Set number of sensors
Set length of extension time
Set quick mode ON or OFF
Set user access to front buttons
Set optimum stop temperature
Set constant fan ON or OFF
Set Hi/Low differential*
*When applicable
iew run log
Set power & cost parameters
Set service date parameters
Set new extended menu password
Restricted access
6 15
Installation
IMPORTANT
The Eurotrol 2 or sensor MUST NOT be sited in areas of high electromagnetic fields,
i.e. distribution boards, transformers or heavy duty supply cables.
Eurotrol 2
Siting of the Eurotrol 2 is important in that it must be fitted where the temperature
will be generally representative of the area to be heated. It should be installed 1.7m
above floor level and away from draughty areas or areas subjected to direct heat
from sunlight, radiators etc. (Unless a remote sensor is being used)
Remote sensor (optional
The siting of the Eurotrol 2 should be no greater than 100m from the sensor and
should be in a position easily accessible for programming and control. Siting of the
sensor is important in that it must be fitted where the temperature will be generally
representative of the area to be heated. It should be installed 1.7m above floor level
and away from draughty areas or areas subjected to direct heat from sunlight,
radiators etc.
Fixing
For fixing into wood use No.8 x 1¼ woodscrews, on masonry use screws together
with wallplugs and on metal use M5 machine screws.
Remote sensor (optional
Remove cover and offer the sensor up to the intended mounting position and mark
two fixing holes. Fix sensor base plate to the wall.
See connection diagrams on page 16
Eurotrol 2
Remove the two screws from the terminal cover and remove. Offer the unit up to
the intended mounting position and mark the location of the three fixing holes using
the template on the packaging box Secure the top fixing leaving approximately 5mm
protruding, hang the Eurotrol 2 on the top fixing screw, line up the bottom fixing holes
and secure using two screws.
Electrical Connections
IMPORTANT
Wiring external to the Eurotrol 2 must be installed in accordance with I.E.E. Regulations
together with any local regulations which may apply. Wiring should be completed
in conduit, entry for which is provided in the bottom of the unit. See external wiring
diagram Mains supply and control circuit wiring should be completed in cables not
less than 0.5mm² and fan circuit in not less than 1.5mm². The connection to the
mains electrical supply can be taken from the appliance or a separate local supply,
but in both cases a local isolator must be fitted adjacent to the Eurotrol. Should
more than one appliance be controlled from one Eurotrol 2 a relay box MUST BE
USED.
WARNING - SENSOR WIRING
Sensor cable must be screened two core and a minimum of 0.6mm² if solid and 7
x 0.2mm² if multistrand. The screen must be grounded only at the Eurotrol 2. Wiring
for the temperature sensor MUST BE RUN SEPARATELY and apart from ALL other
wiring. Failure to regard this instruction may cause the Eurotrol 2 to malfunction
and may render it faulty.
e
e
e
e
e
e
e
e
e
e