Pittway NOTIFIER AFM-16AT User manual

THE
ANNUNCIATOR
FIXED
MODULE
Installation Manual for the
AFM-16AT and AFM-32A
AnnunciatorModules
12 Clintonville Road
Northford, CT 06472
203-484-7161 FAX: 203-484-7118
Document 15048
07/16/97 Revision: D1
ECN 97-294
www.PDF-Zoo.com
firealarmresources.com

WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/
or inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service,
or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72-1993 Chapter
7 after any programming operation or change in site-
specific software. Reacceptance testing is required after
any change, addition or deletion of system components,
or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, up to a
maximum of 50 devices, must be tested and proper
system operation verified.
This system meets NFPA requirements for
operation at 0-49OC/32-120OF
and at a relative
humidity of 85% RH (non-condensing) at 30O C/86O
F. However, the useful life of the system's standby
batteries and the electronic components may be
adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an
environment with a nominal room temperature of 15-
27OC/60-80OF.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased suscep-
tibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or en-
countered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making
modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any
circuits so that static charges are removed from the body. Use
static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from
standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise feature
of each detector should be tested at least once per year by
a qualified fire protection specialist.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled.
The most common cause of fire alarm malfunctions, how-
ever, is inadequate maintenance. All devices and system
wiring should be tested and maintained by professional fire
alarm installers following written procedures supplied with
each device. System inspection and testing should be sched-
uled monthly or as required by National and/or local fire codes.
Adequate written records of all inspections should be kept.
An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warn-
ing devices, and a fire alarm control with remote notification
capability can provide early warning of a developing fire. Such
a system, however, does not assure protection against prop-
erty damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in walls, or roofs, or
on the other side of closed doors. Smoke detectors also may
not sense a fire on another level or floor of a building. A
second floor detector, for example, may not sense a first floor
or basement fire. Furthermore, all types of smoke detectors
- both ionization and photoelectric types, have sensing limi-
tations. No type of smoke detector can sense every kind of
fire caused by carelessness and safety hazards like smoking
in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children
playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm
system, crippling its ability to report a fire.
While installing a fire alarm system may make lower insur-
ance rates possible, it is not a substitute for fire insurance!
Fire Alarm System Limitations
Installation Precautions Adherence to the following will aid in problem-free
installation with long-term reliability:
Technical Publishing Document PRECAUSM.PM6 07/12/96
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 3
The AFM
Inventory
Installation
Mounting the Backbox
Terminating the Shield
Inserting Display Labels
Annunciator Jumper Options
Mounting the Dress Plate
Applying the Annunciator Label
Installing AFM Options
AFM Field Connections
Installation Requirements
Main Power Supply Connections
Operation
AFM-16AT Operation
AFM-32A Operation
Annunciator Point Functions
Slide-In Labels
4
6
8
9
9
10
12
13
13
14
15
16
17
18
18
19
20
Table of Contents
Section One:
Section Two:
Section Three:
Section Four:
(center)
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
4
Section One:The AFM
Annunciator Fixed Modules provide the control panel with discrete display and control
points. These annunciators turn their LEDs ON and OFF as commanded by the system's
CPU. In addition, they report selected switch activations to the CPU for action.
Limits
The AFM-16AT is intended for use in systems that require 16 annunciation points or less.
TheAFM-32Aisintendedforuseinsystemsthatrequire32annunciationpoints(alarmonly)
or less. Only one annunciator may be used in a system. Each annunciator's address is
internally fixed at "1."
Capabilities
The AFM-16AT can annunciate the following:
Circuits: IZ-4, IZ-8 and IZM-8 Initiating Device Circuits (alarm and trouble)
AIM-200 Software Zones (alarm and trouble)
IC-4, ICM-4 and ICE-4 Notification Appliance Circuits (trouble)
CR-4, CRM-4 and CRE-4 Control Relays (trouble)
TC-2, TC-4, TCM-2, and TCM-4 circuits (trouble)
CPU Controls: Acknowledge, Signal-Silence and System Reset. If desired,
the Alarm Relay, Indicating Circuits 1 and 2, and the Remote Station
Municipal Tie may be controlled from the AFM-16AT.
