Phoenix Contact QUINT4-INV User manual

1Description
DC/AC inverter
QUINT4-INV/24DC/1AC/600VA/
USB
© PHOENIX CONTACT
Data sheet
The QUINT-INV DC/AC inverter is used for generating AC
electricity in DC applications.
The output AC voltage RMS value can be configured via
software from a total of nine values in two ranges. The range
will be selected via the signal terminal during device startup.
The QUINT-INV can be connected in parallel to generate a
redundant system, to increase power, or to generate a 3-
phase grid.
– Can be used worldwide thanks to manual selection of
AC output voltage via signal terminal
– Pure sine curve at the output
– Comprehensive signaling
– Parallel connection possible (increased performance
and redundancy, 3AC)
– Integrated USB interface
– High efficiency
Technical data (short form)
Nominal input voltage 24 VDC
Input voltage range 20 VDC ... 30 VDC
Current consumption typ. 23 A / max. 28 A
Apparent power 600 VA
Real power 480 W
Nominal output voltage / Nominal
output current , 100%load
120 VAC / 5 A
( 100VAC/6A...130VAC/4,6A )
230 VAC / 2.6 A
( 200 VAC /3A...240V/2,5A )
Output voltage tolerance ( no soft
start )
±2%
Nominal output frequency 60 Hz / 50 Hz
Output frequency tolerance ±0.5%
Form of output voltage Pure sine
Efficiency ( Nominal load ) > 86 % (120 V AC) /
> 87 % (230 VAC)
MTBF (IEC 61709, SN 29500) 532525 h (40°C)
Ambient temperature (operation) -25 °C ... 60 °C
Dimensions (W/H/D) 180 / 130 / 125 mm
Weight 2.5 kg
All technical specifications are nominal and refer to a room temperature of 25°C and 70% relative humidity at
2000m above sea level.
108987_en_00 2020-09-28

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 2 / 25
2Tableofcontents
1 Description ..................................................................................................................................1
2 Table of contents.........................................................................................................................2
3 Ordering data ..............................................................................................................................4
4 Technical data.............................................................................................................................5
5 Safety regulations and installation notes ...................................................................................10
5.1 Symbols used...............................................................................................................................................10
5.2 Important safety and warning instructions.....................................................................................................10
6 Design.......................................................................................................................................12
6.1 Function elements ........................................................................................................................................12
6.2 Device dimensions and keep-out areas........................................................................................................13
6.3 Block diagram...............................................................................................................................................13
7 Mounting and removing.............................................................................................................14
7.1 Convection ...................................................................................................................................................14
7.2 Normal mounting position.............................................................................................................................14
7.3 Mounting the inverter....................................................................................................................................14
7.4 Removing the inverter...................................................................................................................................15
7.5 Wall mounting...............................................................................................................................................15
8 Device connection.....................................................................................................................17
8.1 Connection parameters ................................................................................................................................17
9 Device connection terminal blocks ............................................................................................17
9.1 DC input........................................................................................................................................................17
9.2 AC output......................................................................................................................................................18
9.3 Connection terminal block signaling .............................................................................................................18
10 Interface ....................................................................................................................................18
10.1 USB mini type B............................................................................................................................................18
11 Device operation .......................................................................................................................19
11.1 Setting the operating mode...........................................................................................................................19
11.2 Remote.........................................................................................................................................................19
11.3 Start120V/Start230V ...............................................................................................................................19
12 Method of operation .................................................................................................................. 20
12.1 Device start...................................................................................................................................................20
12.2 Output voltage setting options ......................................................................................................................20
12.3 Input voltage setting options .........................................................................................................................20
13 Parallel operation ......................................................................................................................21
13.1 Increasing power ..........................................................................................................................................21
13.2 Redundant operation ....................................................................................................................................21
13.3 3AC operation...............................................................................................................................................21

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 3 / 25
14 Signaling ...................................................................................................................................22
14.1 LED indicators and signal outputs ................................................................................................................23
14.2 Signal outputs...............................................................................................................................................24
14.3 Signal inputs .................................................................................................................................................24
15 Derating.....................................................................................................................................25
15.1 Ambient temperature ....................................................................................................................................25
15.2 Installation height..........................................................................................................................................25

