Power Inspired VFI1000QS User manual

VFI1000QS
Online Double Conversion
Silent
UPS System
Version: 1.0
User Manual

Table of Contents
1. Important Safety Warning................................................................................. 1
1.1. Transportation .................................................................................................. 1
1.2. Preparation ...................................................................................................... 1
1.3. Installation ....................................................................................................... 1
1.4. Operation......................................................................................................... 1
1.5. Maintenance, service and faults ......................................................................... 2
2. Principles Of Operation. ..................................................................................... 3
2.1. Protection Features........................................................................................... 3
2.2. Functional Description....................................................................................... 3
2.3. Cooling ............................................................................................................ 4
3. Installation and setup........................................................................................ 5
3.1. Packaging Contents .......................................................................................... 5
3.2. Battery Tray Connection .................................................................................... 5
3.3. Rear panel view................................................................................................ 6
3.4. Rack-mount / Horizontal Installation .................................................................. 6
3.5. Tower Installation ............................................................................................. 7
3.6. UPS Location .................................................................................................... 7
3.7. UPS Connections............................................................................................... 8
3.8. Starting Up the VFI1000QS ............................................................................. 10
3.9. Start up on battery (cold start) ........................................................................ 10
3.10. Switching off the UPS................................................................................... 10
3.11. Install software (Optional)............................................................................ 10
3.12. Battery Replacement.................................................................................... 11
3.13. Battery Kit Assembly .................................................................................... 12
4. Operations........................................................................................................ 13
4.1. Button operation............................................................................................. 13
4.2. LCD Panel ...................................................................................................... 14
4.3. Audible Alarm ................................................................................................. 15
4.4. LCD display wordings index ............................................................................. 15
4.5. UPS Setting .................................................................................................... 17
4.6. Operating Mode Description ............................................................................ 22
4.7. Faults Reference Code..................................................................................... 23
4.8. Warning indicator ........................................................................................... 23
5. Troubleshooting ............................................................................................... 24
6. Storage and Maintenance ................................................................................ 26
7. Specifications ................................................................................................... 27
8. Limited Factory Warranty ................................................................................ 29
9. Contact ............................................................................................................. 29

1
Please comply with all warnings and operating instructions in this manual. Save this manual
and read carefully the following instructions before installing the unit. Do not operate this unit
before reading through all safety information and operating instructions.
Please transport the UPS system only in the original packaging to protect against shock
and impact.
Condensation may occur if the UPS system is moved from a cold to a warm environment.
Please allow at least two hours for the UPS system to acclimatise to the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or heat.
Do not block ventilation holes in the UPS housing.
Do not connect appliances or devices which would overload the UPS system (e.g. laser
printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances, such as hair dryers, to UPS output sockets.
Connect the UPS system only to an earthed outlet which should be easily accessible and
close to the UPS system.
Use supplied input mains cord.
Please use only BS Kite marked, VDE-tested and/or CE marked power cables to connect
the loads to the UPS system.
When installing the equipment, ensure that the sum of the leakage current of the UPS and
the connected devices does not exceed 3.5mA.
Temperature Rating - Units are considered acceptable for use in a maximum ambient of
40°C (104°F), however at higher temperatures, unit derating may be required and battery
service life will be diminished.
Ensure the unit has adequate ventilation to the front and rear of the unit.
Do not disconnect the mains cable on the UPS system or the building wiring outlet whilst
the UPS is in operation since this would cancel the protective earthing of the UPS system
and of all connected loads.
The UPS system features its own internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not
connected to the building outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to switch off
the UPS (note bypass may be active).
1. Important Safety Warning
1.1. Transportation
1.2. Preparation
1.3. Installation
1.4. Operation

