CALIFORNIA PROPOSITION 65 WARNING:
Warning: This product and related accessories
contain chemicals known to the State of California to
cause cancer, birth defects or other reproductive harm.
INSTRUCTION AND REPAIR MANUAL
SERIES 382A-SC 6
SECTION 6ITEM 382A-SC
DATED DECEMBER 2005
APPLICATIONS:
The 382A-SC Series is a superior commercial in-line pump based on the
Aurora Pump 340/380 series which has been manufactured and field
tested under the severest demands of high temperature condensate
service and boiler feed applications for over 50 years. Pumping
applications for the 382A-SC include: hot or chilled water circulation,
pressure booster systems, and cooling towers for office buildings,
hotels, hopitals, universities and warehouses.
OPERATIONAL LIMITS
Maximum Operating Pressure: 175 psi
Maximum Operating Temperature: 225°F (107°C)
ATTENTION: SAFETY WARNINGS:
Read and understand all warnings before installation or servicing pump.
ELECTRICAL SAFETY:
HIGH TEMPERATURE SAFETY:
HIGH PRESSURE SAFETY:
INSTALLATOIN:
The 382A-SC pump must be installed vertically. Install isolating valves
on each side of pump so pump maintenance can be performed with out
draining the system. Special mounting requirements may be required if
the pump is to be mounted near a noise or vibration sensitive area.
A minimum length of straight pipe is required on the suction side of the
pump. Five times the pipe diameter is sufficient to allow a smooth entry
of water into the pump.
Suction and discharge piping must be in line. Do not use pump casing to
force the alignment of the piping. Properly support the piping to provide
a rigid support for the pump. Tighten pump flanges evenly to prevent
flange cocking and liquid leakage. Do not reuse old gaskets.
ELECTRICAL CONNECTIONS:
Warning: Sudden Start-Up Hazard
Disconnect and lockout power source before servicing. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Overload Hazard
Insure all motors have properly sized overload protection. Failure
to follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Shock Hazard
All electrical connections are to be made by a qualified
electrician in accordance with all codes and ordinances.
Failure to follow these instructions could result in serious
personal injury, death or property damage.
Warning: Expansion Hazard
Water expands when heated. Install properly sized thermal
expansion tanks and relief valves. Failure to follow these
instructions could result in serious personal injury, death or
property damage.
Warning: High Pressure Hazard
The pump is rated at a maximum of 175 psi (155 psi). Do not
exceed this pressure. Install properly sized pressure relief valves in
system. Failure to follow these instructions could result in serious
personal injury, death or property damage.
Warning: Spraying Water Hazard
When servicing pump replace all gaskets and seals. Do not re-use
old gaskets or seals. Failure to follow these instructions could result
in serious personal injury, death or property damage.
Warning: Hot Surface Hazard
If pumping hot water, insure guards or proper insulation is installed
to protect against skin contact to hot piping or pump components.
Failure to follow these instructions could result in serious personal
injury, death or property damage.
Warning: Sudden Start-Up Hazard
Disconnect and lockout power source before servicing. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Overload Hazard
Insure all motors have properly sized overload protection. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Shock Hazard
All electrical connections are to be made by a qualified electrician
in accordance with all codes and ordinances. Failure to follow these
instructions could result in serious personal injury, death or property
damage.
INSTRUCTION AND REPAIR MANUAL
SERIES 382A-SC 6
SECTION 6ITEM 382A-SC
DATED DECEMBER 2005
APPLICATIONS:
The 382A-SC Series is a superior commercial in-line pump based on the
Aurora Pump 340/380 series which has been manufactured and field
tested under the severest demands of high temperature condensate
service and boiler feed applications for over 50 years. Pumping
applications for the 382A-SC include: hot or chilled water circulation,
pressure booster systems, and cooling towers for office buildings,
hotels, hopitals, universities and warehouses.
OPERATIONAL LIMITS
Maximum Operating Pressure: 175 psi
Maximum Operating Temperature: 225°F (107°C)
ATTENTION: SAFETY WARNINGS:
Read and understand all warnings before installation or servicing pump.
ELECTRICAL SAFETY:
HIGH TEMPERATURE SAFETY:
HIGH PRESSURE SAFETY:
INSTALLATOIN:
The 382A-SC pump must be installed vertically. Install isolating valves
on each side of pump so pump maintenance can be performed with out
draining the system. Special mounting requirements may be required if
the pump is to be mounted near a noise or vibration sensitive area.
A minimum length of straight pipe is required on the suction side of the
pump. Five times the pipe diameter is sufficient to allow a smooth entry
of water into the pump.
Suction and discharge piping must be in line. Do not use pump casing to
force the alignment of the piping. Properly support the piping to provide
a rigid support for the pump. Tighten pump flanges evenly to prevent
flange cocking and liquid leakage. Do not reuse old gaskets.