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 4 / 25
Description Ty p e Order No. Pcs./Pkt.
Inverter, QUINT, DIN rail mounting, input:24 VDC,
output:1AC / 600 VA, Pure sine.
QUINT4-INV/24DC/1AC/
600VA/USB
1067325 1
3Orderingdata
Accessories Ty p e Order No. Pcs./Pkt.
Used for communication between an industrial PC and
Phoenix Contact devices with USB-Mini-B connection.
MINI-SCREW-USB-
DATACABLE
2908217 1
2-piece universal wall adapter for securely mounting the
device in the event of strong vibrations. The profiles that
are screwed onto the side of the device are screwed
directly onto the mounting surface. The universal wall
adapter is attached on the left/right.
UWA 130 2901664 1
Universal wall adapter for securely mounting the device in
the event of strong vibrations. The device is screwed
directly onto the mounting surface. The universal wall
adapter is attached on the top/bottom.
UWA 182/52 2938235 1
Type 2/3 surge protection, consisting of protective plug
and base element, with integrated status indicator and
remote signaling for single-phase power supply networks.
Nominal voltage 120VAC/DC.
PLT-SEC-T3-120-FM-UT 2907918 5
Type 2/3 surge protection, consisting of protective plug
and base element with screw connection. For single-
phase power supply network with integrated status
indicator and remote signaling. Nominal voltage
230VAC/DC.
PLT-SEC-T3-230-FM-UT 2907919 5
Our range of accessories is being continually extended, our current range can be found in the download area.

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 5 / 25
4 Technical data
Input data
Nominal input voltage 24 VDC
Input voltage range 20 VDC ... 30 VDC
Current consumption typ. 23 A / max. 28 A
Connection data, input
Connection method Screw connection
Conductor cross section, rigid 0.2 mm² ... 6 mm²
Conductor cross section, flexible 0.2 mm² ... 4 mm²
Conductor cross section / flexible with ferrule with plastic
sleeve
0.2 mm² ... 4 mm²
Conductor cross section / flexible with ferrule without
plastic sleeve
0.2 mm² ... 4 mm²
Conductor cross section AWG/kcmil 30 ... 10
Stripping length 8 mm
Tightening torque 0.5 Nm ... 0.6 Nm
Output data
Apparent power 600 VA
Real power 480 W
Power factor (cos phi) 0.8
Nominal output voltage / Nominal output current ,
100%load
120 VAC / 5 A ( 100VAC/6A...130VAC/4,6A )
230 VAC / 2.6 A ( 200 VAC /3A...240V/2,5A )
Output voltage tolerance ( no soft start ) ±2%
Nominal output frequency 60 Hz / 50 Hz
Output frequency tolerance ±0.5%
Form of output voltage Pure sine
Crest factor 2.8
Total harmonic distortion factor (THD) < 3 % (linear load)
< 8 % (non-linear load)
Overload capacity 105 % ( Permanent )
120 % / 150 % ( 20s/5s, then shutdown )
Electronic current limitation > 2,5 x IN(>200ms)

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 6 / 25
Efficiency ( Nominal load ) 120 VAC 230 VAC
> 86 % > 87 %
Eta [%]
Pout [W]
60
65
70
75
80
85
90
95
100
50 100 150 200 250 300 350 400 450 500
Power dissipation 120 VAC 230 VAC
No load typ. 21 W typ. 21 W
Nominal load typ. 72 W typ. 66 W
Output connection data
Connection method Screw connection
Conductor cross section, rigid 0.2 mm² ... 6 mm²
Conductor cross section, flexible 0.2 mm² ... 4 mm²
Conductor cross section flexible, with ferrule with plastic
sleeve
0.2 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without
plastic sleeve
0.2 mm² ... 4 mm²
Conductor cross section AWG/kcmil 30 ... 10
Stripping length 8 mm
Tightening torque 0.5 Nm ... 0.6 Nm
Status and diagnostic indicator / signal output Alarm
Connection labeling 3.1
Switching output Transistor output, active
Output voltage 24 V
Continuous load current 20 mA
LED status indicator red
Status and diagnostic indicator / signal output AC OK
Connection labeling 3.2
Switching output Transistor output, active
Output voltage 24 V
Continuous load current 20 mA
LED status indicator green
Status and diagnostic indicator / signal output DC OK
Connection labeling 3.3
Switching output Transistor output, active
Output voltage 24 V
Continuous load current 20 mA
LED status indicator green

