Pittway Notifier RPT-485W User manual

12 Clintonville Road
Northford, CT 06472
203/484-7161
FAX:203/484-7118
The RPT-485W/RPT-485WF
EIA-485 Annunciator Loop Repeater
forTwisted Pair Wiring/Fiber Optic Cable
Document 15640
08/13/97 Revision: B1
15640:B1 ECN 97-294
www.PDF-Zoo.com

WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72-
1993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49OC/32-120OF
and at a relative humidity of 85% RH (non-condensing) at 30O C/86OF.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27OC/60-80O
F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
Fire Alarm System Limitations
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further-
more, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
FCC Warning
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.
Technical Publishing Document PRECAULG.P65 12/31/96
www.PDF-Zoo.com

3
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Contents
Section One: Introduction ..................................................................................... 4
Isolated System with Remote Supplies ............................................. 4
Section Two: RPT-485W ........................................................................................ 5
Parallel/Series Connection of RPT-485Ws ....................................... 6
Section Three: RPT-485WF ...................................................................................... 7
Parallel/Series Connection of RPT-485WFs ..................................... 8
Section Four: Installation ....................................................................................... 9
Mounting ........................................................................................... 9
Wiring the RPT-485W ..................................................................... 11
Wiring the RPT-485WF ................................................................... 12
Connections Between the RPT-485 and EIA-485 Devices ............. 13
Section Five: Power Supply Specifications ....................................................... 14
Main FACP Wiring for Power .......................................................... 15
Power/Reference Wiring for a Remote RPT-485 ............................ 16
Power/Reference Wiring for Multiple RPT-485s.............................. 17
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
4
Figure 1-1: Isolated System with Remote Supplies
The RPT-485W/RPT-485WF ACS annunciator loop repeaters are designed to boost the EIA-485 annunciator
signalfromthefirealarmcontrolpanel(FACP).TheRPT-485Wisarepeaterwhichsupportstwistedpairwireonly;
the RPT-485WF supports fiber optic cable between two repeaters. Any Notifier FACP that has an EIA-485
annunciator loop can employ RPT-485s. The boosted branch can have a maximum of 32 EIA-485 devices on it.
TheseEIA-485devicesincludeAMG-1,AMG-E,UZC-256,NIB-96,ACM-16AT,allannunciatorsandotherRPT-
485s. Note there is a maximum of two RPT-485s that can be connected in series.
Thesource EIA-485 circuitina NotifierControlPanelwill supportupto 32 devicesandup to32addressesalong
a 6000 ft. (maximum) loop. Each RPT-485 can be employed to boost the distance of the circuit and/or add up to
32 additional EIA-485 devices (but not addresses) in the system. Figure 1.1 illustrates an electrically isolated
system.ElectricalisolationismaintainedbyemployingseparatepowersuppliesforthesourceandboostedEIA-
485 loops.
Toremainisolated,connectionsbetweeneachEIA-485devicemusthaveareferencewirefromthepowersupply
providingpowertoeachdevice.Thisreferencewirereducestheamountofnoiseonthecommunicationwire.Both
thesourceandboostedEIA-485loopconnectionterminalsareisolated fromeach other.These wiresconnect to
REF A on TB1 and REF B on TB2. In order to maintain electrical isolation between separate system power
supplies, REF A and REF B must be connected using a separate wire.
Thesourceand boosted EIA-485 loops are isolated from each other, as well asfromthe RPT-485 power supply
terminals.Thisimportant feature eliminates the need to interconnect power supplies. This feature alsoprovides
aneasiermethodoflocatinggroundfaultconditionssinceitallowsforseparategroundfaultzones.Theisolation
featuredoesnoteliminatetheneedforreferenceconnectionsbetweennodesoneachisolatedloop.Theisolation
feature will maintain isolation when networking slaves on an EIA-485 loop with the use of a NIB-96.
Section One:
Introduction
www.PDF-Zoo.com

