Perry Electric RECESS Series User manual

RECESS SERIES ELECTRONIC
THERMOSTATS MODULE - H 45 mm
Models with differential ON/OFF intervention and luminous charge inserted signal
1TITE301/MC Electronic thermostat with input for external night reduction control-
1TITE303/MC - Electronic thermostat with Winter-Off-Summer control and input for night reduction
Night reduction control remote
Night reduction temperature (referred to the set): -4°C
Temperature set lock mechanical with “range disc” (supplied)
Light signaling
PERFORMANCE DATA
TECHNICAL DATA
Supply voltage: 230 V~ 50 ÷ 60 Hz
Type of action, disconnect and device: 1 / B / Electronic
Type of output relay with changeover contact NO / COM / NC:
voltage free - 8(2)A / 250 V~
Output connection (load): 2 or 3 conductors
Wire section at terminals: min. mm0,75 2- max. 2,5 mm2
Insulation type: Class II
Protection degree: IP 30
Pollution:
Temperature adjustment range: from + 5 °C to + 30 °C
Thermal gradient: max 1K/15 min.
Differential operation: T=0,7°C
Precision of reading ± 1 °C
Operating temperature limits: 0 °C ÷ + 50 °C
Reference standard for CE mark: LVD EN60730-2-9 EMC EN60730-2-9
DIMENSIONS
INSTALLATION EXAMPLES
Examples of installation in heating systems
with a thermostat that controls:
A) Wall mounted boiler
B) Burner
C) Circulation pump or Motorized solenoid valve
D) Area solenoid valve
AB
C
DD
Install the thermostat at a height of 1,5 m ÷ 1,7 m from the floor, far from heat sources, air vents,
doors or windows and anything else that could affect its operation.
N.B.: the examples contained in this documentation are in principle.
PE - DETIPE013 02/18
Reference index for temperature setting
Selector for controlling work mode (only for 1TITE303/MC)
Load status LED:
alight = load ON
Temperature setting knob
5°C÷30°C
--0(Winter - OFF - Summer)
normal
SAFETY PRECAUTIONS
Attention: before starting any operations on the device, disconnect the 230V~ mains power supply
Insallation
and user
intructions
COMPATIBILITY TO THE MOST COMMON RESIDENTIAL SERIES PLATES
IMPORTANT: for the assembly procedure of the thermostat with the chosen
residential plate, follow instructions contained in the specific compatibility
sheet contained in the package.
SIGNALS AND CONTROLS (according to model)
LED showing charge inserted/disengaged
Read this manual carefully before using the
product as it provides important guidelines
regarding safety, installation and use.
The manual must be preserved with care for
future reference.
DISPOSAL OF OLD ELECTRICAL & ELECTRONIC EQUIPMENT
This symbol on the product or its packaging to indicates that this product shall not be
treated as household waste.
Instead, it shall be handed over to the applicable collection point for the recycling of
electrical and electronic equipment, such as for example:
- sales points, in case you buy a new and similar product
- local collection points (waste collection centre, local recycling center, etc...).
By ensuring this product is disposed of correctly, you will help prevent potential negative
consequence for the environment and human health, which could otherwise be caused by
inappropriate waste handing of this product.
The recycling of materials will help to conserve natural resources. For more detailed
information about recycling of this product, please contact your local city office, your house
hold waste disposal service or the shop where you purchased the product.
ERP Energy classification: ErP: Class I; 1% Reg. EU 811/2013
This appliance must be intended only for the use for which it was built. Any other use must be considered improper and dangerous.
PERRY ELECTRIC Srl
Via Milanese, 11
22070 VENIANO (CO)
ITALY www.perry.it
PE - DETIPE013EN 05/19
Important: the installation and electrical connection of the devices and appliances must be implemented by person with electrotechnical expertise only and in conformity with current laws and
regulations. he manufacturer declines any liability for the use of products subject to special environmental and/or installation standards.T
The programmable thermostat is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or by those with a lack of experience and knowledge of the
instructions, unless they are supervised or have received the necessary instructions concerning use of the device by a person responsible for their safety.
5
10
10
15
15
20
20
25
25
30
30
h 1,5 m
5
10
10
15
15
20
20
25
25
30
30
5
10
15
15
20
20
25
25
30
30
5
10
15
15
20
20
25
25
30
30
C
Children should be supervised to ensure that they do not play with the device.
()limitable
English