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 7 / 25
Status and diagnostic indicator / signal output P>Pn
Connection labeling 3.4
Switching output Transistor output, active
Continuous load current 20 mA
LED status indicator green
Status and diagnostic indicator / signal input Start230V
Connection labeling 3.6
Low signal Connection to SGnd with < 2.7 kΩ
High signal Open (> 200kΩbetween Start and SGnd)
Status and diagnostic indicator / signal input Start120V
Connection labeling 3.7
Low signal Connection to SGnd with < 2.7 kΩ
High signal Open (> 200kΩbetween Start and SGnd)
Status and diagnostic indicator / signal output Out1
Connection labeling 3.5
Switching output Transistor output, active
Status and diagnostic indicator / signal input Remote
Connection labeling 3.8
Low signal Connection to SGnd with < 2.7 kΩ
High signal Open (> 35 kΩbetween remote and SGnd)
Signal ground SGnd
Connection labeling 3.9
Function Signal ground
Reference potential For signal inputs and signal outputs
Signal connection data
Connection method Screw connection
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule with plastic
sleeve
0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without
plastic sleeve
0.2 mm² ... 1.5 mm²
Conductor cross section AWG/kcmil 30 ... 12
Stripping length 8 mm
Tightening torque 0.5 Nm ... 0.6 Nm

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 8 / 25
Data interface USB (Modbus/RTU)
Connection labeling 5.1
Interface designation USB (Modbus/RTU)
USB classification MINI-USBTypeB
Transmission physics USB 2.0
Locking Screw
Electrical isolation yes
Data interface Parallel Port
Connection labeling 5.2
Interface designation Parallel Port
Connection method RJ45
Locking Locking clip
Electrical isolation yes
Device combinations
Connection in parallel yes , max. 3
Connection in series no
General data
Overvoltage category according to EN 61010-2-201 II
MTBF (IEC 61709, SN 29500) 532525 h (40°C)
Degree of protection / Protection class IP20 / I
Dimensions (W/H/D) 180 / 130 / 125 mm
Weight 2.5 kg
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Derating ( Output power ) >50°C: 2,5%/K
Ambient temperature (storage/transport) -40 °C ... 85 °C
Humidity, non-condensing ≤95 %
Installation height ≤3000 m
Derating ( Output power ) >2,000m:0.6%/100m
Degree of pollution 2
Vibration (operation) 5Hz...100Hz, 0.7g (EN60068-2-6)
Shock 20g in all directions (EN 60068-2-27)
Approvals
UL UL/C-ULRecognizedUL1778
UL/C-UL Listed UL61010-1
UL/C-UL Listed UL61010-2-201
Current approvals/permissions for the product can be found in the download area under
phoenixcontact.net/products

