Philips CHLORIDE COMPAC CXX Series User manual

Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
www.philips.com/luminaires
NORMAL OPERATION/MANUAL TEST
OP-PANELINDICATORS/OPERATION:
GREEN - Status: Solid indicates system normal and AC power is on.
NOTE: To start the Manual test, simply press the Green Indicator (button) as indicated below. To Reset/Cancel a test press the Green Indicator
(button) once during any test. When Unit is in test mode the Green Indicator LED is flashing.
1 Press: perform a 5-sec brief lamp test, LED strip operating from battery only.
2 Presses: perform a 1-min diagnostic test, LED strip operating from battery
only.
3 Presses: perform a 90-min diagnostic test, LED strip operating from battery
only.
6-sec
Continuous
Press: perform a RESET operation.
CONTINUOUS MONITORING: The system monitors the following continuously:
Battery, 2) LED strip, 3) Charger, 4) Transfer function.
The battery requires at least 24 hours of charge time to perform any extended diagnostic test. If the battery has not charged for 72 hours after
installation and a diagnostic test is requested, the charger light will come on and stay on for one minute indicating that the battery is not fully charged
for attempted test.
OPTIONAL FACTORYEQUIPPEDITEMS:
FIRE-ALARM INTERFACE (FI): Unit will be supplied with a connector at the FAFI location and an interface cable to connect to the building system
(per wiring diagram).
FLASHING EM (F): Unit will flash the EXIT sign when operating from the battery only. (Flash rate is 1 flash/sec. with a 70%-on duty cycle.)
BUZZER EM (B): Unit will buzz for approx. ½ -sec during power-up sequence or after a reset operation. Buzzer does not activate during either manual
or automatic testing. Buzzer will only activate when operating from the battery and only due to AC power loss.
No Rigid
Conduit
Flexible
Conduit Only
Emergency Lighting
COMPAC
Thermoplastic Exit
oSimple snap-out Chevrons
CHEVRON CHEVRON
CXX
Series
INSTRUCTION SHEET
LASER TEST (LX): To operate using a laser pen: use laser pen and point the laser beam over the remote sensor (see below), thereby duplicating
the manual button (1,2,3) pushes. The laser must impact the remote sensor for at least 0.2 seconds to be recognized.
TROUBLE INDIC
A
TORS/TROUBLESHOOTING
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WARNING: Electrical Shock Potential!! Do not attempt to install, maintain or relamp without disconnecting
TEST
Button
REMOTE SENSOR
(IF EQUIPPED)
Xtest DISPLAY PANEL INDICAT
OR:
GREEN - Status: solid indicates system normal and AC power is on and flashes during any manual/auto test
cycle.
RED –CHARGER FLASHING: a charger failure requires the diagnostic charger board to be replaced.
RED –BATTERY FLASHING: battery is disconnected or if it is connected and charged for more than
24 hours, a replacement is needed.
RED - LAMP FLASHING: LED strip is disconnected or if it is connected a replacement is needed.
ALL 3 RED FLASHING: bad transfer; battery and LED strip are disconnected or if they are connected a
replacement diagnostic charger board is needed.
all power. Failure to disconnect power can result in electrocution, shock, or severe burns.
CAUTION: This fixture is designed for permanent installation in ordinary (NON-HAZARDOUS) locations in
accordance with the National Electrical Code and all applicable local codes. Do not use in areas of limited
ventilation or in high ambient enclosures. When using electrical equipment, basic safety precautions should
always be followed; including the following:
Do not use outdoors.
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If
WIRING INFORM
A
TION
Transformer Inputs
BLACK - 120V
WHITE - Common or Neutral
RED - 277V
Diagnostic Charger
Board
Buzzer
(If Equipped)
acid is spilled on skin or in eyes, flush acid with fresh water and contact a
physician immediately.
Equipment should be mounted in locations and at heights where it will not readily
be subjected to tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause
an unsafe condition.
Do not use this equipment for other than intended use.
Servicing of this equipment should be performed by qualified personnel only.
Transformer
Connector
EXIT
Connector
Battery
Connector
Fire-Alarm Interface
Connector (If Equipped)
SAVE THESE
INSTRUCTIONS
9
Philips Lighting Canada Ltd.
281 Markham Road,
Markham, ON, Canada L6C 2S3
Phone: 800-668-9008
www.philips.com/luminaires
727543101
CMANU0505A
February 2016

Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
www.philips.com/luminaires
INST
ALL
A
TION
INSTRUCTIONSWALL (BACK) MOUNT
Remove stencil door (front) from exit housing. Place screwdriver in slot
1 on bottom of housing and gently pry door in direction 2. Repeat on
opposite corner. Door should pop loose. See Fig. 1.
It is not necessary to remove back plate from housing when wall
mounting.
Route AC service wires through the round center knockout in back
plate, mount back plate to outlet box using screws. Use the Box
pattern knockouts in the back panel as needed to mount to wall box
and secure unit to the wall. See Fig. 2.
Remove snap out chevrons as needed.
Make AC service connection at this time. See OPERATING
INSTRUCTIONS.
INSTRUCTIONS BACK PLATE REMOV
AL
(DOUBLE FACE ON
L
Y)
To remove back plate, place screwdriver in slot 1 on bottom of housing
and gently pry door in direction 2. Repeat on opposite corner. Door
should pop loose. See Fig. 1.
Snap on EXIT stencil and reassemble exit.
INSTRUCTIONS CEILING / END MOUNT
Remove the two snap-out plugs at the desired location for the
Fig. 1
PLUG
PLUG
Fig. 2
NORMAL POWER-UP SEQUENCE
APPLY
ALL INDICATOR
LEDs FLASH 6
TIMES
EMERGENCY LAMPS
BRIEFLY ON
SELF-TESTING / SELF-DIAGNOSTIC
The unit will self-test approximately every
30 days for a minimum of 30 minutes.
canopy to fit. See Fig. 2.
Route supply wires through the hole in the body for the canopy that is
labeled “<<INPUT FEEDACCESS”.
Thread wires through opening in canopy. Insert canopy into holes in
body and snap locking bracket (Fig.3) into place, making sure wires
are clear.
Align the metal adapter plate for mounting direction and mount it to the
junction box with the input wires out though the center hole.
Make AC service connection and push the wires and wire nuts back into
junction box through the center hole in the metal adapter plate and
mount the canopy/exit-sign to the metal adapter. SEE
OPERATING INSTRUCTIONS
Remove the snap-out chevrons in the EXIT panels as needed, replace
EXIT panel(s) back on to the sign and proceed to POWER- UP
SEQUENCE.
Fig. 3
LED
STRIP
LOCKING
BRACKET
CANOPY
LOCKING
BRACKET
BACK
PANEL
BATTERY
PACK
GREEN STATUS - ON
Battery Charging
BATTERY
INDICATOR
Y
FLASHING
N
LAMP
INDICATOR
Y
FLASHING
N
BATTERY DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:
1) Most likely the Battery is not connected. Verify that the Battery is connected to the diagnostic charger
board.
2) If the Battery is connected, wait for 24 hours to charge the Battery. After 24 hours, if the Battery
indicator LED is flashing, the Battery is faulty and needs to be replaced.
3) After Battery replacement, the Battery indicator LED will stop flashing within approximately 10 to 20-
sec.
LAMP DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:
1) Verify that the LED strip is connected to the diagnostic charger board.
2) If some or all of the LEDs are off, the LED strip needs to be replaced.
OPERATING INSTRUCTIONS
TRANSFORMER
CHARGER
BOARD
Fig. 4
CHARGE
INDICATOR
FLASHING
N
Y
CHARGER DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:
1) Indicates a faulty diagnostic charger board that must be replaced.
1. Connect AC supply wires to transformer leads and push through knockout into outlet or ceiling/surface box. Observe the wire colors.
BLACK wire 120 volt AC input.
WHITE wire common or neutral for 120 or 277 volts AC input.
RED wire 277 volt AC input.
CAUTION: CAP ALL UNUSED BLACK OR RED WIRES TO PREVENT SHORTING OR ELECTRICAL SHOCK.
Note: when all wiring connections are made, push wires thru knockout into outlet box.
2. Connect the red and black wire with the 2-pin connector from battery to BATT connector on the diagnostic charger board, if not already
connected.
3. Connect the red and white wire with the 2-pin connector from transformer to XFMR connector on the diagnostic charger board if not already
connected..
4. Energize AC power to equipment and check the unit using the POWER-UP SEQUENCE (see next page). Leave AC connected for a
minimum of 24 hours to charge battery before performing normal operation/manual
tests.
ALL 3 RED
INDICATORS
FLASHING
N
TO NORMAL
OPERATION
ALL 3 DIAGNOSTIC INDICATORS FLASHING AFTER POWER-UP:
Y
1) Verify that the LED strip and the Battery are connected to the diagnostic charger board.
2) If everything is connected then the Transfer function is faulty and the diagnostic charger board must be
replaced.
P/N 717053101
20120503
Philips Lighting Canada Ltd.
281 Markham Road,
Markham, ON, Canada L6C 2S3
Phone: 800-668-9008
www.philips.com/luminaires
727543101
CMANU0505A
February 2016
Other Philips Security Sensor manuals

Philips
Philips EasySense SNS200CMP User manual

Philips
Philips EasyAir SNS300 User manual

Philips
Philips DUS804C User manual

Philips
Philips LRM226500 User manual

Philips
Philips 17266xx16 Series User manual

Philips
Philips LCN3110/05 User manual

Philips
Philips OccuSwitch LRM1771 User manual

Philips
Philips HP8115 User manual

Philips
Philips EasyAir SNS212 MC User manual

Philips
Philips EcoSet SEG101 User manual
Popular Security Sensor manuals by other brands

SW Stahl PROFI Tools
SW Stahl PROFI Tools 21050L instruction manual

Pepperl+Fuchs
Pepperl+Fuchs OBT350-R100-2EP-IO manual

PCB Piezotronics
PCB Piezotronics J113B03/062A01 Installation and operating manual

Elmes Electronic
Elmes Electronic PTX50 manual

INIM
INIM FireVibes WD200 manual

NOMA
NOMA 052-7801-8 instruction manual