The AFM-32A can annunciate the following:
Circuits: IZ-4, IZ-8 and IZM-8 Initiating Device Circuits (alarm and trouble)
AIM-200 Software Zones (alarm and trouble)
CPU Controls: System Alarm, and the activation of Indicating Circuits 1 and 2,
the Remote Station Municipal Tie and the Alarm Relay.
Controls: Local Silence/Acknowledge and Lamp Test.
Software Required
The AFM is fully compatible with the System 500 (CPU–500). To operate the AFM with a
System 5000 FACP, the CPU-5000 must be operating under software with ROM U4
software numbered 73085 or greater.
Electrical Ratings
Input Voltage: 24 volts DC (must be power-limited).
Current Draw from 24 volt DC Input: 0.040 Amps in Standby; 0.056 Amps in Alarm
Data Communications Port: EIA-485 operating at 20.833 Kbaud(must be power-limited).
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 5
Fire Alarm
Control Panel
Wiring
Communication between the control panel and the AFM is accomplished over a two-wire
power-limited EIA-485 serial interface (formerly referred to as RS-485). This communica-
tion, to include the wiring, is supervised by the control panel's CPU. Loss of communication
resultsin"SystemTrouble" and "ModuleFailure"indications attheCPU. Power fortheAFM
mustbepower-limitedandisprovidedviaaseparatepowerloopfromthecontrolpanelwhich
is inherently supervised (loss of power also results in a communication failure at the control
panel). No End-Of-Line Resistor needs to be installed because the EIA-485 circuit is
internally terminated on the annunciator.
Wiring Specifications
The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion from the
controlpaneltotheAFM. Themaximumwiringdistancebetweenthepaneland annunciator
is 6000 feet. The wiring size should be a 18 AWG to 14 AWG twisted-pair
cable having a Characteristic Impedance of approxi-
mately 120 ohms. Limit the total wire resistance to 100
ohmsontheEIA-485circuit,andto10ohmsonthepower
runtotheannunciator. Donotruncableadjacentto,orinthesame
conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells
or horns, audio circuits above 25 voltsRMS, motor control circuits, or SCR power circuits.
Twisted-shielded wiring should be used for EIA-485 circuits that are not contained entirely
in conduit.
Functions
Thefirealarmcontrolpanelautomaticallyassignsannunciatorpointstothemodules directly
totherightoftheCPUandoutward.Therefore,wheninstallingthesystemmodules,Initiating
ZoneModules(IZ-4,IZ-8,orIZM-8)shouldbeinstalledinribboncablepositionsimmediately
next to the CPU (and outward) to permit full annunciation of initiating circuits.
AFM
Annunciator
Two-wire EIA-485
Circuit
(Maximum of 6000 feet )
power-limited
Power for AFM
(18 to 14 AWG )
power-limited
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
6
AFM-16AT
(H = 8-3/8" W = 4-3/8" D = 1-3/8")
The Annunciator Fixed Module-16AT con-
tains 16 red alarm and 16 yellow trouble
LEDs, 16 momentary touch-pad switches,
asystemtroubleLED,anONLINE/POWER
LED, and a local piezo sounder with a
silence/acknowledge switch for audible in-
dication of alarm and trouble conditions.
The AFM-16AT can be mounted in two
types of backboxes - the ABS-1 or ABF-1.
AFM-32A
(H = 8-3/8" W = 4-3/8" D = 1-3/8")
TheAnnunciator FixedModule-32A con-
tains 32 red alarm LEDs, a System
TroubleLED,anONLINE/POWER LED,
andapiezosounderwithaLocalSilence/
Acknowledge switch for audible indica-
tionof alarmand troubleconditions. The
AFM-32Acanbemountedintwotypesof
backboxes - the ABS-1 or ABF-1.