2
Ensure no fluids or other foreign objects can enter the UPS system.
The UPS system operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery
and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and
verify that no current is present and no hazardous voltage exists in the terminals of high
capability capacitor such as BUS capacitors.
Only persons that are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Caution - risk of electric shock. The battery circuit is not isolated from the input voltage.
Hazardous voltages may occur between the battery terminals and the ground. Before
touching, please verify that no voltage is present!
Caution - Do not dispose of batteries in a fire. The batteries may explode.
Caution - Do not open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
Batteries may cause electric shock and have a high short-circuit current. Please take the
precautionary measures specified below and any other measures necessary when working
with batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source and load prior to installing or maintaining the battery.
Remove battery grounds during installation and maintenance to reduce likelihood
of shock. Remove the connection from ground if any part of the battery is
determined to be grounded.
When changing batteries, install the same number and same type of batteries or battery
packs.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
WARNING: This is a category C2 UPS product. In a residential environment, this product
may cause radio interference, in which case the user many be required to take additional
measures.
WARNING: Changes or modifications not expressly approved by the party responsible
for compliance could void the user's authority to operate the equipment.
1.5. Maintenance, service and faults

3
The VFI1000QS is a true online double conversion UPS System providing the highest degree of
power protection for your load.
Blackouts
In the event of a power cut, the VFI1000QS
will seamlessly transfer to battery power.
This is true “no-break” with zero transfer
time.
Sags
Spikes
Under
Voltage
Over
Voltage
The output remains constant regardless of
what is happening at the input. Momentary
sags and spikes are effortlessly taken care of.
Prolonged under and over voltages do not
require the VFI1000QS to enter into battery
mode due to its wide input voltage window.
Noise
Transients
Harmonics
Distortions on the input mains voltage are
not transferred to the load. The load is
powered from the UPS inverter at all times,
which is “ReGenerating” a new AC power
waveform clean of any power contaminants
on the input.
Frequency
The VFI1000QS can be set to frequency
conversion mode, with a fixed output
frequency. This means that in situations
where the input frequency may be unstable,
for example when on generator power, the
load still receives the required voltage and
frequency.
The UPS is composed of mains input, EMI/RFI filters, rectifier/PFC, inverter, battery charger,
DC-to-DC converter, battery, dynamic bypass and UPS output.
2. Principles Of Operation.
2.1. Protection Features
2.2. Functional Description

4
These are represented by a graphic on the LCD:
The rectifier converts the incoming AC power into DC. In doing so, surge suppressors
and filters remove any noise and damaging surges. The rectifier is Power Factor Corrected
(PFC) which means the UPS presents itself as a purely resistive load, ensuring the UPS has no
detrimental effects on power quality elsewhere in the building. The rectifier performs two
functions. The first is to provide the DC for the inverter, and the second is to provide a charging
voltage (and current) for the battery.
The battery has two circuits connected to it. The first is the charger that has an
adjustable battery charge current to allow extra battery packs to be connected without
compromising on recharge time. The second is a DC-DC converter that converts the battery DC
voltage to the DC bus voltage to feed the inverter when running on battery operation.
The inverter converts the DC bus voltage into the AC output voltage. It is a high
frequency, highly efficient design that utilizes PWM driven IGBTs to create a pure sine wave
output via the output low pass filter. The output voltage is constantly monitored and adjusted
for differing load levels to maintain a highly stable output. The voltage can be adjusted
depending upon requirements.
See section 4.6 for details of operating modes and graphical representation on the LCD.
The VFI1000QS utilises Power Inspired’s propriety Advanced Speed
Control (ASC) cooling system. Utilising super quiet fans the fan
speed is set according to actual cooling requirements. Thus, at low
loads and temperatures the fans will run at low speeds making the
units practically inaudible. This makes the VFI1000QS suitable for
applications where the highest degrees of power quality and
protection are required but where unit silence is paramount.
2.3. Cooling

5
The unit packaging comprises the following:
VFI1000QS Silent UPS System
Vertical support brackets
Left & Right Rack Ears and affixing screws
Input Mains Lead
Product Manual
Software CD & USB lead
Rubber Feet x4
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original packaging in a safe place for future use.
For safety the UPS is shipped out from the factory without connecting the battery. Before
installing the UPS, please follow below steps to connect the battery.
Step 1
Step 2
Step 3
Remove front panel.
Connect the DC input and
battery connector.
Refit the front panel.
3. Installation and setup
3.1. Packaging Contents
3.2. Battery Tray Connection

