Potter VSA User manual

VSA-S
VAULT SOUND ALARM
SYSTEM
PAGE 1 OF 4
PRINTED IN USA MKT. #8870002 - REV L
8/02
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
UL Listed
Dimensions: 12 1/4"H x 8 3/8"W x 3 1/8"D
31,1cm H x 21,3cm W x 7,9 cm D
Weight: 8 lbs. (3,6 kg.)
Enclosure: 18 Gauge - Cold Rolled Steel
Power Input: 12VAC, 20VA, 60Hz
Operating Voltage: 6VDC
Typical Current: 20mA
Alarm Current: 25mA
Contact Ratings: Alarm Relay and
Tamper Switch
1.0 Amp at 28VDC
0.1 Amp at 130VDC
The Model VSA is a sound detection system listed by Underwriters’
Laboratories, Inc. for the primary protection of reverberant and non-
reverberant vaults such as bank and mercantile vaults.
Where U.L. certification is required, the VSA system must be installed in
compliance with U.L. 681. Including at least one manual initiating device
in the vault and connection of the VSA to a U.L. listed control unit.
The VSA amplifier unit is housed in a tampered steel cabinet with
provisions for conduit connections.
The standby battery provides in excess of 80 hours operation in the event
of a power failure. An external low voltage plug-in transformer maintains
the battery at a fully charged state.
The amplifier unit provides SPDT alarm relay contacts and provisions for
1 to 10 microphones to be connected into the supervised microphone
circuit.
The VSA contains a DC differential balance control which is adjusted so
that the impedance of the external microphone circuit is balanced with the
INSTALLATION - SEE FIGS. 1, 2, 3 AND 4
1. Mount VSA amplifier unit. (See Fig. 7 Suggested Wire Routing.)
2. Connect BLACK battery lead to NEGATIVE battery post.
3. Connect RED battery lead to POSITIVE battery post.
4. Plug in transformer to unswitched 110VAC outlet and apply 12VAC to
terminals 1 and 2 of VSA amplifier.
5. Mount microphones and wire according to installation drawing (see
Figs. 1, 2, 3, and 4).
Note: A PSM-T or PSM-FT (microphone with built-in test sounding
device) must be used in every installation.
6. See Fig. 1 for connection of remote test unit Model PTU-B and/or central
station test unit if applicable.
Note: Install jumper across terminals 12 and 13 if PTU-B is not used.
Maximum of 10 microphones on each VSA amplifier. Microphone
circuit not to exceed 1000 ft. of #22 gauge 2 conductor shielded cable.
Maximum loop resistance 1000 ohms. Battery must be charged for 48
hrs. before putting unit into service.
BALANCE ADJUSTMENT
1. Adjust sensitivity to full CCW position.
2. Monitor balance adjustment jacks on circuit board with 20K ohms per
volt meter set on 10VDC scale.
3. Jumper terminals 4 and 5 on VSA unit. Note meter reading (4.2 to 5.2
volts).
4. Remove jumper from terminals 4 and 5.
5. Adjust balance control to half of previous voltage reading (2.1 to 2.6
volts)
6. If balance control will not adjust to this reading, check wiring for open
shorts or grounds.
SENSITIVITY ADJUSTMENT
1. Adjust the SENSITIVITY control to approximately 1/3 scale.
2. Strike the vault surface with a plastic mallet and adjust the SENSITIV-
ITY control to provide desired protection.
CAUTION: EXTREME CARE SHOULD BE EXERCISED SO THAT THE
PROTECTED SURFACES ARE NOT MARRED OR DAMAGED WHILE
PERFORMING THE ATTACK TESTS.
TESTING
Pressing test button on front of VSA amplifier applies test signal to
sounding device in PSM-T or PSM-FT, causing the VSA to go into the
alarm condition, which is indicated by a RED LED adjacent to the test
button (RED LED will not indicate when sensitivity is set at 2 or below).
If system will not test properly, increase sensitivity control setting until
reliable manual tests are obtained.
Verify that reliable tests are obtained at remote test unit Model PTU-B and/
or from central station test unit if utilized.
The subscriber must be instructed to test the system each time the alarm
is set per instructions on front of VSA amplifier unit.
internal impedance of the differential circuit. The VSA will alarm if the
external impedance of the microphone circuit increases or decreases.
The microphones are available in surface mount (Model PSM) or flush
mount (Model PSM-F). Audio signals detected in the vault enclosure are
fed to the amplifier unit where the sensitivity control determines the sound
level necessary to alarm the unit.
The Models PSM-T (surface mount) and PSM-FT (flush mount) are
microphones with a built-in test sounding device. One PSM-T or PSM-FT
must be used in every application.
An alarm indicator light and test switch are provided for system testing by
the subscriber. Terminals are provided for remote subscriber and/or
central station testing.
The Model APC (Accumulating Pulse Counter) is a plug-in option which
allows the system to alarm after receiving a set number of pulses during
a 10 minute time frame. The pulse counter has an adjustable range of 1
to 9 pulses (see page 4).