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 9 / 25
Electromagnetic compatibility / Conformance with EMC Directive 2014/30/EU
Noise emission in accordance with EN61000-6-4
Conducted noise emission EN 61000-6-4
Noise emission EN 61000-6-4
Immunity in accordance with EN61000-6-2
CE basic standard EN61000-6-2 requirement Te s t e d
Electrostatic discharge EN 61000-4-2
Housing contact discharge ± 6 kV ± 6 kV
Housing air discharge ± 8 kV ± 8 kV
Comments Criterion B Criterion A
Electromagnetic HF field EN61000-4-3
Frequency range 80 MHz ... 1 GHz 80 MHz ... 6 GHz
Test field strength 10 V/m 10 V/m
Comments Criterion A Criterion A
Fast transients (burst) EN61000-4-4
Input ± 2 kV ± 2 kV
DC input ± 2 kV ± 2 kV
Output ± 2 kV ± 2 kV
Signal ± 2 kV ± 2 kV
Signal USB -- ± 2 kV
Comments Criterion B Criterion A (B for USB)
Surge voltage load (surge) EN61000-4-5
Input ± 1 kV (symmetrical)
± 2 kV (asymmetrical)
± 1 kV (symmetrical)
± 2 kV (asymmetrical)
Output ± 1 kV (symmetrical)
± 2 kV (asymmetrical)
± 2 kV (symmetrical)
± 4 kV (asymmetrical)
Signal 1 kV (asymmetrical) 1 kV (asymmetrical)
Comments Criterion B Criterion A
Conducted interference EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz
Signal 10 V 10 V
Comments Criterion A Criterion A
Power frequency magnetic field EN 61000-4-8
Frequency 50 Hz , 60 Hz 50 Hz , 60 Hz
Signal 30 A/m 30 A/m
Comments Criterion A Criterion A
Key
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 10 / 25
5 Safety regulations and installation
notes
5.1 Symbols used
Instructions and dangers are labeled with the corresponding
symbols in this installation note.
There are different categories of personal injury that are
indicated by a signal word.
The following symbols are used to indicate potential
damage, malfunctions, or more detailed sources of
information.
5.2 Important safety and warning instructions
– Only skilled persons may install, start up, and operate
the device.
– For indoor use only.
– Never carry out work when voltage is present.
– Establish connection correctly and ensure protection
against electric shock.
– Connect the protective conductor device terminal block
with ground.
– Ensure that the primary-side wiring and secondary-side
wiring are the correct size and have sufficient fuse
protection.
– Cover termination area after installation in order to avoid
accidental contact with live parts (e. g., installation in
control cabinet).
– Keep flames, embers or sparks away from the module.
– Provide a switch/circuit breaker close to the device at
the DC input and the AC output respectively, which are
marked as the disconnecting device for this device.
This is the safety alert symbol. It is used to alert
you to potential personal injury hazards. Obey all
safety measures that follow this symbol to avoid
possible personal injuries.
WARNING
This indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
This indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
NOTE
This symbol together with the signal word NOTE
and the accompanying text alert the reader to a
situation which may cause damage or malfunction
to the device, hardware/software, or surrounding
property.
This symbol and the accompanying text provide
the reader with additional information or refer to
detailed sources of information.
This indicates that the device can be hot and
should not be touched without taking care.
WARNING: Danger to life by electric shock!
CAUTION: Hot surface
The housing can become hot, depending on the
ambient temperature and device load.

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 11 / 25
– Observe the national safety and accident prevention
regulations.
– Assembly and electrical installation must correspond to
the state of the art.
– The inverter is a built-in device. The IP20 degree of
protection of the device is intended for use in a clean
and dry environment.
– The device must be installed in a control cabinet that
can be locked and only opened by specialist staff.
– Use in a CONTROLLED ENVIRONMENT - the unit is
intended for installation in a temperature-regulated,
indoor area that is relatively free of conductive
contaminants.
– The housing can become hot, depending on the
ambient temperature and device load.
– Observe the mechanical and thermal limits of the
device.
– Ensure sufficient convection. Information on minimum
clearances to other devices is listed in the section:
Device dimensions and keep-out areas.
– Ensure that the location is sufficiently ventilated.
– Mount the device horizontally (standard mounting
position).
– Use copper cables with an operating temperature of
75°C(ambient temperature55°C)and
90°C (ambient temperature75°C).
– For the connection parameters, suchas the required
stripping length for wiring with and without ferrule, refer
to the technical data.
– To reduce the risk of fire, connect only to a circuit
provided with the following maximum branch circuit
overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70.
– To reduce the risk of fire, replace fuses only with those
that have the same type and rating. Relevant fuses can
be found in the accessories in the ordering data.
– The device is maintenance-free. Repairs may only be
carried out by the manufacturer. Opening the housing
invalidates the warranty.
– The inverter may only be used for its intended use.
– Improper use invalidates the device protection.
– Provide an easily reached switch/ fuse for wiring input
terminal close to the device at one pole of the DCinput,
which is marked as the disconnecting device for this
device (30VDC,50A, slow blow).
– Ensure that no hazardous voltage in normal mode or
single fault case applies to all signal terminals and
communication interfaces.
– Source connected to the inverter input must be SELV
circuits that can be either battery circuits or secondary
circuits derived from mains circuits of overvoltage
category CAT II up to 300V and have to be separated
from mains circuits by double or reinforced insulation.
– A suitable electrical and fire enclosure which provides
adequate mechanical rigidity shall be provided by the
end product.
– When using a battery, follow the battery manufacturer's
instructions and ensure that the input data of the
inverter are observed.
– The switching outputs are active outputs according to
SELV. These may only be operated on permitted SELV
circuits.
– The permanent output power PNis limited at an ambient
temperature of 60°C. Observe the maximum output
powers for the respective operating conditions.
– Keep these instructions in a safe place – this data sheet
contains important safety notes which must be
observed during installation and maintenance of the
device.
NOTE
More follows