6
Schuko Type UK Type
❶Programmable outlets: connect to non-critical loads
❷Output receptacles: connect to mission-critical loads
❸AC input
❹Network/Fax/Modem surge protection
❺USB communication port
❻RS-232 communication port
❼SNMP / Relay Card intelligent slot
❽Emergency power off function connector (EPO)
❾External battery connection
This UPS can be either rack (horizontal) or tower (vertical) mounted. Please choose proper
installation to position this UPS.
Step 1
Step 2
Fit the rack ears observing left (marked L) and
right (marked R) positions when looking at the
unit.
When in a rack the VFI1000QS must be
supported by a shelf or rack rails / sliders.
Adjustable rack sliders are available as an
option.
The VFI1000QS can be positioned horizontally on a desk or similar. Rubber feet have been
provided to avoid surface scratching. Position these on the base of the unit toward the corners.
Note when in horizontal placement the UPS should be placed off the floor to avoid excessive
dust ingress.
3.3. Rear panel view
3.4. Rack-mount / Horizontal Installation

7
Step 1
Step 2
Step 3
Make up the vertical
support brackets
Carefully position the UPS in the
support brackets. Pop out the LCD and
rotate into vertical orientation if
required.
Note the LCD should be
at the top.
1. The UPS should be placed on a flat surface. Place it in an area away from vibration, dust,
humidity, high temperature, flammable liquids, gases, corrosive and conductive
contaminants. Install the UPS indoors in a clean environment. Do not operate the unit
whilst still in its box or packaging.
2. Maintain an ambient temperature range of 15ºC to 25ºC for optimal operation. For every
2ºC above 30ºC, the UPS will need to be derated by 10% of nominal capacity at full load.
The highest working temperature requirement for UPS operation is 40ºC. Note
temperatures above 30ºC have a detrimental effect on battery float life.
3. It’s required to maintain a maximum altitude of 1000m to keep UPS normal operation at full
load. If it’s used in high altitude area, please reduce connected load. Altitude derating
power with connected loads for UPS normal operation is listed as below:
Altitude
(m)
Derating
Factor
Altitude
(m)
Derating
Factor
Altitude
(m)
Derating
Factor
1000
1.00
2500
0.86
4000
0.74
1500
0.95
3000
0.82
4500
0.70
2000
0.91
3500
0.78
5000
0.67
3.5. Tower Installation
3.6. UPS Location

8
4. Ventilation:
The UPS is equipped with a fan for cooling. Therefore, place the UPS in a well-ventilated
area. It’s required to maintain minimum clearance of 100mm in the front of the UPS and
300mm in the back of the UPS for heat dissipation and easy-maintenance. Maintain
minimum clearance of 100mm in the bottom of the UPS to avoid dust ingress and adequate
air intake (Horizontal orientation only).
3.7.1.
External battery connection
Follow the procedure in the external battery cab manual.
3.7.2.
UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords. The power cord is supplied in the UPS package. In the UK, circuit protection is provided
via the plug fuse, in other areas ensure that the circuit feeding the VFI1000QS has over current
protection in place not exceeding 16A (e.g. a circuit breaker).
Note: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when
the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting
section).
3.7.3.
UPS output connections
There are two kinds of outputs: programmable outlets and general outlets. Please connect
non-critical devices to the programmable outlets and critical devices to the general outlets.
During power failure, you may extend the backup time to critical devices by setting shorter
backup time for non-critical devices.
Note that the programmable outlet feature is an option in settings (Section 4.5 –09 ) and if
disabled the programmable outlets operate the same as the general outlets, and therefore you
can connect critical loads to both sockets.
Do not connect any power cord to the output of the UPS that is in excess of 10m. This is to
ensure compliance with EMC regulations.
3.7. UPS Connections