Section Two: Inventory
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 7
ABF-1
(H = 9-15/16" W = 4-5/8" D = 2-1/2")
The Annunciator Flush Box-1 provides for the
remote mounting of the AFM annunciator in a
flush-mount enclosure . The ABF-1 includes a
trimplate(height=11" width=6-1/4"),mounting
hardware, and an adhesive-backed annuncia-
tor label.
Annunciator Label
ABS-1
(H = 8-1/2" W = 4-1/2" D = 1-3/8")
The Annunciator Surface Box-1 provides for
the remote mounting of the AFM annunciator
in a surface-mount enclosure. Knockouts are
providedforuse with1-2" conduit. Theannun-
ciator mounts directly to the ABS-1 without a
dress plate.
Note: The ABS-1 will not support the installa-
tion of the AKS-1 or APJ-1.
AKS-1
The Annunciator Key
Switch provides access
security for the control
switches on the AFM-
16AT. Includes a key,
mounting hardware and an adhesive-
backed annunciator label.
The AKS-1
canonlybeemployedwithaflush-mount
type backbox.
APJ-1
TheAnnunciatorPhoneJackpro-
vides a fireman's telephone jack
that mounts to the ABF-1 dress
plate. Includes mounting hard-
ware and an adhesive-backed
annunciator label.
The APJ-1 can only be
employed with a flush-mount type backbox.
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
8
AFM Installation Summary
RuntheEIA-485andpowercircuitsoutto the location oftheannunciator.
Select an appropriate knockout on the backbox and mount the backbox.
Connect the backbox to a solid ground, such as a properly grounded
metallic cold water pipe.
Draw all annunciator and power wiring into the enclosure. Do not
terminate the shield (if employed) to the backbox (see Figure 3-2).
Insert the custom display labels into the annunciator (see Figure 3-3).
As appropriate, cut jumper options on the annunciator as outlined in
Figure 3-4.
ABF-1 Only -
Turn the ABF-1 Dress Plate face down on a surface with
the screw studs facing up. Position the AFM-16AT over the screw studs
andsecuretothedressplatewiththetwonutsandlockwashersprovided
(see Figure 3-5).
ABF-1 Only -
Remove the backing from the Annunciator Label and affix
to the dress plate as illustrated in Figure 3-6.
ABF-1 Only -
If employing an Annunciator Key Switch (AKS-1), mount
the switch to the dress plate. Plug the switch leads to Connector J4 on
the Annunciator (see Figure 3-7).
ABF-1 Only -
If employing an Annunciator Phone Jack (APJ-1), mount
the jack to the ABF-1 Dress Plate. Connect the telephone circuit to the
leads of the APJ-1(see Figure 3-7).
Connect power-limited EIA-485 circuit and power-limited power wiring to
the Annunciator Terminal Blocks as illustrated in Figure 3-8.
Placethe annunciator/dress plateassemblyinto the backboxandsecure
with two screws.
Connect the EIA-485 circuit to the CPU as illustrated in Figure 3-9.
Connect the power loop for the annunciator to the Main Power Supply as
illustrated in Figure 3-10.
Installation of the AFM Annunciator is complete. Program the AFM into
the respective CPU and full test the system.
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Section Three: Installation
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 9
Figure 3-2: Terminating the Shield
The EIA-485 circuit should be wired using a twisted-pair cable having a Characteristic
Impedanceofapproximately120 ohms. Do notruncable adjacentto,or inthesame conduit
as,120-voltAC service, noisyelectrical circuitsthat are poweringmechanical bellsor horns,
audio circuits above 25 volts (RMS), motor control circuits, or SCR power circuits. Twisted-
shieldedwiring shouldbe usedforEIA-485 circuitsthat arenotcontained entirelyinconduit.
Donotallowtheshieldtoenterortouchtheannunciatorenclosure,asillustratedabove. The
shield should only be terminated at the fire alarm control panel. Wire-nut multiple shields
together outside of the cabinet.
Figure 3-1:
Mounting the Backbox
Select a knockout on the backbox. Mount the
backbox and draw all annunciator, power, and
telephone wiring (if employing an APJ-1) into the
enclosure. Connectthebackboxtoasolidground
such as a metallic cold water pipe.