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 12 / 25
6Design
6.1 Function elements
Figure 1 Position of the function elements
Key
N
2.4 1.3 230V
120V
AC OK
P>Pn / Remote
Output AC 120/230V
LN
2.1 2.2 2.3
Input DC 24V
+-
1.1 1.2 5.1
QUINT AC-INV 600VA
Alarm
Alarm
3.1
AC OK
3.2
DC OK
3.3
P>Pn
3.4
Out1
3.5
Start230V
3.6
Start 120V
3.7
Remote
3.8
SGnd
3.9
L1 (Slave)
L1
(Master)
L1
(Master)
Soft Start
L3
L2
Single Redundancy
Power
3AC
Link
Parallel Port
5.2
DC OK
15
114 13 12 11 10
8
7
6
5
4
3
2
9
No. Designation Connection
labeling
1PE/Nbridge connection terminal
blocks
2.4, 1.3
2 Universal DIN rail adapter (rear of
housing)
3 Signaling connection terminal
blocks
3.1...3.9
4 LED parallel run
5 Communication interface parallel
run
5.2
6 Rotary selector switch parallel run
mode: Operating mode
7 LED status indicator Alarm
8 Rotary selector switch parallel run
mode: Phase
9DCOKLED
10 Communication interface (device
underside)
5.1
11 Connection terminal blocksinput
voltage: InputDC+/-
1.1, 1.2
12 LED AC OK/P>Pn/Remote
13 QR code web link
14 Output voltage connection termi-
nal blocks:
Output AC L/N/
2.1...2.3
15 PE/N bridge

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 13 / 25
6.2 Device dimensions and keep-out areas
Figure 2 Device dimensions and keep-out areas
6.3 Block diagram
Figure 3 Block diagram Key
N
2.4 1.3 230V
120V
AC OK
P>Pn / Remote
Output AC 120/230V
LN
2.1 2.2 2.3
Input DC 24V
+-
1.1 1.2
QUINT AC-INV 600VA
Alarm
Alarm
3.1
AC OK
3.2
DC OK
3.3
P>Pn
3.4
Out 1
3.5
Start 230V
3.6
Start 120V
3.7
Remote
3.8
SGnd
3.9
L1 (Slave)
L1
(Master)
L1
(Master)
Soft Start
L3
L2
Single Redundancy
Power
3AC
Link
Parallel Port
5.2
5.1
130 50
50
180
DC OK
125
132,5
=
=
=
C
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
2.1
2.2
2.3
1.1
1.2
5.15.2
-
+Output
AC
N
L
PE
Alarm
AC OK
DC OK
P>Pn
Out 1
Start 230V
Start 120V
Remote
SGnd
Input
DC
Parallel
PE
N
Port
2.4
1.3
Element Designation
DC/DC converter with electrical isolation
Inverter
Microcontroller
LED
Temperature sensor
Rotary selector switch
=
=
µC
J

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 14 / 25
7 Mounting and removing
7.1 Convection
Figure 4 Convection
7.2 Normal mounting position
Figure 5 Normal mounting position
7.3 Mounting the inverter
Proceed as follows to mount the device:
1. In the normal mounting position the device is mounted
on the DIN rail from above. Make sure that the universal
DIN rail adapter is in the correct position behind the DIN
rail (A).
2. Then press the device down until the universal DIN rail
adapter audibly latches into place (B).
3. Check that the device is securely attached to the DIN
rail.
Figure 6 Snapping onto the DIN rail
NOTE
The device must be installed in a control cabinet
that can be locked and only opened by specialist
staff.
CAUTION: Hot surface
The housing can become hot, depending on the
ambient temperature and device load.
NOTE: enable convection
To ensure sufficient convection, maintain an
adequate minimum clearance between the
inverter and above/below the installed devices.
For information on the required minimum
clearances, refer to the section: Device
dimensions and keep-out areas.
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
QUINT AC-INV 600VA
Alarm
DCOK
3AC
Link
Power
Single
Redundancy
AC OK
P>Pn/ Remote
L1 (Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
Parallel Port
5.2
LN
2.1 2.2 2.3
Output AC120/230V
N
2.4 1.3
5.1
230V
120V
+
-
1.1 1.2
Input DC24V
The device can be snapped onto all DIN rails
according to EN60715 and should only be
mounted in the normal mounting position.
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
QUINT AC-INV 600VA
Alarm
DCOK
3AC
Link
Power
Single
Redundancy
AC OK
P>Pn/ Remote
L1 (Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
Parallel Port
5.2
LN
2.1 2.2 2.3
Output AC120/230V
N
2.41.3
5.1
230V
120V
+
-
1.1 1.2
Input DC 24V
Click
B
A

