Polypipe POLYPLUMB PB1ZP User manual

Publication: FHC1
Under Floor Central Heating
Programmable Control Pack
Floor Heating Controls
PROGRAMMABLE CONTROL PACK
www.polyplumb.co.uk www.ufch.com
February, 2007

The Programmable Zone Control Packs allow all
rooms to be individually controlled for both time
and temperature.
When using The Single Zone Pack (PB1ZP) no
Actuators are required, however actuators
(PB00401) will be required for all other packs.
A Zone Valve installed on the flow to the manifold
is always required.
The Master Unit provides wiring connections for
The Boiler (incl. Volt Free), Zone Valve, UFH pump,
Valve actuators and The Programmable Room Stat.
The Power Supply to the unit must come from the
230v - 50Hz Supply from main heating isolator.
The Programmable room stat can be installed
outside wet areas and connected to the Wet area
sensor (PB23020) where this is required.
FLOOR HEATING CONTROLS
HOT & COLD PLUMBING & HEATING SYSTEM
Programmable
Control Pack
Master
Connection Unit
Slave Unit
Programmable Room Thermostat
Programmable
Room Thermostat
Overview
The Programmable Room Thermostat controls and
regulates the room temperature. The thermostats
should be positioned 1·2m from the floor and away
from other heat producing appliances.
Note
Programmable Room Thermostats differ in operation
from conventional Room Controls as they not only set
a maximum room temperature but also set a
minimum temperature that the room temperature is
allowed to fall to.
This is particularly important when controlling floor
heating systems as the heating response is slower
than that of conventional radiators.
Features
• 7 Day Programme
• 5 built in and 2 User Defined Programmes
• Holiday Function
• Frost protection programme
• Battery replacement without loss of programme
Technical Characteristics
Pack Code 4 Zone 4 Zone Programmable
Master Slave Room Thermostat
PB1ZP 1 1
PB4ZP 1 4
PB6ZP 1 1 6
PB8ZP 1 1 8
Measuring Accuracy 0·1°C
Operating Temperature 0°C - 50°C
Ambient Temperature range 5°C - 37°C in steps of 0·5°C
Characteristics of different Integral proportional band or
regulations Static differential
Electrical Protection Class II – IP30
Feeding & Autonomy 3 batteries AA LR06 1·5 V/> 2 years
(alkaline batteries)
Output Relay 5A 250V ac

Individual Room Wiring Diagram
2 Links fitted to board as standard
1. Time Switch 2. Zone Valve
The Time Switch link should NOT be removed
The Zone Valve link SHOULD be removed on installation of a
Zone Valve
Boiler Connections
1. Multiple Zone Valves on System
When a System has zone valves in
addition to the one connected to this
unit, e.g. other UFH manifolds, hot
water, etc., link the incoming live to
the volt free on as shown to prevent
back feed. (diagram 1)
2. One Zone Valve on System
Where the zone valve connected to
the unit is the only zone valve on the
system connection can be made
directly to the boiler. (diagram 2)
Diagram 1
Diagram 2
▼
Boiler
Connection
detail
230v Supply from
Main Heating
Isolator
Programmable Room Stat.
Common
Demand

