PORTUGUES
LANGUAGE
Example:
12 characters maximum.
ASSISTANCE NAME 1
Example:
12 characters maximum.
ASSISTANCE NAME 2
Example:
14 characters maximum.
ASSISTANCE PHONE
Example:
4, 5, 6, 7, 8, 9, 14
SYSTEM 5
SYSTEM 6
SYSTEM 4SYSTEM
Example:
2510, 2750, 2815, 2900, 3150, 3900
2850
2900
2815 VALVE
Example:
Upflow
Downflow
Filter
DOWNFLOW
FILTER
UPFLOW
REGEN. FLOW
Example:
Softener Meter Delayed
Softener Meter Immediate
Time Clock
Day of the Week.
SOFTENER METER IMM
TIME CLOCK
SOFTENER METER DEL
REGEN. TYPE
Example:
Metric
US
US
METRIC UNITS
Example:
Range: 0-9,999,999 grains
0023828
CAPACITY - GRAINS
Example:
Range: 0-199 GPG
Example:
Fixed Volume
Weekly Reserve
Variable Reserve
Fixed %
WEEKLY RESERVE
VARIABLE RESERVE
FIXED VOLUME
RESERVE
Example:
Off, Immediate, Delayed
OFF
IMMEDIATE
DELAYED
REMOTE REGENERATION
Example:
Range:
1-9999 seconds
1 S
REMOTE SIGNAL DURATION
Example:
Range: Off - 99 Days
10 D
DAY OVERRIDE/TIME-DRIVEN
Example:
Range: 0 - 23 Hours 59 Minutes.
Example:
Start Lock Window
End Lock Window
02:OOHR
REGEN. TIME
OFF
ON LOCK WINDOW #1
Example:
Range: 0 - 240 M
10 M
BACKWASH
Example:
Range: 0 - 240 M
60 M
DRAW
Example:
Range: 0 - 240 M
10 M
RAPID RINSE
Example:
Range: 0 - 240 M
12 M
TANK REFILL
Example:
Range: 0 - 240 M
Example:
Range: 0.1 to 999.9 gpm/Lpm
0 M
PAUSE
Example:
Paddle (0.75”, 1”, 1.5”, 2”, 3”)
Turbine (0.75”, 1.25”, 1.5”)
Generic
1.00” PADDLE
1.00” TURBINE
0.75” TURBINE
METER TYPE
OFF
ON
CONTINUOUS FLOW DETECT
Example:
Off, Alarm Based, Cycle Based, Time Based,
Volume Based, Standby
OFF
ALARM BASED
STANDBY
AUXILIARY 1
Example:
Off, Alarm Based, Cycle Based, Time Based,
Volume Based, Standby
OFF
ALARM BASED
STANDBY
AUXILIARY 2
OFF
ON
SAVE AS NON-FACTORY
Example:
Off, Delayed, Enter Code, Time Based
OFF
DELAYED
TIME BASED
LOCK SETTINGS
025
HARDNESS - GPG
Example:
2, 3, 4, 5, 6, 7, 8
2
8
3NUMBER OF TANKS
Example:
Trip Points only available/visible when
System Type 14 is selected.
0001
TRIP POINT #1 - GPM
1 S
TRIP POINT #1 - SERVICE DURATION
60 S
TRIP POINT #1 - STANDBY DURATION
Example:
Range: 1-90 seconds
Example:
Range: 60-300 seconds
MASTER PROGRAMMING MODE
FLOW CHART
Before entering Master Programming, please
contact your local professional water dealer.
NOTE: Depending on current option settings, some values
cannot be viewed or set.
Master Programming Mode
1. Press and hold the Left and Down buttons simultaneously
for 3 seconds to enter Master Programming mode.
2. To navigate, press the Extra Cycle button to advance to the
next value. Press the Left button to retreat to the previous
value.
3. Where applicable, use the Down and Up buttons to adjust
a value as desired. When entering data into text fields
(such as Assistance Name) or numerical fields (such as
Hardness), press the Extra Cycle button to advance to the
next character/digit and press the Left button to retreat to
the previous character/digit. Proceed through all available
characters/digits to advance to the next value.
4. To reset/clear a value (such as Assistance Name), while
on the value, press and hold the Down and Up buttons
simultaneously for 5 seconds.
5. To exit Master Programming Mode, progress through all
available values or after 5 minutes of inactivity the timer
will exit automatically. To exit master programming without
saving changes, press the Left button until you return to
the service screen.
6. Depending on the current controller programming, certain
values may not be able to be viewed or set.
7. The timer will display local information, not system
information.
8. In the event of a regeneration occurring while displaying
master programming, the regeneration step and time
remaining will be displayed. When regeneration has been
completed, the display will return to the main screen.
System 4 - Single Unit
Single Tank configurationTime Clock: No MeterImmediate: One
MeterDelayed: One MeterRemote Signal Start
System 5 (2-8 Units) Parallel Interlock)
All tanks in parallel supplying treated water. Each unit in the
system will have its own flow meter/sensor input. The control
will delay the start of Regeneration if another unit is already
in Regeneration. Once that unit has completed a Regeneration
cycle, and has returned to Service, the unit with the longest
regeneration queue time will begin Regeneration. No more
than one unit will be in Regeneration at at time.
System 6 (2-8 Units) Parallel Series Regeneration
All tanks in parallel supplying treated water. Only #1 control
will monitor flow meter/sensor input. When a regeneration is
required for the system, it will regenerate valve address #1
first, immediately followed by #2, then #3, then #4 if installed.
No more than one unit will be in Regeneration at a time.
System 7 (2 Units) Alternating Immediate
One tank online supplying treated water, one tank in Standby.
Only #1 control will monitor its flow meter/sensor input.
Regeneration of a unit will begin after the other control has left
Standby and returned to Service. When the Regeneration cycle
is complete, the regenerated unit will enter Standby. Standby
on each tank is controlled by the relay on the NXT2 circuit
board.
System 8 (2 Units) Alternating Delayed
Immediate Transfer Delayed RegenerationOne tank online
supplying treated water, one tank in Standby. Only #1 control
will monitor its flow meter/sensor input. Online unit depletes
its volume. Once this occurs the offline unit comes online. The
previously online unit goes offline and delays its regeneration
until the programmed regeneration time has been reached.
System 9 (2-8 Units) Alternating with Standby
Units
Up to 7 tanks online supplying treated water, one tank
in Standby. Meter/sensor input is required on each tank.
Regeneration of a unit will begin after the other control has left
Standby and returned to Service. When the Regeneration cycle
is complete, the regenerated unit will enter Standby. Standby
on each tank is controlled by the relay on the NXT2 circuit
board.
System 14 (2-8 Units) Demand Recall
Meter input is required on each tank. Unit #1 will begin In
Service with #2, #3, and #4 (if installed) will begin in Standby.
At least one unit is In Service at all times. When flow rate to the
Primary Service Unit increases to a user specified rate, the
next unit in sequence will move from Standby to Service. As
the flow rate falls below the user specified rate, subsequent
tanks will return to Standby. When the Primary Service Unit
regenerates, the next unit in sequence will become the new
Primary Service Unit. As each units capacity is reached, the
controller will initiate a Regeneration of that unit. Depending
on the number of units in the system and flow rate demand,
the regenerated unit will then be placed either into Standby or
Service. Only one unit will be in Regeneration at a time.
8 • Pentair Fleck NXT2 Timer Pentair Fleck NXT2 Timer • 9