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
10
AFM-16AT Slide-In Labels
Slide-in labels for the AFM-16AT Annunciator are contained
onthefollowingpages. TwolabelsarerequiredfortheAFM–
16AT - one for the left-hand side and one for the right-hand
side of the faceplate. Each label has a distinctive format.
Three types of labels are offered:
Set A: Factory-printed zone labels:
These provide labels for alarm zones 1 through 16.
Set B: Factory-printed system/zone labels:
These provide labels for Acknowledge, Signal Silence, Sys-
temReset,andotherCPUcontrolfunctions,aswellasalarm
zones 1 through 8.
Set C: Custom User Labels:
These blank labels can be customized by the user. If
information is to be typed onto these labels, they should be
reproducedonacopymachinesothattheentirepagecanbe
insertedintoatypewriter. Twosetsofcustomuserlabelsare
provided so that one set may be used as a work sheet.
Effective Window Size
The size of the visible portion of an AFM-16AT label window
is9/16" highby 1"across. Using apitch of10 charactersper
inch at six lines per inch, up to three lines of 10 characters
each may be typed within this window space. If information
is to be typed onto these labels, make a reproduction on a
copy machine to use as a practice copy.
1"
9/16"
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 11
AFM-32A Slide-In Labels
Slide-in labels for the AFM-32A Annunciator are contained
onthefollowingpages. TwolabelsarerequiredfortheAFM–
32A - one for the left-hand side and one for the right-hand
side of the faceplate. Each label has a distinctive format.
Three types of labels are offered:
Set D: Factory-printed zone labels:
These provide labels for alarm zones 1 through 32.
Set E: Factory-printed system/zone labels:
These provide labels for System Alarm, Supervisory condi-
tion, and alarm zones 1 through 24.
Set F: Custom User Labels:
These blank labels can be customized by the user. If
information is to be typed onto these labels, they should be
reproducedonacopymachinesothattheentirepagecanbe
inserted into a typewriter.
Effective Window Size
The size of the visible portion of an AFM-32A label window
is1/2"highby1-3/8"across. Ifinformationistobetypedonto
these labels, make a reproduction on a copy machine to use
as a practice copy.
1-3/8"
1/2"
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
12
AKS-1 Connector
(shown here for reference
only)
Jumper JP3 (orange)
Cut this jumper to enable the Local Si-
lence/Acknowledge switch and all point
controlswitches(ontheAFM-16AT). This
will allow the execution of system control
functions,suchasACKNOWLEDGEand
RESET, from the AFM-16AT.
Note: Jumper JP1 must also be cut to
execute these functions.
Figure 3-4: Annunciator Jumper Options
Jumper JP2 (red)
Cutthisjumpertoenablethelocalpiezoto
sound during alarm, trouble, or supervi-
sory activity within the system.
Jumper JP1 (brown)
Cut this jumper to display the
status of the eight CPU func-
tionsinthefirsteightpointson
the annunciator.
Removethecenterpagesofthismanual.If
using the custom user display labels, type
the appropriate information on the labels.
Carefullycutout the labelsand insertthem
intothe AFMbyslippingthemintothelabel
slots on the back side of the annunciator
face plate.
Note: Toensurethebestfit,cutdirectly
along the dotted line surrounding each
label.
Figure 3-3: Inserting Display Labels
AFM-16AT
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 13
Figure 3-5: Mounting the Dress Plate
Position the annunciator over the screw studs on the
dressplate andsecurewith twonutsand lockwashers
provided.
ABF-1
Dress Plate
AFM
Figure 3-6: Applying the Annunciator Label
Remove backing from adhesive-backed Annunciator Label and
affix the label to the bottom of the ABF-1 Dress Plate as illustrated.
Note: If an AKS-1 is to be installed, use the label supplied with the
appropriate kit and discard the other label.
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
14
Figure 3-7:
Installing AFM Options
If employing an Annunciator Key Switch
(AKS-1),mountthe switch tothe ABF-1Dress
Plate. Plug the switch leads from the AKS-1 into
Connector J4 on the annunciator.