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 15 / 25
7.4 Removing the inverter
Proceed as follows to remove the device:
1. Take a suitable screwdriver and insert this into the lock
hole on the universal DIN rail adapter (A).
2. Release the lock by lifting the screwdriver (B).
3. Carefully swivel the device forward (C) so that the lock
slides back into the starting position.
4. Then separate the device from the DIN rail (D).
Figure 7 Removing from the DIN rail
7.5 Wall mounting
The UWA 182/52 universal wall adapter (Order No.
2938235) or UWA 130 universal wall adapter (Order No.
2901664) is used to attach the device directly to the
mounting surface.
The use of the universal wall adapter is recommended under
extreme ambient conditions, e.g.,strong vibrations. Thanks
to the tight screw connection between the uninterruptible
power supply and the universal wall adapter or the actual
mounting surface, an extremely high level of mechanical
stability is ensured.
7.5.1 Mounting the UWA182/52 universal wall
adapter
Proceed as follows to disassemble the universal DIN rail
adapter that comes pre-mounted:
1. Remove the screws for the universal DIN rail adapter
using a suitable screwdriver (Torx 10).
2. Remove the universal DIN rail adapter from the rear of
the device.
3. Position the universal wall adapter in such a way that
the keyholes or oval tapers face up. The mounting
surface for the device is the raised section of the
universal wall adapter.
4. Insert the Torx screws into the appropriate hole pattern
on the universal wall adapter so that the necessary
mounting holes of the device can be accessed.
5. Screw the universal wall adapter onto the device.
Figure 8 Mounting the UWA 182/52 universal wall
adapter
The maximum tightening torque of the Torx screw
(Torx® T10) is 0.9 Nm.
Make sure you use suitable mounting material
when attaching to the mounting surface.
C
D
B
A
The UWA182/52 universal wall adapter (Order
No. 2938235) is attached to the device by means
of the Torx screws of the universal DIN rail
adapter.

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 16 / 25
7.5.2 Mounting the UWA130 2-piece universal wall
adapter
Proceed as follows to disassemble the universal DIN rail
adapter that comes pre-mounted:
1. Remove the screws for the universal DIN rail adapter
using a suitable screwdriver (Torx 10).
2. Remove the universal DIN rail adapter from the rear of
the device.
3. Position the two-piece universal wall adapter on the
right and left side of the housing.
4. Insert the Torx screws into the appropriate hole pattern
on the universal wall adapter so that the necessary
mounting holes of the device can be accessed.
5. Screw the two-piece universal wall adapter onto the
device.
Figure 9 Mounting the UWA130 universal wall adapter
The UWA 130 universal wall adapter (Order No.
2901664) is attached to the device using the Torx
screws provided.

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 17 / 25
8 Device connection
8.1 Connection parameters
Figure 10 Connection parameters
9 Device connection terminal blocks
9.1 DC input
The supply voltage is connected via the connection terminal
blocks: InputDC24V.
Figure 11 Input voltage connection terminal blocks:
InputDC+/-(1.1,1.2) and N/(2.4,1.3)
The neutral conductor of the AC output is connected to PE
via the pre-installed bridge in terminals 2.4 and 1.3.
Remove the bridge to change the output voltage supply
system configuration.
[mm²]
0.2-4
0.2-4
0.2-4
0.2-1.5
Input DC 1.1...1.2
Output AC 2.1...2.3
Signals 3.1...3.9
N 2.4, PE 1.3 Screw
0.2-6
0.2-6
0.2-6
0.2-1.5
[mm²]
0.2-4
0.2-4
0.2-4
0.2-1.5
[mm²] [mm²]
0.2-4
0.2-4
0.2-4
0.2-1.5
(Cu)
30-10
30-10
30-10
30-12
8
8
8
8
L[mm]
0.5-0,6
0.5-0.6
0.5-0.6
0.5-0.6
[Nm] [lb in]
5-7
5-7
5-7
5-7
AWG
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
QUINT AC-INV 600VA
Alarm
3AC
Link
Power
Single
Redundancy
AC OK
P>Pn / Remote
L1(Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
ParallelPort
5.2
LN
2.1 2.2 2.3
Output AC 120/230V
N
2.4 1.3
5.1
230V
120V
+
-
1.1 1.2
Input DC24V
N
2.4 1.3
+-
1.1 1.2
Input DC 24V