9
3.7.4.
Communication connection
Communication ports:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the
communication cable to the USB/RS-232 port and the other to the communication port of your
PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and
monitor UPS status through PC. The USB port is Human Interface Device (HID) compliant
which allows the UPS to have basic communication with Windows or MAC operating systems
directly without the need to install software.
The UPS is equipped with intelligent slot for optional SNMP or AS400 relay cards. These cards
will provide advanced communication and monitoring options. To fit the card remove the two
screws securing the Intelligent Slot cover. Locate the card in the location grooves in the
housing and slide into place. The card will need a gentle push to fully engage. Ensure the card
is properly located within the grooves in the housing before attempting to fully engage.
3.7.5.
Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected
“IN” outlet on the back panel of the UPS unit. Connect from
“OUT” outlet to the equipment with another modem/fax/phone
line cable. Note this is a connection for protecting against “back-door” surges on network
cables. It is a passive circuit and provides no network function.
3.7.6.
Emergency Power Off (EPO) function
The VFI1000QS is equipped with Emergency Power Off (EPO) function. The EPO port is located
on the rear panel (refer to section 3.3 Rear Panel) and consists of a plug and socket
arrangement. When shipped the factory default is to have the plug fitted with a shorting link
and this is inserted and screwed to the socket. To use the EPO function, remove the plug and
shorting link, connect to your preferred EPO scheme and reconnect the plug to the UPS.
If the EPO function is not to be used leave the
plug in-situ.
Note: The EPO function logic can be set up via
LCD setting. Please refer to program 16 in UPS
setting for the details.

10
1. Apply mains power to the unit.
The unit is equipped with ultra quiet cooling fans controlled by Power Inspired’s ASC
controller. When power is first applied, in order to ensure proper fan start up, the fans will
spin up to full speed and hold for several seconds before reverting to a quiet low speed
setting. See troubleshooting if the fans remain at high speed.
2. Make changes to the UPS settings if required. See section 4.
3. Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period, however the VFI1000QS
can be used normally.
The unit can be used to provide power from a switched off status with no mains power
available (providing adequate battery charge).
1. Press the ON/Mute button on the front panel for two seconds to power on the UPS.
2. The unit will start up in battery mode.
1. Press and hold the OFF/Enter button for at least 2 seconds to turn off the UPS.
2. The UPS will enter standby or bypass mode if AC power is present, or switch off if
switched off when in battery mode.
For optimal computer system protection, install the UPS monitoring software to fully configure
UPS and PC shutdown. Use supplied RS-232 or USB communication cable to connect
RS-232/USB port of UPS and RS-232/USB port of PC. Then, follow below steps to install
monitoring software.
1. Insert the included installation CD into CD-ROM drive and then follow the on-screen
instructions to proceed software installation. If there no screen shows 1 minute after
inserting the CD, please execute setup.exe file for initiating software installation.
2. Follow the on-screen instructions to install the software.
3. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
Note the USB port is HID (Human Interface Device) compliant. This means in can
communicate directly with Windows and MAC O/S power management without the need to
install the software.
3.8. Starting Up the VFI1000QS
3.9. Start up on battery (cold start)
3.10. Switching off the UPS.
3.11. Install software (Optional)

11
NOTICE: This UPS is equipped with internal batteries that the user can replace without
shutting down the UPS or connected loads (hot-swappable battery design). Replacement is a
safe procedure, isolated from electrical hazards.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries.
Note: Upon battery disconnection, equipment is not protected from power outages.
Step 1
Step 2
Step 3
Remove front panel.
Disconnect battery wires.
Pull out the battery box by
removing two screws on the
front panel.
Step 4
Step 5
Step 6
Remove the top cover of
battery box and replace the
inside batteries.
After replacing the
batteries, put the battery
box back to original location
and screw it tightly.
Re-connect the battery wires.
Step 7
Put the front panel back to the unit.
3.12. Battery Replacement

12
NOTICE: Please assemble battery kit first before installing it inside of UPS.
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by
following below diagram.
Step 3: Put assembled battery packs on
one side of plastic shells.
Step 4: Cover the other side of plastic shell as
below.
3.13. Battery Kit Assembly
Tapes
Tapes