2-LIMITATION OF THE MAXIMUM ROOM TEMPERATURE
It is possible to preset from 16 °C to 24 °C, with 2 °C step, the maximum temperature value.
NB: the thermostat is supplied with the "range disc" preinstalled with pin in the neutral hole (no temperature limitation).
16 °C
18 °C
20 °C
22 °C
24 °C
Neutral hole
Holes for temperature setpoint limitation
Temperature limit setting or its subsequent modification
aRotate the knob anti-clockwise and pull it out.
b)
c) Reinsert the knob and verify at the end of the anti-clockwise limit corresponding to 5°C
with index, if different, re-insert the rotated by 180°.knob
Holes
Pin
Range disc
Range disc seat Fig. 1
AB C
FG
1-INSTALLATION EXAMPLE
Apply the chosen front Make the electrical connections Insert the thermostat
into the frame until it is blocked
Apply the two ledges to the frame Apply the chosen plate
Right ledge
Front
Plate
Thermostat body
E
Insert the knob
Correct knob
position
D
Set temperature lock
(only if desired)
Range disc
(if required based on the plate type)
Knob
(4 lateral blocking teeth)
Attention to the position of the
insertion pins of the ledges
Fasten the chosen frame
from the type 503 recess box
Index
3 - ELECTRICAL CONNECTIONS
Thermostat with inputs for controlling night temperature reduction, external ( )example time switch
Switch mains supply off
Connect 230V ~ power supply to the terminals: n° 4(Line) and n° (Neutral).5
Connect the wires of the device to be controlled to the terminals: n° = common1
n° =2normally open
n° =3normally closed
IMPORTANT: for heavy inductive loads (pumps and solenoid valves)
it is advisable to connect an RC filter in parallel with the load.
Fig. 3
-Example of connection to boiler and clock for night reduction control
time switch
230 V~
1TITE301/MC
1TITE303/MC
Heater
Supply voltage (230V~)
Inputs for
night reduction control
230 V~
1TITE301/MC
1TITE303/MC
Time switch with NO
contact, common to
all thermostats
1TITE301/MC
1TITE303/MC
Multiple installations
Comfort
Open
Set temperature Comfort
Contact Open
Reduction
Closed
hours 06hours 22
Fig. 2
Remote selection of "Comfort" or "Reduction" temperature
If you want to use remote control of “Comfort" or "Reduction" temperature,
connect the exterior contact to the terminals: n° and n° of the thermostat67 (fig. 3 e fig. 4).
“Comfort” Temperature = external contact open
“ ” TemperaturReduction e = external contact closed
Fig. 4
Besides all that has been mentioned above, in multiple installations (for
example offices, schools, houses, etc.) operated only by one clock for the
centralized night reduction, it is necessary to follow carefully the indications
below (fig. 4).
For all thermostats
1) Supply voltage (230V~)
Terminal n° : (230 V~)4connect the Line of network
Terminal n° :5connect the Neutral of network (return)
N.B.: normally residential power supply used the unified
colours "brown” for the phase, "blue" for neutral (line return).
2) Connections for night reduction control
All terminals n°. : connect in parallel with output time switch6of the .2
All terminals n°. : connect in parallel with output time switch7of the .1
ATTENTION: the connections to the external reduction selection contacts are network potential.
Example
20 °C
16 °C
The manufacturer reserves the right to introduce any technical and/or constructive changes deemed necessary, with no prior notice.
COMPATIBILITY TO THE MOST COMMON RESIDENTIAL SERIES PLATES
IMPORTANT: for the assembly procedure of the thermostat with the
chosen residential plate, also follow instructions contained in the
specific compatibility sheet contained in the package.
IMPORTANT! Left ledge
Take out the “temperature range” disc and reinsert it by locating
the maximum desired temperature hole over the pin placed on thermostat (Fig.1).
Selecting “Reduction” temperature determines
a decrease of 4 °C with respect to the set
temperature value.
Make sure to remove the 230V mains supply before proceeding with the installation
This manual suits for next models
2
Table of contents
Other Perry Electric Thermostat manuals

Perry Electric
Perry Electric 1TX CR028WIFI Guide

Perry Electric
Perry Electric Recess Series User manual

Perry Electric
Perry Electric MODULE Series User manual

Perry Electric
Perry Electric V002 Series Guide

Perry Electric
Perry Electric TE542 User manual

Perry Electric
Perry Electric TE540 User manual

Perry Electric
Perry Electric TE541 User manual