5
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Purpose
The RPT-485W is an ACS annunciator loop repeater for twisted pair wiring which extends the loop length and
node capacity of the EIA-485 Annunciator Loop. The RPT-485W electrically isolates the EIA-485 Annunciator
Loop.
Features
4 Extends EIA-485 distances in 4000 ft. increments.
4Allows additional boosted EIA-485 loops.
4Each boosted loop increases annunciator node capacity by 32.
4EIA-485 branch connections are electrically isolated to prevent ground fault detection problems.
4Two LEDs indicate data reception.
4Removable terminal blocks.
4A variety of mounting options.
SectionTwo:
The RPT-485W
Figure 2-1: The RPT-485W
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
6
Two RPT-485Ws In Series Configuration
In order to further extend the EIA-485 loop, 2 RPT-485s can be arranged in a series connection. Between the
two RPT-485s, 32 EIA-485 devices, 32 RPT-485s, or a combination of both can be hung from the loop. The
source EIA-485 loop can extend up to 6,000 feet and have 32 EIA-485 devices (including the RPT-485s)
hung from it. An example of wiring an EIA-485 loop using RPT-485Ws is pictured in Figure 2-2. Notice that
both ends of every EIA-485 loop must be terminated by a 120 ohm resistor and there cannot be more than 2
RPT-485s connected in series.
Figure 2-2: Parallel/Series Connection of RPT-485Ws
www.PDF-Zoo.com

7
Document 15640 Rev B1 08/13/97 P/N 15640:B1
SectionThree:
RPT-485WF
*ST is a registered trademark of AT&T Lightguide Cable Connectors.
Figure 3-1: RPT-485WF
Purpose
The RPT-485WF is used to provide fiber optic capability, which may be necessary in environments exposed
to strong electromagnetic interference such as power plants and areas with frequent lightning or in areas
where a high level of security is required. The RPT-485WF optically isolates the EIA-485 annunciator loop
eliminating ground loops and noise.
Features
4Extends the EIA-485 loop up to 10,000 ft with a 10dB maximum guaranteed (15dB typically achievable)
attentuation for 820-850 nM fiber optic cable.
4Allows additional boosted EIA-485 loops.
4Each boosted loop increases annunciator node capacity by 32.
4Optically isolated.
4Two LEDs indicate data reception.
4Removable terminal blocks.
4A variety of mounting options.
Fiber Optic Cable Requirements
Dual Fiber 62.5/125um, with ST* Bayonett style connectors.
Note: Use the protective caps to protect the cable connections from damage and dirt accumulation when the
cable is not connected.
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
8
Wiring RPT-485WFs
TheRPT-485WFs mustbeusedinpairs. ThesourceEIA-485loopcan extendupto6,000feet andhave32EIA-
485 devices (including the RPT-485s) hung from it. An example of wiring an EIA-485 loop using RPT-485WFs
is pictured in Figure 3-2. Notice that both ends of every loop must be terminated by a 120 ohm resistor.
Figure 3-2: Parallel/Series Connections of the RPT-485WF
www.PDF-Zoo.com

9
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Section Four:
Installation
CHS-4
Inner Position (RPT-485W ONLY):
Screw (2) 6-32 standoffs
onto PEM studs in chassis. Screw (2) 4-40 screws into top
holes of board and attach (2) 4-40 standoffs. Place tab on
bottom of board into slot. Screw boards into 6-32 standoffs
with (2) 6-32 screws (refer to Figure A). The top standoffs
should just rest on the back of the chassis.
Outer Position: The board's components must be facing inward!
Slip the tab of the board into the top slot
on CHS-4 with the components facing the back of the chassis. Rest the top of the board on the mounting tabs
at the top of the CHS-4. Screw the board on using (2) 4-40 screws.
CHS-4L
Inner position only:
Screw (2) 4-40 standoffs onto the top row of
PEM studs on the CHS-4L. Slide tab of board into inner slot
of CHS-4L and rest on standoffs. Use (2) 4-40 screws to fix
the board onto the chassis (refer to Figure B).
CHS-4
Installation
The RPT-485W/RPT-485WF board can be mounted in a listed CHS-4, CHS-4L, or an ABS-8R (remote).
When mounting on a CHS-4L, use the inner position. When the RPT-485WF is mounted on the CHS-4 and
CHS-4L, adequate clearance above the board is required. Outer position mounting on the CHS-4 is also
possible but the board has to be mounted with components facing inward. For the RPT-485WF, using the
ABS-8R, use the upper center knockout for the fiber optic cable's entry/exit.
CAB-3 Mounting
CHS-4L
6-32 screws
Figure A
4-40 screws
Figure B
4-40 screws
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
10
ABS-8R Mounting
Before mounting the ABS-8R, determine which knockouts are needed
to wire the RPT-485.
If you are using an RPT-485WF, you must use
the center top knockout for the fiber optic cable.
Remove knockouts.
Mount the ABS-8R. Place the RPT-485 in the box and afix into PEM
standoffs using (4) 4-40 screws (refer to Figure C). Draw appropriate
wiring in through knockouts.
ABS-8R
Figure C
4-40 screws
www.PDF-Zoo.com

