
Installaon & Operang Instrucons for
MA24 & MA115 Series Remote Alarm Systems
Powerex • 150 Producon Drive • Harrison, OH 45030 •USA
T 1.888.769.7979 • F 513.367.3125 • www.powerexinc.com
IN596400AV • 01/2016
Page 2 of 4
Introducon
Powerex remote alarms are designed to aach to Powerex
manifold systems or to pressure switches. They signal an alarm
condion is present.
A typical alarm setup signals when pressure in the supply
cylinders of a manifold goes below a set point, indicang the
cylinders need replacing.
All of the Powerex Remote Alarm models acvate when the
control circuit opens. The open circuit signals an alarm condion.
A closed circuit indicates a system normal condion.
Powerex manufactures the six remote alarm models shown
below.
PX-MA24-1V PX-MA115-1V
PX-MA24-1AV PX-MA115-1AV
PX-MA24-2AV PX-MA115-2AV
Model Descripons
The PX-MA24 models require a 24 VAC power source. These
models are designed to aach to a Powerex automac or
semiautomac switchover manifold. The 24 VAC power comes
from the power supply provided with the manifold control box
(Part # PX-1118-0100). The power supply box also contains dry
contacts which are acvated by pressure switches inside the
manifold control box. When these dry contacts are connected to
the Powerex PX-MA24 remote alarm, the alarm gives a visual or
audio/visual indicaon of a low supply gas condion.
The PX-MA115 models are designed to connect to 115 VAC.
These units have an internal transformer and an external six (6)
foot power cord that terminates in a stan dard two-prong 115
VAC plug. These units are designed to aach to any pressure
switch(es) on any manifold system to signal an alarm condion.
The 115 VAC models all ulize 12 VAC internal power to sense the
open or closed condion across the pressure switch.
The PX-MA24-1V and PX-MA115-1V models (Figures 1 and 2)
have provisions for connec on to a single manifold or pressure
switch. The 1V models have a single set of lights to indicate
the low pressure condion. The set of lights consist of a green
“System Normal” and a red “Bank Depleted” light. The “System
Normal” light is acvated as long as the manifold or pressure
switch circuit is in a closed condion and power is supplied to
the alarm box. When the alarm circuit opens, the green “’System
Normal” light goes out and the red “Bank Depleted” light goes
on.
The PX-MA24-1AV and PX-MA115-1AV models (Figures 3 and 4)
have provisions for con necon to a single manifold or pressure
switch. The 1AV models have a single set of lights and a buzzer
that sounds to signal that an alarm condion is present. The
single set of lights consists of a green “System Normal” and a red
“Bank Depleted” light There is a squelch buon on the front of
the 1AV panel. Pushing the squelch buon stops the buzzer. The
buzzer automacally resets when the normal condion resumes.
The PX-MA24-2AV and PX-MA115-2AV models (Figures 5 and 6)
have provisions to aach to two manifolds or pressure switches.
The 2AV models have two sets of lights, each set aached to a
dierent manifold sensor. Each set of lights consists of a green
“System Normal” and a red “Bank Depleted” light.
The 2AV models also have one buzzer which sounds when either
bank reaches an alarm condion. Like the 1AV models, the 2AV
has a squelch buon that silences the buzzer when pushed. The
buzzer automacally resets when the normal condion resumes.
Figure 1: PX-MA24-1V Figure 2: PX-MA115-1V
Figure 3: PX-MA24-1AV Figure 4: PX-MA115-1AV
Figure 5: PX-MA24-2AV Figure 6: PX-MA115-2AV