Telephone
Circuit (+)
(red wire)
Telephone
Circuit (-)
(black wire)
Telephone
Circuit (-)
(black wire)
Telephone
Circuit (+)
(red wire)
If employing an Annunciator Phone Jack
(APJ-1),mountthejacktotheABF-1Dress
Plate. Connect the telephone circuit to the
leads of the APJ-1 as shown below.
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 15
Figure 3-8: AFM Field Connections
Connect the annunciator and power wiring to the terminal blocks on the back of the AFM as
illustrated below.
Caution! Failure to observe proper
polarity on these connections may
result in damage to the annunciator.
TB2
TB1
2
1
2
1
24 VDC ( - )
24 VDC (+)
EIA-485 and power
mustbepower-limited
EIA-485 ( - )
EIA-485 (+)
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
16
Installation Requirements
TheEIA-485 circuitthat drivesthe AFM mustbe connectedto theCPU asillustrated below.
Connect the EIA-485 (+) and (-) lines to the CPU terminals. On a System 5000, ensure that
the CPU U4 ROM software is Part Number 73085 or greater.
Figure 3-9: Connecting the EIA-485 Loop
EIA-485 (-)
Supervised and Power-limited
Supervised and Power-limited
EIA-485 (-)
(+) EIA-485
(+) EIA-485
CPU-500
FIRE
ALARM
SYSTEM
5000
AC
POWER
SYSTEM
ALARM
SUPERVISORY
SIGNAL
SYSTEM
J11
MODULE
TYPE
LAMPS
SWITCH
17 18 19 209 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8
CPU-5000
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 17
Figure 3-10: Main Power Supply Connections
The AFM annunciator can be powered by an MPS-24A or an MPS-24B. This power run
to the annunciator
need not contain a Power Supervision Relay since loss of power is
inherently supervised through communication loss.
MPS-24A Main Power Supply :
Connect the power run for the AFM to MPS-24A TB3 Terminals 1 (+) and 2 (-) (1 amp max)
or Terminals 3 (+) and 4 (-) (3 amps max). The total amount of current drawn from these
terminals cannot exceed the above ratings in standby or in alarm.
24 VDC Power (+)
to AFM TB1 Terminal #1
MPS-24A
MPS-24B Main Power Supply:
ConnectthepowerrunfortheAFMtoMPS-24B TB2Terminals1(+)and2(-). Nomorethan
200 mA current can be drawn from these terminals in standby or alarm.
24 VDC Power (+)
to AFM TB1 Terminal #1 ( - ) Common
to AFM TB1 Terminal #2
( - ) Common
to AFM TB1 Terminal #2
MPS-24B
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
18
Section Four:
Operation
If the Annunciator loses communication with the
control panel, all the yellow LEDs will flash.
16 Annunciator Points
Acknowledge
Switch This switch serves two purposes:
1) When pressed, it lights all the LEDs on the AFM
(except the On Line LED) and sounds the piezo for
as long as the switch is held down.
2) It acknowledges all status changes for the AFM.
Flashing LEDs will latch on solid and the piezo will
be silenced.
On Line LED
This green indicator flashes during communication
with the control panel.
System Trouble LED
This yellow indicator lights for all trouble conditions
in the system (not just for those points or zones
mapped to the annunciator).
Control Switch
FunctionsasalocalLampTestforthetwo
LEDs dedicated to this point.
If not inhibited, the control switches can
also be used to execute the system func-
tions of ACKNOWLEDGE, SIGNAL SI-
LENCE, and SYSTEM RESET, and con-
trol system outputs (see Table 4-1).
Red LED
Yellow LED
Figure 4-1: AFM-16AT Operation
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1 19
This switch serves two purposes:
1) When pressed, it lights all the LEDs on the AFM
(except the On Line LED) and sounds the piezo for
as long as the switch is held down.
2) It acknowledges all status changes for the AFM.
Flashing LEDs will latch on solid and the piezo will
be silenced.
On Line LED
This green indicator flashes during
communication with the control panel.