Mode OCCUPIED
Use this function to set your installation in occupied mode.
Use the keys and to adjust the occupied temperature.
The «occupied» temperature of the thermostat is unlimitedly
maintained. Push the for an instantaneous adjustment
display (default setting: 21°C).
Mode AUTO
The thermostat follows the chosen programme in
accordance with the actual hour. By using the and
keys, you can adapt the temperature until the next change
within the programme. The symbol is displayed.
Mode SETBACK TEMPERATURE
Using this function to put your installation in “setback
temperature mode”. Use the and keys to adjust
the setback temperature. The «setback» temperature of the
thermostat is unlimitedly maintained. Push the for an
instantaneous adjustment display (default setting: 17°C)
Mode ANTI-FREEZE
Use this function if you want to protect your installation
against frost. Use the and keys to adjust the anti-
freeze temperature. The «Anti-freeze» temperature of the
thermostat is unlimitedly maintained. Push the for an
instantaneous adjustment display (default setting: 6°C)
Mode CLOCK ADJUSTMENT
Push : the hour blinks, then you can adjust the hour by
using the and keys, Press the key again: the
day of the week blinks, you can choose the day now by
using the and . For example: 1 = Monday
Push the key to Valid your adjustments.
Mode OFF
Use this function to switch off your installation. The programme’s
version is displayed during 5 seconds before the thermostat is
definitely switched off. Press 1 of the keys to restart the thermostat.
Mode PROGRAMME
Push the key: the number of the current programme blinks.
– You can choose a programme now by using and .
(default setting: P1)
– By pressing the key, you can display the programme
in case of a built-in programme (P1 to P5) or you can
create or adapt a user’s programme (U1 and U2).
– The programme operates between the temperatures
«comfort» and «reduced».
Built-in programmes descriptions:
P1: Morning, evening and weekend
P2: Morning, noon, evening and weekend
P3: 7h - 19h (office) evening and weekend
P4: Weekend (secondary house)
P5: 8h - 19h, Saturday (shop)
KEYBOARD LOCK AND UNLOCK FUNCTION
In , , , modes, you can lock the keyboard by
simultaneously pushing on the and key, a appears.
To unlock, simultaneously push the and key ( disappears)
1. Function mode
2. Installer’s or user’s menu
3. Block number in programme mode Display
running programme in AUTO mode
4. Display of temperature, task, hour or title of the
parameter when “2” is indicated
5. The ambient temperature is indicated
6. Keyboard locked
7. Mode Auto
8. Temporary deviation
9. Cooling demand
10. Heating demand
11. Replace batteries
12. Days of the week
Quick Set-Up
Use the and keys to change the mode
1
2
3
Setting the Time and Day
Push : the hour blinks, then you can adjust
the hour by using the and keys, press
the key again: the day of the week blinks,
you can choose the day now by using the
and . For example: 1 = Monday
Push the key to validate your adjustments.
Choose a Programme for The Room
Push the key: the number of the current
programme blinks.
– You can choose a programme now by using
and . (P1 standard)
– By pressing the key, you can display the
programme in case of a built-in programme
(P1 to P5)
– The programme operates between the
temperatures Occupied Temperature (default
21°C) & The Setback Temperature (default 17°)
Built-in programmes descriptions.
(see details page 6)
P1: Morning, evening and weekend
P2: Morning, noon, evening and weekend
P3: 7h - 19h (office) evening and weekend
P4: Weekend (secondary house)
P5: 8h - 19h, Saturday (shop)
Set to Auto
Use the and keys to Auto Mode –
After a few seconds The Room Temperature and
Time will be displayed.
Programmable Room Thermostat
Operating Instruction – Display Operating Instructions of all Functions
Use the and keys to change the mode
FLOOR HEATING CONTROLS
HOT & COLD PLUMBING & HEATING SYSTEM
Mode HOLIDAYS
Use this function during a long absence
Use the keys and for controlling:
– The duration in hours «H» when it’s less than 24h or in days «d».
– The desired temperature for this period
(adjustable between 5°C and 35°C)
To exit the HOLIDAYS mode, set duration on «no».
1
2
3
4
567
8
9
10
11
12

Installing the Wet Room Sensor
(P23020)
Where time and temperature control
needs to be applied to a bathroom or
wet area, the wet area sensor can be
installed within the Wet Room and
connected to the programmable Room
Thermostat installed in an adjacent dry
area.
How can you create or change a user’s programme
(U1 or U2)
To programme the remaining days, repeat step «4» to «14» and
this for all the days of the week. *(You can only leave the
programme mode if all days have been filled in)
Once you have run through the whole programming, you only
have to put the Thermostat in the mode
Before, select one of the user’s programme’s U1 or U2 by using
and .
The Sensor can either remain in the
supplied housing and be wall mounted
or be removed from the housing and be
used as a floor surface sensor.
To Enable the Room Thermostat to
operate from the sensor you need to
enable the User menu.
Your Thermostat has two menus with
parameters:
To Enter these Menus go to and
keep the pressed.
The first Menu will show – 01
Keep pressed and the display will
show – 12
Use the key until
– 14 SENSOR Air.
Use to change to SENSOR FLor
The Wet Room Sensor is now being used.
You do NOT need to press but
keep pressing until – 29 END
then press .
As shown
12
34
56
78
910
11 12
13 14
15
Number of the
block during
the day
Starting hour
of the block Finishing hour
of the block
Temperature of the block
Identical days
or
Select the
number of
days to be
programmed
or
Adjust the
temperature
of the first
block
or
Adjust the
finishing hour
of the first
block
or
Adjust the
finishing hour
of the first
block
End of the day
Programme the remaining days
or
or
Adjust the final
temperature of
the second
block
or