13
Button
Function
ON/Mute
Button
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to
turn on the UPS.
Mute the alarm: With the UPS in battery mode, press and hold this button
for at least 3 seconds to disable or enable the alarm system. This does
not apply to situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press ON/Mute buttons for 3 seconds to
enter UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter
Button
Turn off the UPS: Press and hold this button at least 2 seconds to turn off
the UPS. UPS will be in standby mode under power normal or transfer to
Bypass mode if the Bypass enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS
setting mode.
Select
Button
Switch LCD message: Press this button to change the LCD message for
input voltage, input frequency, battery voltage, output voltage and
output frequency.
Setting mode: Press and hold this button for 3 seconds to enter UPS
setting mode when in Standby or Bypass mode.
Down key: Press this button to display the next selection in UPS setting
mode.
ON/Mute
+ Select
Button
Switch to bypass mode: When the main power is normal, press ON/Mute
and Select buttons simultaneously for 3 seconds. Then UPS will enter to
bypass mode. This action will be ineffective when the input voltage is out
of acceptable range.
Exit setting mode or return to the upper menu: When working in setting
mode, press ON/Mute and Select buttons simultaneously for 0.2 seconds
to return to the upper menu. If it’s already in top menu, press these two
buttons at the same time to exit the setting mode.
4. Operations
4.1. Button operation

14
Display
Function
Backup time information
Indicates the estimated backup time.
H: hours, M: minute, S: second.
Configuration and fault information
Indicates the configuration items, and the configuration items are listed in
details in section 4-5.
Indicates the warning and fault codes, and the codes are listed in details in
section 4-7 and 4-8.
Mute operation
Indicates that the UPS alarm is disabled.
Output & Load information
Indicate the input voltage, input frequency, input current, battery
voltage, battery current, battery capacity, ambient temperature, output
voltage, output frequency, load current and load percent.
k: kilo, W: watt, V: voltage, A: ampere, %: percent, ℃: degree centigrade, Hz: frequency
Load information
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
Indicates overload.
Programmable outlets information
Indicates that programmable management outlets are working.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
4.2. LCD Panel

15
Display
Function
Indicates charging status
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the AC to DC circuit is working.
Indicates the inverter circuit is working.
Indicates the UPS is working in converter mode
Indicates the output is working.
Battery information
Indicates the battery level by 0-24%, 25-49%, 50-74%, and 75-100%.
Indicates low battery.
Battery Mode
Sounding every 5 seconds
Low Battery
Sounding every 2 seconds
Overload
Sounding every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
HLS
High loss
LLS
Low loss
BAT
Battery
BAH
Battery AH
CHA
Charger current
CBV
Charger boost voltage
CFV
Charger float voltage
EPO
EPO
AO
Active open
AC
Active close
4.3. Audible Alarm
4.4. LCD display wordings index

16
Abbreviation
Display content
Meaning
OIT
Output isolation transformer
EAT
Estimated autonomy time
RAT
Running autonomy time
CF
Converter
ON
ON
SD
Shut down
OI
Over input current
EP
EPO
TP
Temperature
CH
Charger
FU
Bypass frequency unstable
BR
Battery Replace
EE
EEPROM error

17
There are two parameters to set up the UPS.
Parameter 1: Setting ID. Refer to below table.
Parameter 2: Options values for each setting.
01: Output voltage setting
Interface
Setting
Parameter 3: Output voltage
You may choose the following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2: Enable or disable converter mode. You may
choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
04: ECO enable/disable
Interface
Setting
Parameter 2: Enable or disable ECO function. You may
choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
4.5. UPS Setting

18
05: ECO voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
low voltage point for ECO mode by pressing Down key or Up
key.
HLS: High loss voltage in ECO mode in parameter 2.
The setting range in parameter 3 is from +7V to +24V of the
nominal voltage. (Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
The setting range in parameter 3 is from -7V to -24V of the
nominal voltage.
(Default: -12V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2: Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high voltage point
230-264: setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
Table of contents
Other Power Inspired UPS manuals

Power Inspired
Power Inspired VFI-C Series 1KR User manual

Power Inspired
Power Inspired Willo User manual

Power Inspired
Power Inspired iPower-DC2 User manual

Power Inspired
Power Inspired VIX3065 User manual

Power Inspired
Power Inspired VFI6KT User manual

Power Inspired
Power Inspired VIX2060 User manual

Power Inspired
Power Inspired VIS0750 User manual