System Trouble LED
Thisyellow indicator lights forall trouble conditions
in the system (not just for those points or zones
mapped to the annunciator).
Local Silence/Acknowledge
Switch
If the Annunciator loses communication with the control
panel, the yellow System Trouble LED will flash.
32 Annunciator Points
Figure 4-2: AFM-32A Operation
Red Alarm LED
www.PDF-Zoo.com
firealarmresources.com

Document 15048 Rev. D1 07/16/97 P/N 15048:D1
20
Annunciator Operation
Annunciator points "track" or follow those control panel points they are programmed to
annunciate; they do not latch. The table below outlines the annunciation of various circuits
and functions. Note: Control Switches marked "not used" will still function as local LAMP
TEST or local ACKNOWLEDGE switches for their respective points.
Circuit Type
ANNUNCIATOR
POINT # 1
ANNUNCIATOR
POINT # 2
ANNUNCIATOR
POINT # 3
ANNUNCIATOR
POINT # 4
ANNUNCIATOR
POINT # 5
ANNUNCIATOR
POINT # 6
ANNUNCIATOR
POINT # 7
ANNUNCIATOR
POINT # 8
IZ-4, IZ-8, IZM-8
IC-4, ICM-4, ICE-4
CR-4, CRM-4, CRE-4
TC-2, TC-4 TCM-2,
TCM-4
AIM-200 zone
AFM-32A
Only
AFM-16AT
Table 4-1: Annunciator Point Functions
2
1If Jumper JP1 has not been cut, the eight CPU functions will not be active.
2These control switches will function only if Jumper JP3 has been cut.
3These Status LEDs are active only when the CPU has been programmed for "Output Status."
4These control switches require that the CPU be programmed for "Output Control."
5TheAFMannunciatestheeightAIM-200softwarezonesonly,noteachaddressablepointontheAIM.
6If an IZ-4, IZ-8 or IZM-8 circuit has been programmed as a supervisory point,
both
the red and yellow
LEDs will be illuminated for a supervisory condition. Illumination of the yellow LED alone indicates a
trouble condition (open circuit) on a supervisory zone.
5
3
6
3
3
4
4
4
C
P
U 1
M
O
D
U
L
E
S
Yellow LED
Indicates
System Trouble
Indicates that signals
have been silenced
not used
Indicates
Supervisory condition
Indicates trouble
status of circuit
Indicates trouble
status of circuit
Indicates trouble
status of circuit
Indicates
Module Trouble,
Power Failure or
Disabled Circuit(s)
Indicates trouble
status of circuit
Indicates trouble
status of circuit
Indicates trouble
status of relay
Indicates trouble
status of relay
Indicates trouble
status of circuit
Control Switch
Functions as an
ACKNOWLEDGE
Functions as a
SIGNAL SILENCE
Functions as a
SYSTEM RESET
not used
Controls Indicating
Circuit 1
Controls Indicating
Circuit 2
Controls
Remote Signalling
Municipal Tie
Controls
Alarm Relay
not used
Control
Indicating Circuit
Controls
Relay
Remote Switch
Functions
not used
Red LED
Indicates
System Alarm
not used
not used
not used
Indicates that Indicating
Circuit 1 has been activated
Indicates that Indicating
Circuit 2 has been activated
Indicates that the Remote
Signalling Municipal Tie
has been activated
Indicates that
the Alarm Relay
has been
activated
Indicates alarm
status of circuit
Indicates Activation
Indicates Activation
Indicates Activation
Indicates alarm
status of circuit
www.PDF-Zoo.com
firealarmresources.com
This manual suits for next models
1
Table of contents
Other Pittway Security System manuals

Pittway
Pittway Notifier RPT-485W User manual

Pittway
Pittway Notifier Inertia AFP-300 Assembly instructions

Pittway
Pittway Notifier AM2020 User manual

Pittway
Pittway System Sensor SpectrAlert DS2475WAR User manual

Pittway
Pittway SYSTEM SENSOR SpectrAlert H12 User manual

Pittway
Pittway SYSTEM SENSOR SPECTRAlert SC2415W User manual