ELECTRICAL CONNECTIONS:
Warning: Sudden Start-Up Hazard
Disconnect and lockout power source before servicing. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Overload Hazard
Insure all motors have properly sized overload protection. Failure
to follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Shock Hazard
All electrical connections are to be made by a qualified
electrician in accordance with all codes and ordinances.
Failure to follow these instructions could result in serious
personal injury, death or property damage.
Warning: Expansion Hazard
Water expands when heated. Install properly sized thermal
expansion tanks and relief valves. Failure to follow these
instructions could result in serious personal injury, death or
property damage.
Warning: High Pressure Hazard
The pump is rated at a maximum of 175 psi (155 psi). Do not
exceed this pressure. Install properly sized pressure relief valves in
system. Failure to follow these instructions could result in serious
personal injury, death or property damage.
Warning: Spraying Water Hazard
When servicing pump replace all gaskets and seals. Do not re-use
old gaskets or seals. Failure to follow these instructions could result
in serious personal injury, death or property damage.
Warning: Hot Surface Hazard
If pumping hot water, insure guards or proper insulation is installed
to protect against skin contact to hot piping or pump components.
Failure to follow these instructions could result in serious personal
injury, death or property damage.
Warning: Sudden Start-Up Hazard
Disconnect and lockout power source before servicing. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Overload Hazard
Insure all motors have properly sized overload protection. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Shock Hazard
All electrical connections are to be made by a qualified electrician
in accordance with all codes and ordinances. Failure to follow these
instructions could result in serious personal injury, death or property
damage.
INSTRUCTION AND REPAIR MANUAL
SERIES 382A-SC 6
SECTION 6ITEM 382A-SC
DATED DECEMBER 2005
APPLICATIONS:
The 382A-SC Series is a superior commercial in-line pump based on the
Aurora Pump 340/380 series which has been manufactured and field
tested under the severest demands of high temperature condensate
service and boiler feed applications for over 50 years. Pumping
applications for the 382A-SC include: hot or chilled water circulation,
pressure booster systems, and cooling towers for office buildings,
hotels, hopitals, universities and warehouses.
OPERATIONAL LIMITS
Maximum Operating Pressure: 175 psi
Maximum Operating Temperature: 225°F (107°C)
ATTENTION: SAFETY WARNINGS:
Read and understand all warnings before installation or servicing pump.
ELECTRICAL SAFETY:
HIGH TEMPERATURE SAFETY:
HIGH PRESSURE SAFETY:
INSTALLATOIN:
The 382A-SC pump must be installed vertically. Install isolating valves
on each side of pump so pump maintenance can be performed with out
draining the system. Special mounting requirements may be required if
the pump is to be mounted near a noise or vibration sensitive area.
A minimum length of straight pipe is required on the suction side of the
pump. Five times the pipe diameter is sufficient to allow a smooth entry
of water into the pump.
Suction and discharge piping must be in line. Do not use pump casing to
force the alignment of the piping. Properly support the piping to provide
a rigid support for the pump. Tighten pump flanges evenly to prevent
flange cocking and liquid leakage. Do not reuse old gaskets.
ELECTRICAL CONNECTIONS:
Warning: Sudden Start-Up Hazard
Disconnect and lockout power source before servicing. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Overload Hazard
Insure all motors have properly sized overload protection. Failure
to follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Shock Hazard
All electrical connections are to be made by a qualified
electrician in accordance with all codes and ordinances.
Failure to follow these instructions could result in serious
personal injury, death or property damage.
Warning: Expansion Hazard
Water expands when heated. Install properly sized thermal
expansion tanks and relief valves. Failure to follow these
instructions could result in serious personal injury, death or
property damage.
Warning: High Pressure Hazard
The pump is rated at a maximum of 175 psi (155 psi). Do not
exceed this pressure. Install properly sized pressure relief valves in
system. Failure to follow these instructions could result in serious
personal injury, death or property damage.
Warning: Spraying Water Hazard
When servicing pump replace all gaskets and seals. Do not re-use
old gaskets or seals. Failure to follow these instructions could result
in serious personal injury, death or property damage.
Warning: Hot Surface Hazard
If pumping hot water, insure guards or proper insulation is installed
to protect against skin contact to hot piping or pump components.
Failure to follow these instructions could result in serious personal
injury, death or property damage.
Warning: Sudden Start-Up Hazard
Disconnect and lockout power source before servicing. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Overload Hazard
Insure all motors have properly sized overload protection. Failure to
follow these instructions could result in serious personal injury,
death or property damage.
Warning: Electrical Shock Hazard
All electrical connections are to be made by a qualified electrician
in accordance with all codes and ordinances. Failure to follow these
instructions could result in serious personal injury, death or property
damage.