11
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Figure 4-1: Wiring the RPT-485W
NOTE: For EIA-485 device terminals connections, see Table 4-1.
Use a power
limited supply
Use a power
limited supply
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
12
NOTE: For EIA-485 device terminal connection, see Table 4-1.
Figure 4-2: Wiring the RPT-485WF
Use a power
limited supply
Use a power
limited supply
www.PDF-Zoo.com

13
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Table 4-1: Connections between the RPT-485 and EIA-485 Devices
EIA-485 IN EIA-485 OUT
REF
(+) (-) (+) (-)
ACS Series
ACM-8R
LDM Series
SCS/SCE
TB2-1 TB2-4 TB2-2 TB2-3 TB1-4/1-5
AFM-16A TB2-1 TB2-2 TB2-1 TB2-2 TB1-1
AFM-16AT
AFM-32A TB2-1 TB2-2 TB2-1 TB2-2 TB1-2
AMG-1
AMG-E P3-6 P3-4 P3-5 P3-3 P4-6
LCD-80 P2-2 P2-4 P2-1 P2-3 P1-4/1-5
NIB-96 P4-5 P4-3 P4-6 P4-4 Power Supply
Batt Neg
UZC-256 TB2-3 TB2-5 TB2-4 TB2-6 TB2-2/2-1
NOTE: For additional information, reference the respective manuals listed in Table 4-2.
The ACS Series Annunciators 15842
The ACM-8R Annunciator 15342
The LDM Series Annunciators 15885
The SCS/SCE Smoke Control Station 15657
The AFM-16A Annunciator 15207
The AFM-16/AFM-32A Annunciators 15048
The AMG-1/AMG-E (VAM-2020) 15889
The LCD-80 Liquid Crystal Display 15037
The NIB-96 Network Interface Board 15666
The UZC-256 Universal Zone Coder 15216
Table 4-2: EIA-485 Device Manuals
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
14
Section Five:
Power Supply Specifications
A power limited power supply, listed for Fire Protection Signaling, (may be located remotely) with both
Primary and Secondary power, must be used for Fire Protective Signaling Applications.
Operating Voltage Range
18-28 VDC
Maximum current draw; (All states)
RPT-485W 0.047 A
RPT-485WF 0.049 A
The maximum allowed voltage drop along the supply loop is limited by the minimum input voltage (18VDC)
measured across TB3 (+24V, power supply common) of the RPT-485W/WF.
Calculating the maximum wiring resistance (Rmax) permitted for the +24V power supply connection.
Formula:
For a Listed Power Supply (listed for Fire Protective Signaling use) with battery supplied secondary power,
the lowest supply voltage possible is 20.4V.
Example: MPS-24A with batteries
RPT-485W: Rmax = 20.4V-18V = 51 Ohm
0.047A
RPT-485WF: Rmax = 20.4V-18V = 49 Ohm
0.049A
Rmax= (Lowest Power Supply Voltage Possible) - (Minimum Operating Voltage of RPT-485W/WF )
Maximum Current Required by RPT-485W/WF
www.PDF-Zoo.com