PAGE 2 OF 4PRINTED IN USA MKT. #8870002 - REV L
8/02
VSA-S
VAULT SOUND ALARM
SYSTEM
FIG. 2 VSA SOUND ALARM SURFACE MOUNTED MICROPHONES
FIG. 1 VSA INSTALLATION

VSA-S
VAULT SOUND ALARM
SYSTEM
PAGE 3 OF 4
PRINTED IN USA MKT. #8870002 - REV L
8/02
VSA SOUND ALARM FLUSH MOUNTED MICRO-
PHONES
FIG. 6 EXAMPLE
MODEL APC ACCUMULATION PULSE COUNTER
The Accumulation Pulse Counter, Model APC, is a plug-in option designed
for applications where extraneous sound levels penetrating the vault
environment may cause false alarms.
The function of the APC option is to allow the system to detect and
accumulate sound energy over a period of time and to cause an alarm
condition when sufficient energy has been detected. When used with the
APC, the purpose of the VSA is to detect a single noise of high energy
content. For this reason, the APC should be adjusted such that it is more
sensitive than VSA. An amber LED on the APC indicates when a noise
pulse has been counted.
The pulse counter control is adjustable from 1 to 9. This adjustment
determines the number of pulses required, during a 10 minute time frame,
to alarm the unit.
FIG. 5
Point A - Pulse level exceeds counter threshold and accumulates.
Point B - New 10 minute time frame starts. Previous pulses erased.
Point C - Pulse below counter threshold does NOT accumulate.
Point D - Pulse accumulates
Point E - Pulse does NOT accumulate
Point F and G - Pulses accumulate
Point H - 10 minute time frame ends with 3 pulses accumulated.
If pulse counter was set at 3 or below, the unit would have
alarmed. If pulse counter was set at 4 or above, no alarm would
have been received and the 3 accumulated pulses erased.
IF A SINGLE PULSE EXCEEDS THE ALARM THRESHOLD THE UNIT
WILL ALARM.
TYPICAL MICROPHONE
LAYOUTS
FIG. 4
FIG. 3

PAGE 4 OF 4PRINTED IN USA MKT. #8870002 - REV L
8/02
VSA-S
VAULT SOUND ALARM
SYSTEM
ORDERING INFORMATION
VSA-S Vault Sound Alarm System (Surface Mount) consists of:
Qty. Comp. No. Description
1 2000103 VSA - Amplifier with housing
1 5270080 Transformer 12V, 20VA
1 5130080 Battery 6V, 4 AH
2000008 PSM - Microphone (Surface Mount)
(45 ohm impedance)
1 2000041 PSM-T - Microphone with
Test Sounding Device
Additional Items Available:
Qty. Comp. No. Description
1 2000008 PSM - Microphone (Surface Mount)
1 2000034 PSM-F - Microphone (Flush Mount)
(Includes back box)
1 5090008 Back Box for PSM-F
1 2020121 PTU-B - Remote Test Unit
1 5090033 Back Box for PTU-B
1 2009103 VSA - Less housing/PCB only
1 2000106 APC - Accumulation Pulse Counter
*2020130 HUB-M - Single Action hold up Button
*2020132 HUB-T - Double Action hold up Button
Note: *- At least one of either hold up button is required in the vault
for U.L. installation.
APC SENSITIVITY ADJUSTMENT
1. Set the VSA sensitivity control to 0.
2. Set the APC pulse counter switch to the desired number (1 thru 9).
3. Install the APC and produce the minimum noise level which the
APC is to detect. Adjust the APC sensitivity such that the yellow
LED light blinks each time this noise is produced (disregard the red
alarm light at this time).
4. Unplug and remove the APC.
5. Produce the minimum noise level at which the VSA should alarm
and set the VSA sensitivity control such that the red alarm LED
comes on each time this noise is produced. This noise level should
be much more intense than that used to set the APC sensitivity.
6. Re-install the APC.
TESTING
Slowly pulse the noise used to adjust the APC sensitivity control until
the VSA indicates alarm (illuminated red LED) on the VSA unit. The
counter in the APC is now reset to 0.
Slowly pulse this noise again. When the number of pulses equals the
switch setting on the APC, the VSA will indicate alarm. This verifies
that both the VSA and APC are operating properly at the desired noise
level.
FIG. 7 SUGGESTED WIRE ROUTING
This manual suits for next models
1
Other Potter Security System manuals

Potter
Potter PDC Series User manual

Potter
Potter LED-16F User manual

Potter
Potter PFC-4410G3 User manual

Potter
Potter LED-16 Series User manual

Potter
Potter MHT-1224 Series User manual

Potter
Potter RA-6075R User manual

Potter
Potter DCM-4 User manual

Potter
Potter LED-4410G3 User manual

Potter
Potter Amseco SSX-81 User manual
Popular Security System manuals by other brands

GE
GE Interlogix 60-875 Simon installation instructions

Defender
Defender SENTINEL 3 instruction manual

Kingdun Electronic
Kingdun Electronic KD-122LA user manual

DAITEM
DAITEM Espace range user guide

Labkotec
Labkotec idOil-20 Installation and operating instructions

Ampac
Ampac EvacUwiz MAN3084-0 Programming manual