Preset Program Times Programmable Room Thermostat
P1 Morning, Evening and Weekend
P2 Morning, Mid-day, Evening and Weekend
Preset Program Times Programmable Room Thermostat
P3 07·00 - 19·00 (Office)
P4 08·00 - 19·00 (Shop)
P5 Weekend (Second Dwelling)
P3,1 Monday 0 0 0 0 0 0 0 1 1 1 1 1 111111100000
P3,2 Tuesday 0 0 0 0 0 0 0 1 1 1 1 1 111111100000
P3,3 Wednesday 0 0 0 0 0 0 0 1 1 1 1 1 111111100000
P3,4 Thursday 0 0 0 0 0 0 0 1 1 1 1 1 111111100000
P3,5 Friday 0 0 0 0 0 0 0 1 1 1 1 1 111111100000
P3,6 Saturday 0 0 0 0 0 0 0 0 0 0 0 0 000000000000
P3,7 Sunday 0 0 0 0 0 0 0 0 0 0 0 0 000000000000
P4,1 Monday 0 0 0 0 0 0 0 0 1 1 1 1 11111110000
P4,2 Tuesday 0 0 0 0 0 0 0 0 1 1 1 1 111111100000
P4,3 Wednesday 0 0 0 0 0 0 0 0 1 1 1 1 111111100000
P4,4 Thursday 0 0 0 0 0 0 0 0 1 1 1 1 111111100000
P4,5 Friday 0 0 0 0 0 0 0 0 1 1 1 1 111111100000
P4,6 Saturday 0 0 0 0 0 0 0 0 1 1 1 1 111111000000
P4,7 Sunday 0 0 0 0 0 0 0 0 0 0 0 0 000000000000
P5,1 Monday 1 1 1 1 1 1 1 0 0 0 0 0 000000000000
P5,2 Tuesday 0 0 0 0 0 0 0 0 0 0 0 0 000000000000
P5,3 Wednesday 0 0 0 0 0 0 0 0 0 0 0 0 000000000000
P5,4 Thursday 0 0 0 0 0 0 0 0 0 0 0 0 000000000000
P5,5 Friday 0 0 0 0 0 0 0 0 0 0 0 0 011111111111
P5,6 Saturday 1 1 1 1 1 1 1 1 1 1 1 1 111111111111
P5,7 Sunday 1 1 1 1 1 1 1 1 1 1 1 1 111111111111
PROGRAM DAY 00:00 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00
P1,1 Monday 0 0 0 0 0 0 0 1 1 0 0 0 000001111110
P1,2 Tuesday 0 0 0 0 0 0 0 1 1 0 0 0 000001111110
P1,3 Wednesday 0 0 0 0 0 0 0 1 1 0 0 0 000001111110
P1,4 Thursday 0 0 0 0 0 0 0 1 1 0 0 0 000001111110
P1,5 Friday 0 0 0 0 0 0 0 1 1 0 0 0 000001111110
P1,6 Saturday 0 0 0 0 0 0 0 0 1 1 1 1 111111111110
P1,7 Sunday 0 0 0 0 0 0 0 0 1 1 1 1 111111111110
P2,1 Monday 0 0 0 0 0 0 0 1 1 0 0 0 110000111110
P2,2 Tuesday 0 0 0 0 0 0 0 1 1 0 0 0 110000111110
P2,3 Wednesday 0 0 0 0 0 0 0 1 1 0 0 0 110000111110
P2,4 Thursday 0 0 0 0 0 0 0 1 1 0 0 0 110000111110
P2,5 Friday 0 0 0 0 0 0 0 1 1 0 0 0 110000111110
P2,6 Saturday 0 0 0 0 0 0 0 0 1 1 1 1 111111111110
P2,7 Sunday 0 0 0 0 0 0 0 0 1 1 1 1 111111111110
The OFF times are night set back times and temperature (factory set at 17°C)
The ON times are comfort temperatures (factory set at 21°C)
The Frost protection setting (factory set at 6°C)
Clock Setting (Time of Day)
Program setting Mode (P1 - P5 plus U1 - U4 four user defined settings)
Automatic Operating Mode
Polypipe Building Products Broomhouse Lane, Edlington,
Doncaster, DN12 1ES,
United Kingdom.
Telephone: +44 (0) 1709 770000
Fax: +44 (0) 1709 770001
2410 London Road, Mount Vernon,
Glasgow, G32 8YB,
United Kingdom.
Telephone: +44 (0) 141 778 8822
Fax: +44 (0) 141 778 2703
Dromore Road, Lurgan, Craigavon,
Co. Armagh, BT66 7HL,
Northern Ireland.
Telephone: +44 (0) 2838 881270
Fax: +44 (0) 2838 882344
This manual suits for next models
3
Table of contents
Other Polypipe Heating System manuals
Popular Heating System manuals by other brands

Viessmann
Viessmann Vitotronic 200 KW2 operating instructions

BoilerMag
BoilerMag BM22 Installation & servicing instructions

Alnor
Alnor HRU-WALL user manual

Mitsubishi Electric
Mitsubishi Electric EHSC-VM6A Service manual

Velux
Velux CLI U12 SD0(W/L/F/P) 118 El B/U instruction manual

Aqua-Hot
Aqua-Hot 400 series Service manual

Salda
Salda RIS EKO 3.0 400 PE 0.9 MOUNTING AND INSTALLATION INSTRUCTION

ITR
ITR POLAR HD Installation and operating manual

OSTBERG
OSTBERG HERU S Operation & maintenance manual

Anda
Anda 443423 Installation, maintenance & user instructions

Samsung
Samsung AE050JXYDEH Service manual

STIEBEL ELTRON
STIEBEL ELTRON HSBC 300 cool Operation and installation