15
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Table 5-2: EIA-485 Source Manual
AM2020/AFP1010 Installation Manual 15335
System 5000 Installation 15583
System 2500 Manual 15969
System 500 15019
AFP-200 15511
ID-200 (U.K. only) 15633
MPS-24A MPS-24B
RPT TB3 (+) TB3-1 TB2-1
RPT TB3(-) TB3-2 TB2-2
NOTES:
1) For connections between the RPT-485 and EIA-485
devices, refer to Table 4-1.
2) For connections between the RPT-485 and EIA-485
sources, refer to Table 5-2.
3) Most EIA-485 devices and sources manufactured by
Notifier are not isolated. When making reference
connections to non-isolated EIA-485 devices powered
by separate power supplies, care must be taken to
ensure that only one power supply has Earth Fault
detection enabled within a group of power supplies
sharing the same reference connection.
Figure 5-1: Main FACP Wiring for Power
All EIA-485 loops in
this Figure share a
common reference
and are not isolated
from each other
(see Note 3).
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
16
Figure 5-2: Power and Reference wiring for a Remote RPT-485
NOTES:
1) A remote CAB-3 containing an RPT-485 must be connected to the SLC loop via an MMX and MPS-TR for
detection of troubles. Refer to the MPS-TR Product Installation Drawing, Document 15331 for specific
terminal connections.
2) Most EIA-485 devices and sources manufactured by Notifier are not isolated. When making reference
connections to non-isolated EIA-485 devices powered by separate power supplies, care must be taken to
ensure that only one power supply has Earth Fault detection enabled within a group of power supplies
sharing the same reference connection.
Earth Fault
Disabled
Isolated
www.PDF-Zoo.com

17
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Figure 5-3: Power/Reference Wiring for Multiple RPT-485s
NOTE: Most EIA-485 devices and sources manufactured by Notifier are not isolated. When making refer-
ence connections to non-isolated EIA-485 devices powered by separate power supplies, care must be taken
to ensure that only one power supply has Earth Fault detection enabled within a group of power supplies
sharing the same reference connection.
All EIA-485 loops in this
Figure are isolated from
each other.
www.PDF-Zoo.com

Document 15640 Rev B1 08/13/97 P/N 15640:B1
18
Notes
www.PDF-Zoo.com

19
Document 15640 Rev B1 08/13/97 P/N 15640:B1
Notes
www.PDF-Zoo.com

NOTIFIER®warrantsitsproductstobe freefromdefectsinmaterials andworkmanship
for eighteen (18) monthsfromthedate of manufacture, under normaluse and service.
Productsaredatestampedattimeofmanufacture. The sole and exclusiveobligation
of NOTIFIER®is to repair or replace, at its option, free of charge for parts and labor,
anypartwhichisdefective inmaterialsorworkmanship undernormal use andservice.
For products not under NOTIFIER®manufacturing date-stamp control, the warranty
is eighteen (18) months from date of original purchase by NOTIFIER®'s distributor
unless the installation instructions or catalog sets forth a shorter period, in which
case the shorter period shall apply. This warranty is void if the product is altered,
repairedorservicedbyanyone other thanNOTIFIER®or its authorized distributorsor
if there is a failure to maintain the products and systems in which they operate in a
properand workablemanner. Incaseof defect,securea ReturnMaterialAuthorization
form from ourcustomerservicedepartment. Returnproduct,transportation prepaid,
to NOTIFIER®, 12 Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIER®with respect to its
products. NOTIFIER®does not represent that its products will prevent any loss by
fire or otherwise, or that its products will in all cases provide the protection for which
theyare installed or intended. Buyeracknowledges that NOTIFIER®is not an insurer
and assumes no risk for loss or damages or the cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.
NOTIFIER®GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIER®BE LIABLEFORANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
NOTIFIER®PRODUCTS. FURTHERMORE, NOTIFIER®SHALL NOT BE LIABLE
FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE INTHE COURSE
OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF
ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by
NOTIFIER®. Noincreaseoralteration,writtenorverbal,oftheobligationofthiswarranty
is authorized.
"NOTIFIER" is a registered trademark.
Limited Warranty
12 Clintonville Road, Northford, CT 06472
Phone: (203) 484-7161
FAX: (203) 484-7118
Technical Publishing Document WARNBG-C.P65 04/02/96
www.PDF-Zoo.com
This manual suits for next models
1
Table of contents
Other Pittway Security System manuals

Pittway
Pittway SYSTEM SENSOR SpectrAlert H12 User manual

Pittway
Pittway SYSTEM SENSOR SPECTRAlert SC2415W User manual

Pittway
Pittway NOTIFIER AFM-16AT User manual

Pittway
Pittway Notifier AM2020 User manual

Pittway
Pittway Notifier Inertia AFP-300 Assembly instructions

Pittway
Pittway System Sensor SpectrAlert DS2475WAR User manual