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 18 / 25
9.2 AC output
Buffered output voltage is connected via connection
terminal blocks: OutputAC120/ 230V.
Figure 12 Output voltage connection terminal blocks:
Output AC L/N/(2.1...2.3)
9.2.1 Protection of the secondary side
The inverter is electronically short-circuit-proof and idling-
proof.
Ensure that all output cables are dimensioned appropriately
for the maximum output current or have separate protection.
9.3 Connection terminal block signaling
The inverter has the signal outputs:
– Alarm (can be inverted via software)
– AC OK (can be inverted and parameterized via
software)
– DC OK (can be inverted and configured via software)
–P>P
n (can be inverted and parameterized via software)
–Out1
Figure 13 Connection terminal block signaling (3.1...3.9)
The device also features the signal inputs:
–Remote
–Start120 V: inverter startup in the 120V range, digital
input
–Start230 V: inverter startup in the 230V range, digital
input
10 Interface
10.1 USB mini type B
The device is equipped with a USB Mini type B interface for
data transmission.
A data cable is required for communicating with a PC or a
higher-level controller.
Figure 14 Service USB interface Mini type B (device
bottom) (5.1)
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.23.3 3.4 3.5 3.6 3.7 3.8 3.9
QUINT AC-INV 600VA
Alarm
3AC
Link
Power
Single
Redundancy
AC OK
P>Pn / Remote
L1(Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
Parallel Port
5.2
LN
2.1 2.2 2.3
Output AC 120/230V
N
2.4 1.3
5.1
230V
120V
+
-
1.1 1.2
Input DC24V
LN
2.1 2.2 2.3
Output AC 120/230V
230V
120V
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
QUINT AC-INV 600VA
Alarm
DCOK
3AC
Link
Power
Single
Redundancy
AC OK
P>Pn / Remote
L1(Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
ParallelPort
5.2
LN
2.1 2.2 2.3
Output AC 120/230V
N
2.4 1.3
5.1
230V
120V
+
-
1.1 1.2
Input DC24V
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
Alarm
DC OK
AC OK
Out 1
P>Pn
Start 230V
Start 120V
Remote
SGnd
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
QUINT AC-INV 600VA
Alarm
DCOK
3AC
Link
Power
Single
Redundancy
AC OK
P>Pn / Remote
L1(Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
ParallelPort
5.2
LN
2.1 2.2 2.3
Output AC 120/230V
N
2.4 1.3
5.1
230V
120V
+
-
1.1 1.2
Input DC24V

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 19 / 25
10.1.1 MINI-SCREW-USB-DATACABLE
The uninterruptible power supply unit is connected to the
USB PC connection with data cable MINI-SCREW-USB-
DATACABLE (Order No. 2908217) via USB interface mini
type B.
Figure 15 MINI-SCREW-USB-DATACABLE
11 Device operation
Basic settings for commissioning can be made directly on
the device using the rotary selector switches. Advanced
settings can be made via the POWER MANAGEMENT
SUITE PC software.
11.1 Setting the operating mode
You can set the operating mode via the upper rotary selector
switch on the front of the device:
– Single operation (switch position: Single)
– Parallel operation for power increase (switch position:
Power)
– Parallel operation for redundancy (switch position:
Redundancy)
– Parallel operation for creating a 3AC grid (switch
position: 3AC)
Figure 16 Rotary selector switch parallel run mode:
Operating mode
You can set the device hierarchy via the lower rotary
selector switch on the front of the device:
– Master device in the mode power increase,
redundancy, or 3AC (switch position: L1 (Master))
– Slave device in the mode power increase or
redundancy (switch position: L1 (Slave))
– 1st slave device in the mode 3AC (switch position: L2)
– 2nd slave device in the mode 3AC (switch position: L3)
– Master device in the mode 3AC with “inclined” start
characteristic curve (switch position: L1 (Master) Soft
Start).
Only applicable in 3AC operation at 230V output
voltage. In this switch position, the output voltage drops
briefly during startup.
Figure 17 Rotary selector switch parallel run mode:
Phase
11.2 Remote
You can use the Remote signal terminal to switch the
inverter output on and off.
To do this, you must connect the Remote signal terminal to
the SGnd signal terminal.
t0: Remote signal is set, output will be switched off
t1: the remote signal will be reset, output will be switched
back on
t2: No input voltage, output will be switched off
11.3 Start120V/Start230V
You can use the Start 120V or Start 230V signal terminals
to start the inverter.
–Start120V: The output voltage is 120V/60Hz
–Start230V: The output voltage is 230V/50Hz
To exit operation, you must disconnectsignal terminal
Start120V or signal terminal Start230V from signal
terminal SGnd.
No. Designation
1 Mini type B USB connector with screw connection
2 USB plug type A
3 Cable length: 3m
The latest software version is to be found in the
product download area.
1
3
2
3AC
Power
Single Redundancy
L1 (Slave)
L1
L1
L2
L3
(Master)
(Master)
Soft Start
U
IN
U
OUT
t
0
t
1
Remote
t
2
t

QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00 PHOENIX CONTACT 20 / 25
12 Method of operation
12.1 Device start
When a valid input voltage is applied and one of the Start
terminals are connected to SGnd, the device starts. During
the subsequent LED test, all LEDs on the front of the device
are switched on for a short time. Afterward, any inverters
connected in parallel will be synchronized and the output
switched on.
The inverter always works in one of two voltage ranges with
one of two nominal frequencies:
–100V or 200V range
–50Hz or 60Hz
In order to start in the 100V range, signal terminal
3.7Start120V must be connected with the signal terminal
3.9SGnd (see section: Device operation).
In order to start in the 200V range, signal terminal
3.6Start230V must be connected with the signal terminal
3.9SGnd (see section: Device operation).
To exit operation, you must disconnectsignal terminal
Start120V or signal terminal Start230V from signal
terminal SGnd.
12.2 Output voltage setting options
You can use the POWER MANAGEMENT SUITE software
to set one of the following nominal voltages or nominal
frequencies per voltage range:
–100V range:
– 100V, 110V, 120V(=default), or 130V
50Hz or 60Hz(=default)
–200V range:
– 200V, 210V, 220V, 230V(=default), or 240V
50Hz(=default) or 60Hz
12.3 Input voltage setting options
You can set the following DC input voltage parameters via
the POWER MANAGEMENT SUITE software:
– Lower DC input voltage limit: 20VDC...26.5VDC,
default:20VDC
– Upper DC input voltage limit: 28VDC...30V DC,
default:30VDC
– Activation threshold: 20.5VDC...27VDC, default:
23VDC
Note that the activation threshold must be at least 0.5V
higher than the lower DC input voltage limit. This creates a
hysteresis when switching on with increasing DC input
voltage.
For the upper DC input voltage limit, a hysteresis of 0.5V is
taken into consideration automatically with decreasing DC
input voltage.
Figure 18 Input voltage range: Default
12.3.1 Application example: Operation on an AC/DC
power supply
The inverter DC input voltage is generated via an AC/DC
power supply.
– Lower DC input voltage limit: 20VDC
– Upper DC input voltage limit: 30VDC
– Activation threshold: 20.5VDC
Figure 19 Application example: Operation on an AC/DC
power supply
This example illustrates the broadest possible working
range of the inverter.
If the Start120V or Start230V signal terminal is
already connected to SGnd, the device starts
when a valid input voltage is applied.
Note that when starting in a parallel system the
respective start signal terminal of the individual
inverters are connected with SGnd simultaneously
(time offset <5seconds).
. . .
. . .
[V DC]
Device
on
off
20 23 30
29,5
. . .
. . .
[V DC]
Device
on
off
20
20,5
30
29,5
This manual suits for next models
4
Table of contents
Other Phoenix Contact Inverter manuals